5.0 Power Requirements
Jacuzzi Premium spas are designed to provide optimum performance and flex- ibility of use when connected to the maximum electrical service listed in the tables below. If you prefer, your dealer can perform a minor circuit board modification to allow your spa to accept an electrical service other than the factory setting.
US / Canada J-310 1-Pump Convertible Model (60Hz)
| 120V/15A* | 240V/30A* | 240V/40A** |
Voltage: | 120 VAC | 240 VAC | 240 VAC |
# of Wires: | 3 (15A GFCI Cord) | 4 | 4 |
Frequency: | 60Hz | 60Hz | 60Hz |
Current Draw: | 12A | 21A | 30A |
Circuit Breaker: | 15A, | 30A, | 40A, |
For 240 VAC Heater Operation: Move the red wire on the main terminal strip (TB1) from position #1 to position #3. Make certain wires are connect- ed exactly as shown in
*In the 15A/30A configuration, the heater will not operate at the same time as the
**If the spa is to be operated on 40A service, remove the jumper JP1
US / Canada J-320 / J-330 1-Pump Models (60Hz)
| 240V/50A* | 240V/30A** |
Voltage: | 240 VAC | 240 VAC |
# of Wires: | 3 | 3 |
Frequency: | 60Hz | 60Hz |
Current Draw: | 34A | 24A |
Circuit Breaker: | 50A, | 30A, |
*In the 50A configuration, the heater will operate at the same time as the
**In the 30A configuration, the heater will not operate at the same time as the
Page 8