Roberts Gorden CTH2-175, CTH2-125 General Venting Requirements, United States Requirements

Page 40

CTH2-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

SECTION 8: VENTING

WARNING

Carbon Monoxide Hazard

Heaters installed unvented must be interlocked with sufficient building exhaust.

Heaters must be installed according to the installation manual.

Failure to follow these instructions can result in death or injury.

WARNING

Cut/Pinch Hazard

Wear protective gear during installation, operation and service.

Edges are sharp.

Failure to follow these instructions can result in injury.

8.1 General Venting Requirements

This heater must be vented in accordance with the rules contained in this manual and with the following national codes and any state, provincial or local codes which may apply:

United States: Refer to National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest revision.

Canada: Refer to Natural Gas and Propane Installation Code CSA B149.1 - latest revision.

Exhaust end of heater will accept a 4' (10 cm) vent pipe using the vent adapter (P/N 90502700). To prevent leakage of condensation, install the vent adapter with the seam on top and seal the joint using a high temperature silicone sealant.

Any portion of vent pipe passing through a combustible wall must have an approved thimble to conform with the above listed codes.

Vent pipe must be sloped downward away from the burner 1/2'' (1 cm) for every 20' (6 m).

The heater may be individually vented or common vented. When venting horizontally, a maximum of two heaters can be commonly vented. See Page 36, Section 8.9. When venting vertically, a maximum of four heaters can be commonly vented. See Page 37, Section 8.10.

The heater may also be installed unvented in certain circumstances according to building ventilation codes. Refer to the above codes and Page 34, Section 8.2 for further information. Unvented operation also requires compliance with the clearances to combustibles given on Page 8, Figure 12.

The bottom of the vent or air intake terminal shall not be located less than 1' (.3 m) above grade level.

The vent shall not terminate less than 7' (2.1 m) above grade where located adjacent to public walkways.

Vent terminal must be installed at a height sufficient to prevent blockage by snow and building materials protected from degradation by flue gasses.

Secure all joints with #8 x 3/8 sheet metal screws. Seal all joints with high temperature silicone sealant.

Vent terminal must be beyond any combustible overhang.

8.1.1 United States Requirements

Vent must terminate at least 3' (.9 m) above any forced air inlet located within 10' (3.1 m).

Vent must terminate at least 4' (1.2 m) below, 4'

(1.2 m) horizontally from, or 1' (.3 m) above any door, operable window, or gravity air inlet into any building.

8.1.2 Canadian Requirements

The vent shall not terminate within 6' (1.8 m) of a mechanical air supply inlet to any building.

The vent shall not terminate within 3' (.9 m) of a

window or door that can be opened in any building, any non-mechanical air supply inlet to any building, or of the combustion air inlet of any other appliance.

8.2 Unvented Operation

Sufficient ventilation must be provided in the amount of 4 cfm per 1000 Btu/h firing rate (United States); 3 cfm per 1000 Btu/h firing rate (Canada).

Use of optional outside combustion air is not recommended with unvented heaters.

If exhaust fans are used to supply ventilation air, an interlock switch must be used to prevent the heater from coming on when the fans are off. This may be done using a pressure switch.

