Laarsen Associates LG, LD operation manual 2G-4a. Water Chemistry, 2G-5. Pressure Relief Valve

Page 15

Model LG & LD Pool and Spa Heater

Page 13

 

 

 

 

When chemical feeders are used, plumb the feeder downstream of the heater and install an in- line check valve between the heater and the feeder (a minimum of 18" is required between the heater and the check valve).

Never deposit chemicals directly in the pool skimmer.

2G-4a. Water Chemistry

Proper chemical balances are necessary for sanitary bathing conditions as well as ensuring your heater's long life. Be sure to keep your chemical levels within the values indicated in Table 7. Waterpik

Laars does not warrant heat exchangers damaged by corrosive chemical levels or excess dissolved solids in pool or spa water.

For spas, it is also necessary to perform water changes in addition to chemical treatment. It is recom- mended to change the spa water every 60 days for light usage and every 30 days if usage is heavy.

Table 7. Mineral Concentration Levels

Test

Recommended Level

 

 

Free chlorine

1.0 to 3.0 ppm

Bromine

3.0 to 5.0 ppm

pH

7.2 to 7.8

Total alkalinity (TA)

80 to 120 ppm

Calcium hardness (CH)

200 to 400 ppm

Langelier saturation index (LSI)

-0.5 to +0.5

Total dissolved solids (TDS)

Less than 2000 ppm

Cyanuric acid

30 to 150 ppm

Copper

0 ppm

 

 

2G-5. Pressure Relief Valve

A pressure relief valve is not furnished with the Laars Lite 2 heater. However, it is recommended that a pressure relief valve be installed and may even be required by local codes.

To install a pressure relief valve, remove the 3/4 inch (19 mm) brass plug located on the top of the inlet/ outlet header (see Figure 17). Install the pressure relief valve in the threaded hole from which the plug was removed. The pressure rating of the valve should be at or below the lowest working pressure of any compo- nent in the filter system. Any pressure relief valve installed must comply with provisions of the Standard described in ANSI Z21.22 for the United States, or CAN1-4.6 in Canada.

Figure 17. Thermometer and pressure relief valve.

2G-6. Adjusting the Pressure Switch

Caution

The pressure switch should be adjusted to turn the heater off when the pump is off. Setting the switch to close at too low of a flow can damage the appliance. Adjust the switch to turn the heater off, not on.

The pressure switch is preset at the factory for activation at 2 psi (14 kPa). Adjust the pressure switch only if any part of the filter system piping is 3 feet (0.91 m) or more above the top of the heater jacket.

Do not adjust the pressure switch if the heater is installed more than 15 feet (4.57 m) below or 6 feet (1.83 m) above the pool surface. Consult your local Waterpik Laars representative for recommendations.

On some installations, the piping from the heater to the pool is very short. The back pressure could be too low to trigger the pressure switch. If this happens, it may be necessary to install a directional fitting or elbows where the return line enters the pool. This will increase back pressure enough for the heater to operate properly.

Make sure the pool filter is clean before making any pressure switch adjustment: A dirty filter will restrict the water flow and the pressure switch cannot be adjusted properly. To adjust the pressure switch:

1.Set the control panel rotary switch (LD) or the control panel rocker switch (LG) to the OFF position (see Figure 18).

2.Set the Pool temperature control to the Max position.

3.Turn filter pump on. If a two-speed pump is used, make sure it is at high speed.

Image 15
Contents Outdoor Use Only Installation Laars Lite Pool and Spa HeaterTable of Contents 1A. Introduction Section1D. Technical Assistance 1C. Warranty2B. Field Assembly 1B. Description2C. Site Location 2C-1. Installation InformationUnited States 2C-2. Outdoor Installation2C-3. Flooring Typical Installation 2C-4. Indoor and Outdoor Shelter Installations2D. Combustion and Ventilation Air Supply 2E. Gas Supply and Piping2E-1. General Instructions 2F. Electrical Wiring 2E-2. Special Precautions for Propane Gas2F-1. General Information LD Only Model LD Wiring Diagram Onnection Iagram 2F-2. Auxiliary Time Clock Wiring2G-1. Flange Installation 2G. Water Flow System2F-3. Remote Operation Model LD Only 2G-2. Reversible Water Connections Piping installationFlue collector hold-down brackets 2G-4. Chlorinators, Ozone Generators Sanitizing Chemicals 2G-3. Check Valve Installation2G-6. Adjusting the Pressure Switch 2G-4a. Water Chemistry2G-5. Pressure Relief Valve 2G-7. Automatic Flow Control Valve 2G-8. Temperature RiseTypical installation 2G-9. Adjusting the Manual Bypass Valve3B-1. Model LD see 3B-2. Model LG see 3B. Lighting and Shutdown Procedures3C. Setting the Temperature Control 3A. General InformationDo not try to light any appliance 3B-1. Model LD Direct IgnitionWhat to do if YOU Smell GAS 3B-2. Model LG Standing Pilot3D-3. Spring Start-up 3D. Seasonal Care3D-1. Spring and Fall Operation 3D-2. Winterizing3F. Spa/Hot Tub Safety Rules 3E. Water Chemistry3G. Swimming Pool Energy Saving Tips 3H-1. Owner Inspection 4B. Parts List3H. Periodic Inspection 4A. General InformationOrder Heat Exchanger See Next page for Detail Shown Model LG & LD Pool and Spa Heater Laars Lite Limited Warranty

LG, LD specifications

Laarsen Associates is a reputable engineering and consulting firm known for its innovative solutions in the field of energy and environmental management. Among its notable offerings are the LG and LD series of products, designed to optimize energy efficiency and reduce environmental impact in various applications.

The LG series focuses on providing high-performance tools for efficient energy management in commercial settings. These tools are engineered to integrate seamlessly into existing infrastructures, allowing businesses to monitor, control, and optimize their energy consumption effectively. One of the main features of the LG series is its user-friendly interface, which provides real-time data on energy usage, enabling users to make informed decisions quickly. Furthermore, the enhanced connectivity options facilitate remote access, allowing users to manage their systems from anywhere, significantly improving flexibility and response times.

On the other hand, the LD series is tailored for industrial applications, emphasizing durability and robust performance. The LD products are designed to withstand the harshest environments while maintaining consistent efficiency. Their advanced monitoring systems provide detailed insights into energy consumption patterns, allowing for predictive maintenance and reduced operational costs. Key characteristics of the LD series include high reliability, modular design, and adaptive technologies that can be customized to suit specific industrial requirements.

Both series employ cutting-edge technologies to achieve optimal performance. Smart sensors collect real-time data, which is processed using advanced algorithms to deliver actionable insights. These insights can lead to optimized processes, reduced energy wastage, and enhanced sustainability measures. Moreover, the integration of IoT capabilities allows for smarter energy systems that adapt in real time to changing conditions.

Sustainability is at the core of Laarsen Associates’ offerings. Both the LG and LD series are designed with a commitment to reducing carbon footprints and complying with global standards for environmental protection. Their features not only promote energy efficiency but also support clients in achieving their sustainability goals.

In conclusion, Laarsen Associates’ LG and LD series represent the forefront of energy management and environmental solutions. With their combination of user-centric design, advanced technology, and commitment to sustainability, these products pave the way for businesses and industries to navigate modern energy challenges effectively.