Briggs & Stratton 030249, 030255 Generator Adapter Cord SET, Receptacles, Stopping the Engine

Page 10

PowerBOSS™

5500W Portable Generator

OPERATION

 

 

 

Stopping the Engine

1.Turn OFF and unplug all electrical loads from generator panel receptacles. NEVER start or stop engine with electrical devices plugged in and turned ON.

2.Let engine run at no-load for several minutes to stabilize internal temperatures of engine and generator.

3.Turn engine off according to instructions given in the engine operator’s manual.

4.Move fuel valve to “Off” position.

GENERATOR ADAPTER CORD SET

The generator is equipped with a 25’ generator adapter cord set designed for a 240 Volt, 30 Amp grounded neutral circuit (Figure 5).

Figure 5 — Generator Adapter Cord Set

The maximum load on each outlet is 20 Amps.The maximum total load on both yellow wire outlets or both black wire outlets is 30 Amps.

NOTE: Follow all safety precautions when connecting any extension cord or device to the generator.

RECEPTACLES

CAUTION

Receptacles may be marked with rating value greater than generator output capacity.

NEVER attempt to power a device requiring more amperage than generator or receptacle can supply.

DO NOT overload the generator. See “Don’t Overload Generator”.

120/240 Volt AC, 30 Amp, Locking Receptacle

Use a NEMA L14–30 plug with this receptacle. Connect a 4–wire cord set rated for 250 Volt AC loads at 30 Amps (or greater) (Figure 6).You can use the same 4–wire cord if you plan to run a 120 Volt load.

Figure 6 — 120/240 Volt AC, 30 Amp Receptacle

4-Wire Cord Set

240V

120V 120V

W (Neutral)

Y (Hot)

X (Hot)

NEMA L14-30

Ground (Green)

This receptacle powers 120/240 Volt AC, 60 Hz, single phase loads requiring up to 5,500 watts of power (5.5 kW) at 22.9 Amps for 120 Volts or 240 Volts.The outlet is protected by a push–to–reset circuit breaker.

120 Volt AC, 20 Amp, Duplex Receptacle

Each duplex receptacle (Figure 7) is protected against overload by a push–to–reset circuit breaker.

Figure 7 — 120 Volt, 20 Amp Duplex Receptacle

Use each receptacle to operate 120 Volt AC, single–phase, 60 Hz electrical loads requiring up to 2,400 watts (2.4 kW) at 20 Amps of current. Use cord sets that are rated for 125 Volt AC loads at 20 Amps (or greater).

10

Image 10
Contents Model / Modelo 030249 5500W Safety Rules Table of ContentsEquipment Description When Operating Equipment When Adding or Draining FuelWhen Starting Equipment When Transporting or Repairing EquipmentWhen Adjusting or Making Repairs to Your Generator When Testing for Engine SparkKnow Your Generator Install Wheel Kit AssemblyCarton Contents Unpacking the GeneratorAdd Engine Oil When Adding FuelBefore Starting the Engine Add FuelSystem Ground Using the GeneratorConnecting to a Building’s Electrical System Generator LocationOperating Generator Connecting Electrical LoadsStarting the Engine Stopping the Engine Generator Adapter Cord SETReceptacles 120/240 Volt AC, 30 Amp, Locking ReceptacleCapacity Power ManagementDont Overload Generator ExampleEngine Maintenance SpecificationsGeneral Maintenance Recommendations Generator MaintenanceEngine Storage StorageGenerator Storage Other Storage TipsTroubleshooting Problem Cause CorrectionWarranty Period Limited WarrantyDescripción DEL Equipo Conserve Estas InstruccionesTabla DE Contenidos Reglas DE SeguridadCuando Opere EL Equipo Cuando Añada Combustible O Vacíe EL DepósitoCuando Ponga EN Funcionamiento EL Equipo Cuando Transporte O Repare EL EquipoCuando Ajuste O Haga Reparaciones a SU Generador PrecauciónCuando Pruebe LA Bujía DEL Motor Conozca SU Generador Tomacorriente con Dispositivo de Seguridad deContenido De La Caja MontajeDesembalaje del Generador Instale el Juego de RuedasAgregue Combustible Antes DE Darle Arranque AL MotorAgregar Aceite al Motor Cuando Añada CombustibleConexión al Sistema Eléctrico de un Edificio USO DEL GeneradorTierra del Sistema Ubicación del GeneradorConexion De Cargas Electricas Operando EL GeneradorEncienda el Motor No Sobrecargue EL GENERADOR.Vea No Sobrecargue GeneradorParado Del Motor Juego DE Cables DEL Adaptador DEL GeneradorReceptáculos Precaución 120/240 Voltios AC, 30 Amp, Receptáculo de SeguridadControl de la Energía No Sobrecargue GeneradorCapacidad EjemploMantenimiento del Motor EspecificacionesRecomendaciones Generales DE Mantenimiento Mantenimiento del GeneradorAlmacenando el Generador Diagnositicos DE AveríasAlmacenamiento Almacenando el MotorPeríodo DE Garantía Garantía Limitada