York FRCS024 Physical and Electrical Data, Model, Unit, Dimensions, Refrigerant, Connection

Models: FRCS024

1 16
Download 16 pages 23.34 Kb
Page 2
Image 2
Physical and Electrical Data

036-21004-002 Rev. B (0602)

Physical and Electrical Data

MODEL

 

FRCS0241BD

FRCS0301BD

FRCS0361CD

FRCS0421CE

FRCS0481CE

FRCS0601BF

Unit Supply Voltage

 

 

 

208 / 230

- 1 – 60

 

 

Normal Voltage Range1

 

 

187 to 252

 

 

Minimum Circuit Ampacity

12.1

14.9

18.1

17.8

20.6

31.8

Max Overcurrent Device Amps2

20

20

25

30

35

50

Compressor Type3

 

Inertia

Inertia

ScrollC

ScrollC

ScrollC

ScrollB

Compressor Amps

Rated Load

9.3

10.9

13.5

13.2

15.5

24.3

Locked Rotor

57

64

73

95

109

150

 

Crankcase Heater

 

No

No

No

No

No

No

Fan Motor Amps

Rated Load

.5

1.3

1.3

1.3

1.3

1.4

Fan Diameter Inches

 

22

22

22

24

24

24

 

Rated HP

1/15

1/4

1/4

1/4

1/4

1/3

Fan Motor

Nominal RPM

830

825

825

825

825

1100

 

Nominal CFM

2,260

3,300

3,300

3,300

3,300

3,500

 

Face Area Sq Ft

19.65

23.58

23.58

22.5

27.0

27.0

Coil

Rows Deep

1

1

1

2

2

2

 

Fin /Inch

18

18

18

18

18

18

Liquid Line OD

 

3/8

3/8

3/8

3/8

3/8

3/8

Vapor Line OD

 

7/8

7/8

7/8

1 1/8

1 1/8

1 1/8

Unit Charge (Lbs - Oz)4

8 - 0

9 - 14

9 - 6

14 - 0

14 - 3

15 - 13

Charge Per Foot, oz.

0.70

0.70

0.70

0.76

0.76

0.76

Operating Weight Lbs

209

228

219

240

264

270

1.Rated in accordance with ARI Standard 110, utilization range “A”.

2.Dual element fuses or HACR circuit breaker.

3.All scrolls listed with superscript “B” are Bristol scrolls. All scrolls listed with superscripts “C” are Copeland scrolls.

4.The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.

All dimensions are in inches. They are subject to change with out notice. Certified dimensions will be provided upon request.

C

A

Unit

Dimensions

Refrigerant

Connection

Model

 

(Inches)

 

 

 

Line Size

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A1

 

B

 

C

Liquid

Vapor

024

33

 

37

 

27

 

 

030

39

 

37

 

27

 

7/8

036

39

 

37

 

27

3/8

 

042

32

 

43

 

32

 

 

 

 

 

048

38

 

43

 

32

 

1-1/8

060

38

 

43

 

32

 

 

1.Included Fan Guard

B

2

Unitary Products Group

Page 2
Image 2
York FRCS024 warranty Physical and Electrical Data, Model, Unit, Dimensions, Refrigerant, Connection, Inches, Line Size