4 Type Test Specifications
Electrical Safety | Levels |
| Comments | |
Dielectric Withstand | 2 kV rms for 1 minute |
| ANSI/IEEE C37.90 (1989) | |
|
|
|
| IEC |
High Voltage Impulse | 5 kV peak |
| IEC | |
Insulation Resistance | 500 VDC for 1 minute |
| IEC | |
|
|
|
|
|
Electrical Environment | Levels |
| Comments | |
High Frequency Disturbance | 2.5 kV @ 1MHz for 2s |
| ANSI/IEEE C37.90.1 | |
(Oscillatory) |
| IEC | ||
|
|
| ||
IEC Surge | 4 kV / 2 kV |
| IEC | |
| (Level 4) | |||
|
|
|
| |
IEC Fast Transient | 2 kV / 1 kV |
| IEC | |
| (Level 4) | |||
|
|
|
| |
ANSI/IEEE Fast Transient | 4 kV |
| ANSI/IEEE C37.90.1 | |
IEC Radiated RFI Immunity | 10 V/m |
| IEC | |
ANSI/IEEE Radiated RFI | 35 V/m |
| ANSI/IEEE C37.90.2 | |
Immunity |
| |||
|
|
|
| |
ESD | 15 kV (air discharge) |
| IEC | |
(Electrostatic Discharge) | 8 kV (contact) |
| (Level 4) | |
|
|
|
|
|
Atmospheric Environment | Levels |
|
| Comments |
Temperature (Dry Cold) |
|
| IEC | |
| Test Ad: 16 hrs @ | |||
|
|
| ||
Temperature (Dry Heat) | 85°C |
|
| IEC |
| Test Bd: 16 hrs @ 85°C | |||
|
|
| ||
| 95% |
|
| IEC |
Humidity |
| Test Db: 6 cycles, 55°C, 95% | ||
| ||||
|
|
| Humidity | |
|
|
|
|
15
2006 RuggedCom Inc. All rights reserved | Rev101 |