York GY9S-UP warranty YTG-A-1106, Blower Performance Cfm

Models: GY9S-UP

1 8
Download 8 pages 61.41 Kb
Page 4
Image 4
BLOWER PERFORMANCE CFM

277805-YTG-A-1106

BLOWER PERFORMANCE CFM

Airflow with Bottom or One Side Return - without Filters (CFM)

MODELS

Speed

 

 

 

External Static Pressure, Inches W.C

 

 

 

Tap

 

 

 

 

 

 

 

 

 

 

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH

1635

1590

1535

1480

1415

1340

1280

1185

NR

NR

 

 

 

 

 

 

 

 

 

 

 

 

GY9S040A12UP11

M-HI

1245

1225

1205

1185

1160

1110

1065

995

NR

NR

 

 

 

 

 

 

 

 

 

 

 

M-LO

1005

1000

995

975

955

925

885

825

NR

NR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW

775

770

765

750

725

680

655

620

NR

NR

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH

1650

1605

1570

1525

1465

1410

1350

1275

1170

1060

 

 

 

 

 

 

 

 

 

 

 

 

GY9S060B12UP11

M-HI

1165

1185

1175

1165

1150

1140

1100

1050

970

875

GY9S080B12UP11

M-LO

895

915

935

940

940

920

905

860

815

750

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW

710

725

725

725

720

700

685

660

625

560

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH

2300

2210

2120

2020

1930

1830

1715

1595

1480

1350

 

 

 

 

 

 

 

 

 

 

 

 

GY9S080C20UP11

M-HI

1950

1900

1830

1755

1680

1595

1500

1390

1270

1155

GY9S100C20UP11

M-LO

1610

1545

1490

1440

1390

1315

1230

1155

1050

920

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW

1325

1270

1225

1175

1105

1045

990

905

890

790

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH

1960

1955

1925

1890

1830

1765

1695

1615

1600

1485

 

 

 

 

 

 

 

 

 

 

 

 

GY9S080C16UP11

M-HI

1565

1560

1560

1575

1545

1530

1475

1425

1365

1260

GY9S100C16UP11

M-LO

1230

1275

1285

1300

1310

1300

1280

1245

1190

1070

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW

930

945

965

975

975

975

975

950

910

850

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH

2560

2485

2410

2320

2220

2135

2035

1920

1785

1650

 

 

 

 

 

 

 

 

 

 

 

 

GY9S120D20UP11

M-HI

2090

2050

1990

1970

1885

1820

1760

1675

1545

1405

GY9S135D20UP11

M-LO

1695

1675

1665

1615

1565

1510

1460

1385

1285

1140

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW

1175

1150

1135

1110

1085

1055

1005

980

970

845

 

 

 

 

 

 

 

 

 

 

 

 

 

Airflow with Two Side Returns or with Bottom and One Side Return - Without Filters (CFM)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MODELS

Speed

 

 

 

External Static Pressure, Inches W.C.

 

 

 

Tap

 

 

 

 

 

 

 

 

 

 

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH

2465

2380

2295

2195

2095

1995

1875

1760

1620

1470

 

 

 

 

 

 

 

 

 

 

 

 

GY9S080C20UP11

M-HI

2085

2035

1960

1880

1800

1705

1605

1485

1360

1235

GY9S100C20UP11

M-LO

1725

1625

1595

1540

1485

1405

1315

1235

1125

995

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW

1420

1360

1310

1255

1180

1120

1070

970

950

845

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH

2615

2535

2450

2385

2285

2175

2075

1945

1825

1670

 

 

 

 

 

 

 

 

 

 

 

 

GY9S120D20UP11

M-HI

2055

2045

2015

1985

1932

1855

1785

1730

1605

1470

GY9S135D20UP11

M-LO

1690

1650

1620

1600

1570

1525

1470

1395

1300

1200

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW

1345

1335

1335

1285

1250

1230

1180

1115

1010

850

 

 

 

 

 

 

 

 

 

 

 

 

NOTES:

1.Airflow expressed in standard cubic feet per minute (CFM).

2.Return air is through side opposite motor (left side) for one side return (worst case).

3.Airflows above 1800 CFM require either return from two sides or one side plus bottom.

4.Motor voltage at 115 V.

5.NR = Operation at this static pressure is not recommended.

4

Johnson Controls Unitary Products

Page 4
Image 4
York GY9S-UP warranty YTG-A-1106, Blower Performance Cfm