13.If the furnace will not operate, follow the instructions "To Turn OFF Gas To Furnace" and call your service tech- nician or gas supplier.
SHUTDOWN INSTRUCTIONS - TO TURN OFF GAS TO FURNACE
CAUTION: Should overheating occur, or the gas supply fail to shut off, shut off the main manual gas valve to the furnace before shutting off the electrical supply.
1. Set thermostat to the lowest setting.
TYPICAL GAS PIPING
2.Turn off all electrical power to the furnace if service is to be performed.
3.Remove the control access panel.
4.Turn the knob on the gas control clockwise to OFF.
5.Replace the control acess panel.
YOUR FURNACE’S FILTER -
WHAT IT DOES
The filter in your furnace takes the lint and dust out of the air that passes through it. This keeps dirt particles from getting into the moving parts of the furnace, where they could cause serious damage. It also keeps the dirt from circulating through your home.
As the filter continues to collect these particles, it becomes clogged and no longer allows enough air to circulate through the furnace. If this happens, the heat exchangers and blower motor could overheat; a potentially dangerous situation. It is very important to keep the air filter clean! Never operate your fur- nace without a suitable air filter.
WARNING: When replacing fil- ters DO NOT use a type with excessively high pressure drop. Some high efficiency filters avail- able will cause the furnace to operate improperly and could re- sult in a safety hazard.
UPFLOW FURNACE WITH EXTERIOR FILTER RACK
UPFLOW FURNACE
BOTTOM MOUNT
FILTER RETAINER
To check filters located in the blower compartment, remove the upper furance door by lifting up. Pull out bottom of door and lower from furnace. Remove the blower compartment panel by lifting up.
HONEYWELL
VR8205 GAS VALVE
| Wiring |
| |
Wrench | Terminals |
| |
|
| ||
Boss |
| Outlet | |
Inlet |
|
| |
ON - OFF Switch | Main | Outlet | |
Regulator | Pressure | ||
| |||
| Adjust | Tap |
WHITE-RODGERS 36E24 GAS VALVE
FREQUENCY OF CHECKING FILTERS
Clean your furnace’s filter at least every three months. If you need to replace a filter, check the filter chart to be sure you install the right size and type of filter for your furnace.
If your home is new, you should check the filter every week for the first four weeks after you begin to use the fur- nace, and then at least every three weeks after that, especially if the system runs constantly.
NOTE: Some installations may have more than one filter.
LOCATING/REMOVING FILTERS
UPFLOW FURNACES
Most upflow furnaces have their filters located on the side or bottom of the furnace in a filter frame.
If your furnace has this type return filter frame, remove the door by pulling on it. Slide the filter out of its channel. To replace after cleaning, slide filter into place and snap the door on the end of the filter rack.
Some installations may have filters lo- cated in the blower compartment. Check with the installer for your filter location.
NOTE: The
To remove bottom mounted filter(s) on all furnaces, push the looped end of the filter retainer to the side and then lift up. Reverse the procedure to reinstall filters.
DOWNFLOW FURNACES
The filters in your downflow furnace are located in the plenum or ductwork above the furnace.To check the filters, turn off the electrical supply to the furnace.
RETURN | VENT PIPE | |
AIR | ||
| ||
DUCT |
| |
ACCESS |
| |
PANEL |
| |
FURNACE |
|
DOWNFLOW FURNACE TYPICAL FILTER LOCATION
3