Fisher 244EH, 244ER manual Sensor Connections, RTD or Ohm Inputs

Page 23
Sensor Connections

Figure 2-11. Transmitter Field Wiring Diagrams

Use the following steps to wire the transmitter:

1.Connect the positive lead from the power supply to the transmitter terminal marked “+” and the negative lead to the transmitter terminal marked (see Figure 2-11and Figure 2-13).

2.Tighten the terminal compression screws to ensure adequate contact. No additional power wiring is required.

3.After making connections, recheck the polarity and correctness of connections, then turn the power on.

Model 244EH

Power0000A02C

Supply

-244

Model 244ER

Power0000A02D

Supply

-644

Note: Signal loop may be grounded at any point or left ungrounded.

Sensor Connections

RTD or Ohm InputsThe Models 244E are compatible with a number of RTD and thermocouple sensor types. Figure 2-12shows the correct input connections to the sensor terminals on the transmitter. To ensure proper sensor connections, anchor the sensor lead wires into the appropriate compression terminals and tighten the screws.

RTD or Ohm Inputs

The transmitters will accept a variety of RTD configurations, including 2-wire, 3-wire, 4-wire, and compensation loop designs. If the transmitter is mounted remotely from a 3-wire or 4-wire RTD, it will operate within specifications, without recalibration, for lead wire resistances of up to 10 ohms per lead (equivalent to 1,000 feet of

20AWG wire). In this case, the leads between the RTD and transmitter should be shielded. If using only two leads, both RTD leads are in series with the sensor element, so significant errors can occur if the lead lengths exceed three feet of 20 AWG wire (approximately 0.05 °C/ft). For longer runs, attach a third or fourth lead as described above.

2-13

Image 23
Contents Models 244EH and 244ER PC-Programmable Temperature Transmitters 00809-0100-4737 English Rev. EAPage 00809-0100-4737 Rev EA 10/00 Product ManualModels 244EH and 244ER PC-Programmable Temperature Transmitters ¢00809-0100-4737f¤Page Troubleshooting Table of ContentsInstallation Maintenance andApprovals APPENDIX AReference Data APPENDIX B1 Introduction SAFETY MESSAGESSection MANUAL OVERVIEW Electrical CONSIDERATIONSGeneral MechanicalPage SAFETY MESSAGES Warnings 2 InstallationFigure 2-1. Transmitter Installation Flowchart TOOLS NEEDED FOR INSTALLATIONThe tools needed for installation are as follows Example MOUNTINGMounting a Model 244EH to a DIN Rail Special Mounting ConsiderationsHead Mount Transmitter with DIN Plate Style Sensor INSTALLATION PROCEDURESTransmitter Head Mount Transmitter with Threaded Sensor Figure 2-6. Typical Model 244EH Transmitter Mounting ConfigurationUsing Threaded Style Sensor and Assembly6. Run sensor lead wires from the sensor assembly to the transmitter Figure 2-7. Typical Rail Mount Transmitter Mounting ConfigurationUsing Integral Mount Sensor and Assembly To complete the assembly, follow the procedure described below644-0000A04B Rail Mount Transmitter with Threaded SensorSystem Requirements Configuration SoftwareMultichannel Installations Procedure for Windows 95 or Windows NT Choose the procedure that matches the operating system you are usingProcedure for Windows 3.1 or Windows for Workgroups Screen Conventions Model 244EC Configuration InterfaceSetting Up the Model 244EC Configuration Interface Figure 2-10. Complete Transmitter Configuration System FIELD WIRINGRTD or Ohm Inputs Sensor ConnectionsTotal cable length = 150 m Sensor Lead Wire Resistance Effect RTD InputExamples of Approximate Lead Wire Resistance Effect Calculations GivenThermocouple or Millivolt Inputs Figure 2-13. Transmitter Power, Sensor, and Configuration Terminals FAILURE MODE Changing Switch Positions3 Operation POWER SUPPLY Surges/TransientsGrounding CONFIGURATIONConfiguration Window Configuring a Single TransmitterFigure 3-1. Models 244EH and 244ER Configuration Software Main Configuring Several Transmitters Identically Figure 3-2. Viewing the Process Variable with the 244EC Viewing the Process VariableINTERMITTENT SENSOR ALGORITHM Threshold Value2% of Output Range Case ExamplesCase 1 Open Sensor Case 2 Temperature Change Greater than theCase 3 Temperature Change Within the Threshold Value 2 % of Range Intermittent Sensor Algorithm and Dampingcontinues to approach the input curveaccordingto theequation above Intermittent Sensor Detect Advanced Feature2.0 seconds, the transmitter outputs the reading that corresponds to the damping curve at that time , and continues to calculate andTransmitter Behavior with Intermittent Sensor Detect OFF ImplementationTransmitter Behavior with Intermittent Sensor Detect ON Page TROUBLESHOOTING Model 244EH software version 4 Maintenance and TroubleshootingSAFETY INFORMATION TABLE 4-1. Models 244EH and 244ER Troubleshooting ChartError Message Cause and Possible SolutionsPower Supply TRANSMITTER SPECIFICATION FunctionalAppendix A Reference DataCE Electromagnetic Compatibility Compliance Testing PerformanceUpdate Time Power Supply EffectInput AccuracyTABLE A-2. Model 244E Input Options and Accuracy SensorAmbient Temperature Effect Transmitters can be installed in locations where the ambientMaterials of Construction PhysicalWeight Electrical ConnectionsHead ORDERING INFORMATIONModel Product DescriptionPart Description TABLE A-5. Model 244EC Configuration Interface Ordering InformationTABLE A-6. Transmitter Accessories Typical Model Number 244ECTagging Standard ConfigurationCustom Configuration Unless specified, transmitter will be shipped as followsModel 244ER DIMENSIONAL DRAWINGS TransmitterEnclosure and Model 244EC Configuration Interface Configuration InterfacePage B Approvals HAZARDOUS LOCATIONS INSTALLATIONSCanadian Standards Association CSA Approvals LOCATIONS CERTIFICATIONSFactory Mutual FM Approvals Special Conditions for Safe Use Standard Australia Quality Assurance Service SAAKEMA Approvals Gostandart INSTALLATION DRAWINGSInstallation Drawing Rev. AB Figure B-1. Canadian Standards Association CSA Intrinsic SafetyFigure B-2. Canadian Standards Association CSA Explosion-Proof Installation Drawing Rev. AA00644-0009, Rev. AA Figure B-3. Factory Mutual FM Intrinsic Safety Installation Drawing00644-1049, Rev. AB Figure B-4. Factory Mutual FM Explosion-Proof Installation DrawingC Models 644 and 244E Temperature Transmitters Manual Supplement Models 644H and 244EH Transmitter Design Sensor Wiring Diagrams Special MountingOLD TRANSMITTER ConsiderationsUse with an Existing DIN Plate Style Sensor NEW TRANSMITTERConsiderations HART Communicator Model 644H only 2. Select 1 Off-line, 1 New Configuration, Rosemount, 644 TempEntity Parameters SPECIFICATIONSBASEFFA1 Intrinsically Safe Installation Entity Parameters Factory Mutual3Index Wiring Page Product documentation available at