Emerson GXT2-6000RTL630 user manual Install the Main Cabinet, Installation and Configuration

Page 15

Installation and Configuration

5.0INSTALLATION AND CONFIGURATION

Do NOT attempt to start the UPS, turn on any circuit breaker or energize the input power until instructed to do so in 6.0 - Initial Start-Up and Electrical Checks.

Visually inspect the UPS for freight damage. Report any damage to the carrier and your local dealer or Liebert representative.

! CAUTION

The UPS is heavy (see 13.0 - Specifications). Take proper precautions when lifting or moving it.

Install the UPS indoors in a controlled environment, where it cannot be accidentally turned off. Place it where air flows unrestricted around the unit. The installation location must be free of water, flam- mable liquids, gases, corrosives and conductive contaminants. Maintain a minimum clearance of

4 inches (100mm) in the front and rear of the UPS. Maintain an ambient temperature range of 32-104°F (0 to 40°C).

NOTE

UPS operation in sustained temperatures above 77°F (25°C) reduces battery life.

5.1Install the Main Cabinet

The GXT2-6000RTL630 may be installed in either a tower configuration or in a rack, depending on available space and use considerations. Determine the type of installation and follow the appropriate instructions in either 5.1.1 - Tower UPS Installation or 5.1.2 - Rack-Mount UPS Installation.

5.1.1Tower UPS Installation

When using the GXT2-6000RTL630 in a tower configuration, use the included support base (shown below, left) to stabilize the UPS. If any external battery cabinets are added, they will include spacers to accommodate the additional cabinets (shown below, right).

Attach Bezels to Top

When used as a tower, the GXT2-6000RTL630 requires bezels attached to the top. To connect the bezels:

1.Position the UPS so that the battery compartments are on the right side.

2.Attach the top bezels by placing them on the mounting holes and sliding them toward the rear of the UPS.

Figure 5 Tower-use support bases, spacers for external battery cabinets

3U

3U

2U

2U

5U support base for GXT2

Spacers added to support base

End bases and 3U spacer

to accommodate additional battery cabinets

11

DISCONTINUED

 

PRODUCT

Image 15
Contents Liebert GXT2-6000RTL630 DIS Product Table of Contents Operating Instructions MaintenanceTroubleshooting SpecificationsElectromagnetic Compatibility Important Safety InstructionsProduct Glossary of Symbols Introduction System Description Rectifier/Power Factor Correction PFC CircuitBattery Charger InverterBattery DC-to-DC ConverterDynamic Bypass Main Frame and Electronics Major ComponentsUpper Bezel Internal Battery Packs Connections Removable Power Distribution BoxBypass To UPS Switch ManualWHAT’S Included Configuration Disk DB-9 port coverAttach Bezels to Top Install the Main CabinetInstallation and Configuration Tower UPS InstallationReturn flanges Retaining Latches Front Innermembers members Rack-Mount UPS InstallationInstalling the Adjustable Rack-Mount Kit-Sold Separately QuantityScrews Apply grease inside Push it into the rack Install the Internal BatteriesUPS or CabinetRemove these screws to release connector Connect the Internal Batteries Using the External ConnectorConnect Input/Output Power Battery Door Captive ScrewsAttach Power Distribution Box Front of PD-L630 power distribution boxLoosen these three Distribution Box Electrical Connections External Battery Cabinet Installation Initial START-UP and Electrical Checks GXT2-6000RTL630 Configuration Program Features Configuration ProgramWhat You Will Need Standby/Manual Bypass Button ON/Alarm Silence/Manual Battery Test ButtonControls and Indicators All indicators illuminated for illustration onlyBypass Indicator LED Amber Load Level Indicators 4 Green, 1 AmberBattery Level Indicators 5 Green Fault Indicator LED RedBattery Recharge Mode Normal Mode OperationBattery Mode Operation Bypass Mode OperationDB-9 pin assignment Pin 4 Remote Shutdown on BatteryCommunications Interface Port CommunicationsLiebert’s Ocwebcard DB9 RS232 port covered UPS Intelligent CommunicationsRepo switch connection diagram Remote Emergency Power OffMaintenance Internal BatteryRetaining bracket Internal Battery ReplacementBattery Door Captive Screws 3U Battery Access Door Battery ConnectorsRear View AC Power ConnectionsDisconnect CaptiveReconnect Troubleshooting Indicator meaningsLED status Diagnosis/Audible alarm UPS Troubleshooting guideAlarm conditions Troubleshooting guide cont’dBattery run times Auto-Learning Battery Run Times UPS specifications SpecificationsOutput distribution specifications Internal battery specificationsExternal battery cabinet specifications Battery ParametersModel Number DIS Product Web Site Environmental SystemsNit

GXT2-6000RTL630 specifications

The Emerson GXT2-6000RTL630 is a high-performance uninterruptible power supply (UPS) designed to safeguard critical equipment in various applications, including data centers, telecom systems, and industrial processes. This model is part of the GXT2 series, which is renowned for its reliability and advanced features.

One of the standout characteristics of the GXT2-6000RTL630 is its robust power capacity of 6000 VA/6000 W. This makes it ideal for protecting sensitive electronic devices against power disturbances such as surges, spikes, and complete power outages. The UPS is designed to deliver clean, continuous power with a sine wave output, ensuring that all connected equipment operates optimally.

A key feature of the GXT2-6000RTL630 is its double-conversion online technology. This ensures that the UPS provides uninterrupted power supply through its inverter, converting incoming AC power to DC and then back to AC. This process isolates connected devices from power fluctuations and increases the overall reliability of the power supply. With a wide input voltage range, the UPS can adjust to varying power conditions while maintaining a stable output.

The GXT2-6000RTL630 is equipped with an intuitive LCD display. This user-friendly interface provides real-time information about the UPS status, including input/output voltage, load level, battery capacity, and alarms. This allows users to monitor the system easily and take proactive measures if necessary.

In terms of battery management, the GXT2-6000RTL630 features advanced battery charging technology. It includes a hot-swappable battery design, allowing users to replace batteries without shutting down the system. This capability reduces downtime and increases operational efficiency. Additionally, the UPS employs intelligent battery management to maximize battery life and ensure reliable operation.

Another notable feature is its network management capability. The GXT2-6000RTL630 can be connected to a network through an optional SNMP/HTTP card, enabling remote monitoring and management. This is particularly beneficial for larger installations and organizations that require centralized control over multiple units.

Furthermore, the UPS supports multiple configurations, allowing for flexibility in installation according to space and power requirements. It can be rack-mounted or placed in tower mode, making it suitable for various environments.

In summary, the Emerson GXT2-6000RTL630 is a sophisticated UPS that combines high capacity, advanced technology, and user-friendly features. Its double-conversion architecture, real-time monitoring, and intelligent battery management make it an excellent choice for anyone needing reliable power protection for critical applications. Whether for data centers, telecommunications, or industrial operations, this UPS ensures that equipment remains protected and operational, even in the face of power issues.