Emerson GXT2-6000RTL630 user manual Troubleshooting guide cont’d, Alarm conditions

Page 37

Troubleshooting

Table 3

Troubleshooting guide (cont’d)

 

 

 

 

 

 

Problem

Cause

Solution

 

 

 

 

 

 

 

If the charger is overvoltage, the UPS will shutdown. If the

Fault and LEDs D&E are

 

charger is undervoltage and the batteries are nearly depleted,

Charger malfunction

this alarm will give a temporary warning before the UPS shuts

Illuminated

 

down. UPS requires service. Contact your local dealer, Liebert

 

 

 

 

 

 

representative or Liebert Worldwide Support Group.

 

 

 

Check battery connections, completely power down and restart

 

 

 

UPS.

Battery LED is flashing.

Battery source is not

NOTE: If the battery circuit

available; continuous horn.

opens while the UPS is running,

 

 

 

 

 

it will be detected when the next

 

 

 

battery test is performed.

Table 4

Alarm conditions

 

 

 

 

Condition

 

Alarm

Battery Mode (utility failure)

One short beep every 10 seconds: more than 2 minutes of run time remaining

 

 

Low Battery

Two short beeps every 5 seconds: less than 2 minutes of run time remaining

 

 

Output Overload (Bypass)

One short beep every half second

 

 

Overtemperature (Bypass)

A one-second beep every 4 seconds

 

 

DC Bus Overvoltage (Bypass)

A one-second beep every 4 seconds

 

 

DC-DC failure during battery

A one-second beep every 4 seconds

mode

 

 

PFC Failure (Bypass)

A one-second beep every 4 seconds

 

 

Inverter Failure

A one-second beep every 4 seconds

 

 

Battery Test Failure

A two-second beep every 1 minute

 

 

Fan Locked

A one-second beep every 4 seconds

 

 

REPO Active

A 0.25-second beep every 0.25 seconds

 

 

UPS OFF; Autorestart disabled

A one-second beep every 4 seconds

from previous REPO shutdown

 

Charger Malfunction

A one-second beep every 4 seconds

 

 

 

33

DISCONTINUED

 

PRODUCT

Image 37 Contents
Liebert GXT2-6000RTL630 DIS Product Table of Contents Troubleshooting MaintenanceSpecifications Operating InstructionsElectromagnetic Compatibility Important Safety InstructionsProduct Glossary of Symbols Introduction Battery Charger Rectifier/Power Factor Correction PFC CircuitInverter System DescriptionDC-to-DC Converter BatteryDynamic Bypass Major Components Main Frame and ElectronicsUpper Bezel Internal Battery Packs Bypass To UPS Switch Removable Power Distribution BoxManual ConnectionsWHAT’S Included Configuration Disk DB-9 port coverInstallation and Configuration Install the Main CabinetTower UPS Installation Attach Bezels to TopInstalling the Adjustable Rack-Mount Kit-Sold Separately Rack-Mount UPS InstallationQuantity Return flanges Retaining Latches Front Innermembers membersScrews UPS or Install the Internal BatteriesCabinet Apply grease inside Push it into the rackConnect Input/Output Power Connect the Internal Batteries Using the External ConnectorBattery Door Captive Screws Remove these screws to release connectorFront of PD-L630 power distribution box Attach Power Distribution BoxLoosen these three Distribution Box Electrical Connections External Battery Cabinet Installation Initial START-UP and Electrical Checks Configuration Program GXT2-6000RTL630 Configuration Program FeaturesWhat You Will Need Controls and Indicators ON/Alarm Silence/Manual Battery Test ButtonAll indicators illuminated for illustration only Standby/Manual Bypass ButtonBattery Level Indicators 5 Green Load Level Indicators 4 Green, 1 AmberFault Indicator LED Red Bypass Indicator LED AmberBattery Mode Operation Normal Mode OperationBypass Mode Operation Battery Recharge ModeCommunications Interface Port Pin 4 Remote Shutdown on BatteryCommunications DB-9 pin assignmentLiebert’s Ocwebcard DB9 RS232 port covered UPS Intelligent CommunicationsRepo switch connection diagram Remote Emergency Power OffMaintenance Internal BatteryBattery Door Captive Screws 3U Battery Access Door Internal Battery ReplacementBattery Connectors Retaining bracket Disconnect AC Power Connections Captive Rear ViewReconnect Indicator meanings TroubleshootingLED status Diagnosis/Audible alarm UPS Troubleshooting guideAlarm conditions Troubleshooting guide cont’dBattery run times Auto-Learning Battery Run Times UPS specifications SpecificationsOutput distribution specifications Internal battery specificationsBattery Parameters External battery cabinet specificationsModel Number DIS Product Environmental Systems Web SiteNit