Unitary Products Group 23

FIGURE 7 - UNIT DIMENSIONS (REAR VIEW)

FIGURE 8 - DISCONNECT/BLOWER ACCESS

LOCATION

TABLE 22: UTILITIES ENTRY

HOLE OPENING SIZE (DIA.) USED FOR
A7/8” KO1
1. Opening in the bottom to the unit can be located by the
side in the insulation.
Control Wi ring2
2. Do not remove the 2” knockout ring.
Side
Bottom
B2” KO1Power Wiring Side
Bottom
C1-5/8” KO Gas Piping (Front)
D1-1/2” KO Gas Piping (Bottom)
DISCONNECT SWITCH LOCATION
AND MOTOR ACCESS PANEL FOR
UNIT WITH “BELT-DRIVE” OPTION
CONTROL BOX
ACCESS
A,B
WIRING ENTRY
(See Detail “B”)
MOUNTING BRACKET
FOR DICONNECT SWITCH
(Shipped attached to the
blower housing inside
the blower compartment)
FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION
BLOWER MOTOR
ACCESS
FILTER
ACCESS
DOT PLUGS

TABLE 23: MINIMUM CLEARANCES

LOCATION CLEARANCE
Front 24” (Cooling/Electric Heat)
32” (Gas Heat )
Rear 12” (Less Economizer)
36” (With Economizer or Fixed
Air/Motorized Damper)
Left Side (Filter Access) 24” (Less Economizer)
36” (With Economizer)
Right Side (Cond. Coil) 24”
Below Unit10”
Above Unit272” (For
Condenser Air Discharge)
1. Units may be installed on combustible floors made
from wood or class A, B, or C roof covering material.
2. Units must be installed outdoors. Overhanging struc-
tures or shrubs should not obstruct condenser air dis-
charge outlet.