254599-YTG-C-0807
Unitary Products Group 15
TYPICAL POWER WIRINGTYPICAL CONTROL WIRING

FIGURE 2 - TYPICAL FIELD POWER & CONTROL WIRING

REFERTO THE ELECTRICAL DATATABLESTOSIZE TH E DISCONNECTSWITCH,OVERCURRENT PROTEC-TIONAND WIRING.RVYCGFRY1CY2
THERMOSTAT
1
TERMINALS
UNIT TERMINAL
STRIPT B1
24 VOLT
TRANSFORMER
COOLING ONLY (24 VOLT THERMOSTAT)
1
24 VOLTTHERMOSTAT 2TH07701024. TO CONTROLTHE ECONOMIZERON SECOND STAGE COOLING, USE THETHERMOSTAT 2TH0401224.G
RC
RH
Y1
Y2
W1
W2
G
LED1
LED2
COM
A1
A2
T
T
B
R
Y1
Y2
G
C
X
OCC
W2
W1
THERMOSTAT
1
TERMINALS UNIT TERMINALSTRIP TB1 24 VOLTTRANSFORMERTO REMOTE SENSOR2TH040702224 IF USEDNOTUSEDADDJUMPERADDJUMPER
4
4
3
2
1
ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET04700224 (INCLUDES SUBBASE).
2
SECOND STAGE COOLING IS NOT REQUIRED ON UNITS LESS ECONOMIZER.
3
SECOND STAGE HEATING IS ONLY REQUIRED ON UNITS WITH A TWO STAGE ELECTRIC HEATER OR 2 STAGE GAS HEAT.
4
COOLING / HEATING (ELECTRONIC THERMOSTAT)MULTI STAGE
REMOVE JUMPER J2 FROM TERMINALS 4 AND 9 ON JUMPER PLUG CONNECTOR
P6 ON UNITS WITH ECONOMIZER. TERMINALSA1AND A2 PROVIDE A RELAY
OUT-PUTTO CLOSE THE OUTDOOR ECONOMIZER DAMPERS WHEN THE
THERMOSTAT SWITCHES TOTHE SET-BACK POSITION.
RCYRY1Y2W1WW2GCGRHTHERMOSTATTERMINALSUNIT TERMINALSTRIP TB124 VOLTTRANSFORMERADDJUMPER1COOLING / HEATING (24 VOLTTHERMOSTAT)24VOLTTHERMOSTAT 2ET07701024.TO CONTROLTHE ECONOMIZER ON THE SECONDSTAGE COOLING OR TO HAVE AN ELECTRIC HEAT ACCESSORYWITHTWO STAGES OFHEAT, USE THERMOSTAT 2TH0471024.
1
RHRCYWGRY1W1CGADDJUMPER
THERMOSTAT1
TERMINALS UNIT TERMINAL
STRIP TB1
24 VOLT
TRANSFORMER
1
ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET07701024 (INCLUDES SUBBASE).TO CONTROL THE ECONOMIZER ON SECOND STAGE COOLING, USE THERMOSTAT2TH04700224.

COOLING / HEATING (ELECTRONIC THERMOSTAT)

SINGLE STAGE