Emerson 208V, GXT3 Cable Connection, Connecting Input Plug and Loads, Connecting Battery Cables

Page 23

Installation

2.5Cable Connection

The Liebert® GXT3rear panel has an input cable and plug, output receptacles and output cable(s) (Output cables are on GXT3-3000 models only). Refer to 1.3.2 - Rear Panel Features for details. The battery cables are supplied with the battery cabinet.

2.5.1Connecting Input Plug and Loads

NOTE

Ensure that all the loads are turned Off.

Prepare an input power supply that is properly protected by a circuit breaker in accordance with national and local electrical codes. The wall receptacle must be grounded.

The plug on the power supply cord is intended to serve as the disconnect device. The socket-outlet must be installed near the equipment and must be easily accessible.

Emerson recommends installing an upstream circuit breaker of the same series as the Liebert GXT3’s input circuit breaker.

The specification of input circuit breaker on the rear panel of UPS is given in Table 2.

Table 2

Input circuit breaker specification

 

 

 

 

 

 

Rated Circuit

 

Model

Breaker

 

GXT3-500RT120

8A

 

 

 

 

GXT3-700RT120

10A

 

 

 

 

GXT3-1000RT120

15A

 

 

 

 

GXT3-1000MT120

15A

 

 

 

 

GXT3-1500RT120

15A

 

 

 

 

GXT3-2000RT120

20A

 

 

 

 

GXT3-3000RT120

30A

 

 

 

 

GXT3-3000RT208

20A

 

 

 

 

 

1. Plug all loads into the output receptacles on the rear panel of the Liebert GXT3.

NOTE

1. Distribute loads evenly across all receptacles to prevent overloading individual receptacles.

2.Output cable length should not exceed 32.8 ft (10m).

3.Insert the input plug of Liebert GXT3 into the input power connection.

2.5.2Connecting Battery Cables

1.Switch Off the input breaker of the battery cabinet.

2.Take out the battery cable included with the battery cabinet.

3.Connect one end of the battery cable to the external battery connector on the rear panel of the UPS, and connect the other end to any battery port on the rear panel of the battery cabinet.

4.Switch On the battery breaker on the rear of the external battery cabinet.

5.Use the Configuration Program included with the UPS to specify the number of external battery cabinets connected to the Liebert GXT3. See Table 15 for approximate battery run times.

17

Image 23
Contents Liebert GXT3 UPS 120V/208V 500VA-3000VA Page Table of Contents Communication MaintenanceTroubleshooting OperationFigures Page UPS Safety Notes Important Safety PrecautionsInformation for the Protection of the Environment Battery SafetyGlossary of Symbols Available Models FeaturesUPS models, power ratings Model Nominal Power RatingVentilation Slots Operation Display Panel Rear Panel FeaturesAppearance and Components Front Panel and Controls15R OutputLiebert GXT3 208V rack/tower models-rear panel components Inverter Rectifier/Power Factor Correction PFC CircuitMajor Components Operating Mode Frequency Converter Mode Battery ModeBattery Recharge Mode What’s Included Preparation for InstallationInstallation Unpacking and InspectionFront Plastic Bezel Cover Mechanical InstallationTower Installation Connectors Spacers Support BasesCabinet Operation and Display Panel Rotated Clockwise 90 DegreesLiebert GXT3 Liebert UPS ExternalPulling inner member from each slide rail assembly Rack InstallationInstalling front member of each slide rail assembly Installing rack-mount handles Cable Connection Connecting Input Plug and LoadsConnecting Battery Cables Input circuit breaker specificationConnecting USB Communication Cables Connecting Communication CablesStandby/Manual Bypass Button Controls and Indicators1 On/Alarm Silence/Manual Battery Test Button Control ButtonsLoad Level Indicators IndicatorsLevel Indicators Battery Level Indicators UPS Status Indicator Icon Color Description UPS Status IndicatorsUPS status indicators Manual Bypass Startup Checklist for the Liebert GXT3Manual Battery Test Starting the UPSShut Down the Liebert GXT3 Disconnecting Input Power from the Liebert GXT3Liebert MultiLink Liebert IntelliSlot Communication CardsCommunication Output voltage option Configuration ProgramFactory UPS Model Default, VAC Output Voltage Option, VAC USB Port CommunicationAny-Mode Shutdown Terminal Block CommunicationLow Battery Battery Mode ShutdownOn Battery Replacement internal battery pack model number Replacing the Internal Battery PackMaintenance Battery Replacement ProceduresInternal Battery Pack Handle Pull Out with Battery Handle Battery Door Screws Front BezelBattery Connector Checking UPS Functions Battery ChargingPrecautions Checking UPS StatusIndicator Diagnosis/Audible alarm UPS SymptomsTroubleshooting IndicatorsCondition Alarm Audible AlarmAudible alarm description TroubleshootingTroubleshooting Input Breaker Battery Connectors Battery CabinetSpecifications Environmental Dimensions, D × W × H, in. mmWeight, lb. kg Operating temperature parameters Battery cabinet specificationsVAC RT Battery run timesProduct Warranty Registration Specifications Page Care Ne tIs t Twor k
Related manuals
Manual 48 pages 41.03 Kb Manual 80 pages 38.9 Kb

GXT3, 208V specifications

The Emerson 10-30 kVA, 208V uninterruptible power supply (UPS) solution is a robust system designed to provide reliable power protection for critical applications in commercial and industrial settings. This UPS is ideal for safeguarding IT equipment, communication systems, and other sensitive electronics against power disturbances and interruptions.

One of the standout features of the Emerson 10-30 kVA UPS is its modular design, allowing for flexibility and scalability. This means that as the power needs of a facility grow, the UPS can be easily expanded without requiring a complete system overhaul. This modularity contributes to a more efficient use of resources and minimizes operational costs.

The UPS also incorporates advanced technologies such as double-conversion online architecture, which provides the highest level of power quality. This technology ensures that the output power is consistently clean and stable, effectively eliminating harmful voltage fluctuations and frequency variations. Consequently, connected load receives a pure sine wave output, preventing potential damage or operational issues with sensitive equipment.

Another key feature is the high efficiency rating of the Emerson UPS, which exceeds 95 percent in typical operating conditions. This high efficiency translates to reduced energy costs and a smaller carbon footprint, aligning with modern sustainability goals. The cooling system is designed to be efficient as well, ensuring optimal performance while maintaining a compact footprint.

The user-friendly interface enhances operability, featuring an intuitive LCD display that allows for easy monitoring of critical power parameters. Users can access real-time data related to battery health, load levels, and operational status, which aids in effective management of the power supply.

Battery management is another critical aspect of the Emerson UPS. It employs advanced battery management technologies to ensure optimal battery life and performance. Features such as intelligent battery testing and monitoring help predict potential battery failures before they occur, allowing for proactive maintenance and minimized downtime.

In summary, the Emerson 10-30 kVA, 208V UPS offers a combination of modularity, high efficiency, advanced technologies, and effective power management features that cater to the demanding needs of critical applications. With its reliable performance and user-friendly operation, this UPS solution is an excellent choice for organizations looking to protect their valuable equipment from power disturbances.