34

Image 40
Contents Vantage Page Roberts-Gordon LLC Page Table of Figures Page Heater Safety Manpower RequirementsSafety Labels and Their Placement California PropositionTop and Bottom Panel Label Placement Side and Back Panel Label Placement Installer Responsibility Wall TagCorrosive Chemicals National Standards and Applicable CodesStandard Reflector Inches Centimeters ModelONE Side Reflector Inches C D UnapprovedFoot Deco Grille and Protective Grille National Standards and Applicable Codes Major Components Standard Parts List Contents of the Burner Carton Contents of Core and Extension Packages30’ 9m Heater Installation Typical Suspension Details Linear Heater Assembly Overview Linear Heater Layout Overview Linear Heater Layout Overview Burner Tube Installation Tube Clamp Package InstallationCoupling and Tube Assembly 1 Coupling and Tube Assembly2 Coupling and Tube Assembly Turbulator InstallationReflector Installation By a reflector, except for a U-Tube1 Reflector, U-Clip and Reflector Support Installation Description Part Number Reflector Support PackageBurner Installation Window facing downOptional Heater Accessories Tube ConfigurationTube Heater Assembly Overview Tube Heater Layout Overview Tube Length 2 Elbow Installation Elbow Package Configuration .2.1 Elbow Installation3 Reflector Joint Installation 4 Reflector Joint Installation 5 Reflector Joint Detail Reflector Joint DetailReflector Side Extension .3.1 Bracket Installation 2 Side Reflector InstallationScr ews 2 Frame Shield Installation Distance a Extension2 Grille End Cap Installation 3 Grille InstallationGeneral Venting Requirements United States RequirementsCanadian Requirements Unvented OperationHorizontal Venting Vertical VentingUnvented Operation Tube Termination Length RequirementsVertical Ventilation 4 10 cm Pipe Common Sidewall VentingCommon Vertical Venting Vertical Outside Air Supply for Single Heater Installation Outside Combustion Air SupplyVertical Outside Air Supply for Double Heater Installation Horizontal Outside Air Supply for Double Heater InstallationGAS Piping Correct Positions Line Voltage Thermostat Wiring WiringLow Voltage Thermostat with One Burner Low Voltage Thermostat Wiring with Multiple Burners Internal WiringLadder Diagram Electrical Connection to the BurnerOperation and Maintenance Pre-Season Maintenance and Annual InspectionSequence of Operation To Shut Off HeaterVicinity of the Heater Vehicles and OtherObjects Vent PipeSafety Labels Gas LineBurner Observation WindowTroubleshooting Honeywell SmartValve II Troubleshooting LED Status IndicatesTroubleshooting Flow Chart Troubleshooting Manifold Gas Pressure Setting Top View of HeaterReplacement Parts Motor and Blower Assembly Blower Inlet Gasket Door Switch Description Part Number General Specifications DimensionsGAS Pressure AT Manifold Pipe ConnectionLimitations on Authority Representatives Warranty is Void if ROBERTS-GORDON will not PAY forPage Page Page
Related manuals
Manual 2 pages 5.59 Kb

CTH2-40 CTH2-60, CTH2-175, CTH2-150, CTH2-100, CTH2-80 specifications

Roberts Gorden is a reputable name in the field of heating and energy efficiency, and its CTH2 series of infrared radiant heaters—including the CTH2-150, CTH2-80, CTH2-125, CTH2-100, and CTH2-175—are a testament to innovation and quality. Designed for commercial and industrial spaces, these heaters provide effective and efficient heating solutions tailored to various needs.

The CTH2 series employs advanced infrared heating technology, which radiates warmth directly to objects and individuals in the space rather than heating the air. This method ensures rapid heat-up times and energy conservation, making the heaters ideal for workshops, warehouses, and other large areas where traditional heating systems may be inefficient.

One of the main features of the CTH2 series is its high thermal efficiency. The heaters convert a significant portion of the energy consumed into usable heat, resulting in lower operational costs and a reduced carbon footprint. The CTH2 models utilize durable components designed to withstand the rigors of industrial environments, ensuring longevity and reliable performance.

The CTH2-150, CTH2-80, CTH2-125, CTH2-100, and CTH2-175 models vary in output capacity and design, providing flexibility for different heating requirements. The maximum heat output ranges significantly among the models, with the CTH2-175 offering the highest thermal output, making it suitable for larger spaces or areas requiring immediate and intense heating. Conversely, the CTH2-80 is ideal for smaller areas or those that require less heat.

Installation versatility is another key characteristic of the CTH2 series. These heaters can be mounted from the ceiling or installed horizontally or vertically, accommodating different building layouts and operational needs. The heaters are also designed for easy maintenance, featuring accessible components to facilitate routine checks and repairs.

The CTH2 series incorporates safety features such as overheat protection and flame safeguard systems, ensuring safe operation even in busy industrial settings. Additionally, their sleek and modern design allows them to integrate seamlessly with existing infrastructure without detracting from the overall aesthetic of the space.

In conclusion, Roberts Gorden’s CTH2 series—including the CTH2-150, CTH2-80, CTH2-125, CTH2-100, and CTH2-175—represents a pinnacle of infrared heating technology. With their impressive efficiency, customizable output, versatile installation options, and robust safety features, these heaters are a reliable choice for any commercial or industrial heating requirement.