Briggs & Stratton 30209 owner manual Cold Weather Operation, Volt AC, 20 Amp, Duplex Receptacles

Page 10

5500W Portable Generator

120 Volt AC, 20 Amp, Duplex Receptacles

Each duplex receptacle (Figure 5) is protected against overload by a push–to–reset circuit breaker.

Build a structure that will enclose three sides and the top of the generator:

1.Make sure entire muffler-side of generator is exposed. Note that your generator may appear different from that shown in Figure 6.

Figure 5 — 120 Volt, 20 Amp Duplex Receptacle

Use each receptacle to operate 120 Volt AC, single–phase, 60 Hz electrical loads requiring up to 2,400 watts (2.4 kW) at 20 Amps of current. Use cord sets that are rated for 125 Volt AC loads at 20 Amps (or greater).

Figure 6 — Permanent Cold Weather Shelter

Wind

2.Ensure a minimum of two feet clearance between open side of box and nearest object.

3.Face exposed end away from wind and elements.

COLD WEATHER

OPERATION

Under certain weather conditions (temperatures below 40°F [4°C] and a high dew point), your generator may experience icing of the carburetor and/or the crankcase breather system.

4.Enclosure should hold enough heat created by the generator to prevent problems.

DANGER

Running generator gives off carbon monoxide, an odorless, colorless, poison gas.

Breathing carbon monoxide will cause nausea, fainting or death.

Operate generator ONLY outdoors.

Keep at least 2 feet of clearance on all sides of generator for adequate ventilation.

DO NOT operate generator inside any building or enclosure, including the generator compartment of a recreational vehicle (RV).

Remove generator from shelter when temperature is above 40°F [4°C].

10

Image 10
Contents 030209 5500W Safety Rules Table of ContentsEquipment Description When Operating Equipment When Adding or Draining FuelWhen Starting Equipment When Transporting or Repairing EquipmentWhen Adjusting or Making Repairs to Your Generator When Testing for Engine SparkKnow Your Generator Carton Contents AssemblyInstall Wheel KIT Remove Generator From CartonAdd Engine Oil When Adding FuelBefore Starting the Engine Add FuelOperating Generator Using the GeneratorConnecting to a Building’s Electrical System System GroundStopping the Engine Connecting Electrical LoadsReceptacles 120/240 Volt AC, 30 Amp, Locking ReceptacleCold Weather Operation Volt AC, 20 Amp, Duplex ReceptaclesCapacity Power ManagementDont Overload Generator ExampleEngine Maintenance SpecificationsGeneral Maintenance Recommendations Generator MaintenanceGenerator Storage StorageEngine Storage Other Storage Tips Troubleshooting Problem Cause Correction5500W Portable Generator Schematic Wiring Diagram Exploded View Main Unit Description Exploded View Parts ListParts Not Illustrated Exploded View and Parts List Alternator StatorExploded View and Parts List Control Panel Exploded View and Parts List Wheel KIT WheelLimited Warranty Instrucciones DE Seguridad Tabla DE ContenidosDescripción DEL Equipo AdvertenciaCuando Ponga EN Funcionamiento EL Equipo PeligroCuando Añada Combustible O Vacíe EL Depósito Cuando Opere EL EquipoCuando Ajuste O Haga Reparaciones a SU Generador PrecauciónCuando Pruebe LA Bujía DEL Motor Conozca SU Generador Tapa del Depósito del Aceite Llene el motor con aceitePara Retirar El Generador De La Caja MontajeInstale EL Juego DE Ruedas Contenido de la CajaAgregue Combustible Antes DE Darle Arranque AL MotorAgregar Aceite al Motor Cuando Añada CombustibleTierra del Sistema USO DEL GeneradorOperando EL Generador Precaución Conexión al Sistema Eléctrico de un EdificioParado Del Motor Receptáculos PrecauciónConexion De Cargas Electricas 120/240 Voltios AC, 30 Amp, Receptáculo de SeguridadOperación Durante UN Clima Frío Volt AC, 20 Amp, Receptáculos DoblesControl de la Energía No Sobrecargue GeneradorCapacidad EjemploMantenimiento del Motor EspecificacionesRecomendaciones Generales DE Mantenimiento Mantenimiento del GeneradorAlmacenando el Generador Diagnositicos DE AveríasAlmacenamiento Almacenando el MotorGarantía Limitada