Generac 1403-0 manual Unpacking, Generator Compatibility, Carton Contents, Specifications

Page 2

Generac Portable Products Power Transfer System

NOTE: The maximum load allowed through each

Load Manager™ switch is 7200 Watts: 30 Amps at 240 Volts or 60 Amps at 120 Volts.

Per National Electric Code, connection of a generator to any electrical circuit normally powered by an electric utility must be by means of approved transfer switch equipment so as to isolate the electrical circuit from the utility distribution system when the generator is operating. Failure to isolate the electrical circuits by such means may result in injury or death to utility power workers due to backfeed of electrical energy.

CAUTION: Each Load Manager™ switch is for indoor use only. The connection box is a NEMA type 3R, intended for outdoor use.

NEMA stands for National Electrical Manufacturer’s Association.

UNPACKING

Remove the Power Transfer System components from the shipping carton. Each Load Manager™ switch is completely prewired and ready for installation. Inspect the switches and attached wires and flexible conduit for any shipping damage.

The connection box is supplied ready to be wired. Inspect the box, the connection cord set, and the connecting plug for any damage.

The installer will select and attach the connecting cord plug, as described in the Installation Procedure, step 22.

Items Not Shipped with Power Transfer System:

The following items, required for system installation, are not included and must be provided by the installer:

1. Tools required for installation

GENERATOR

COMPATIBILITY

Only use a generator that is factory-equipped with a NEMA Type 14-50R receptacle.

NEVER use a generator equipped with a 3-prong 240 Volt receptacle because damage may occur in connected appliances.

CARTON CONTENTS

Items in the shipping carton include:

Two Load Manager™ Switches

Connecting Box

Connecting Cord Set

50 Amp Connecting Plug

“Attention” Decal

If any of the above parts are missing or damaged, call the Generac helpline at 1–800–270–1408.

2.Anchors and screws to mount the power transfer system components and conduit.

3.Junction box(s), conduit, fittings, wire nuts, and insulated copper wire for connecting the Load Manager™ switches to the outside connection box.

SPECIFICATIONS

 

Model Number

1403

Maximum Circuits

12

Maximum Load/Circuit from Generator

15 Amps

Maximum Load/Circuit from Load Center

20 Amps

Maximum Watts per Load Manager™

7200

Connecting Cord Length

8 ft.

2

Image 2
Contents Generac DescriptionUnpacking Carton ContentsSpecifications Generator CompatibilityMeasure Actual Loads General Safety InformationPlan the Installation Sum Loads from Data PlatesInstallation Procedure Load Manager SwitchWire Detached From Breaker Make SureShows a properly-connected Green lead Typical Completed Power Transfer System Installation Connection BoxConnection Box Installation Connecting Cord Set Identifying CircuitsInstallation and Load Management Notes Load Manager Schematic Diagram Exploded View & Parts List Description QtyOperating Procedure Switch To Generator PowerCircuit Breakers in Load Manager Switch Switch To Utility PowerTesting Troubleshooting Warranty Schedule Limited WarrantyOne Year Limited Warranty Generac Portable Products