Emerson GXT2-6000RTL630 user manual Troubleshooting guide cont’d, Alarm conditions

Page 37

Troubleshooting

Table 3

Troubleshooting guide (cont’d)

 

 

 

 

 

 

Problem

Cause

Solution

 

 

 

 

 

 

 

If the charger is overvoltage, the UPS will shutdown. If the

Fault and LEDs D&E are

 

charger is undervoltage and the batteries are nearly depleted,

Charger malfunction

this alarm will give a temporary warning before the UPS shuts

Illuminated

 

down. UPS requires service. Contact your local dealer, Liebert

 

 

 

 

 

 

representative or Liebert Worldwide Support Group.

 

 

 

Check battery connections, completely power down and restart

 

 

 

UPS.

Battery LED is flashing.

Battery source is not

NOTE: If the battery circuit

available; continuous horn.

opens while the UPS is running,

 

 

 

 

 

it will be detected when the next

 

 

 

battery test is performed.

Table 4

Alarm conditions

 

 

 

 

Condition

 

Alarm

Battery Mode (utility failure)

One short beep every 10 seconds: more than 2 minutes of run time remaining

 

 

Low Battery

Two short beeps every 5 seconds: less than 2 minutes of run time remaining

 

 

Output Overload (Bypass)

One short beep every half second

 

 

Overtemperature (Bypass)

A one-second beep every 4 seconds

 

 

DC Bus Overvoltage (Bypass)

A one-second beep every 4 seconds

 

 

DC-DC failure during battery

A one-second beep every 4 seconds

mode

 

 

PFC Failure (Bypass)

A one-second beep every 4 seconds

 

 

Inverter Failure

A one-second beep every 4 seconds

 

 

Battery Test Failure

A two-second beep every 1 minute

 

 

Fan Locked

A one-second beep every 4 seconds

 

 

REPO Active

A 0.25-second beep every 0.25 seconds

 

 

UPS OFF; Autorestart disabled

A one-second beep every 4 seconds

from previous REPO shutdown

 

Charger Malfunction

A one-second beep every 4 seconds

 

 

 

33

DISCONTINUED

 

PRODUCT

Image 37
Contents Liebert GXT2-6000RTL630 DIS Product Table of Contents Troubleshooting MaintenanceSpecifications Operating InstructionsElectromagnetic Compatibility Important Safety InstructionsProduct Glossary of Symbols Introduction Battery Charger Rectifier/Power Factor Correction PFC CircuitInverter System DescriptionDC-to-DC Converter BatteryDynamic Bypass Major Components Main Frame and ElectronicsUpper Bezel Internal Battery Packs Bypass To UPS Switch Removable Power Distribution BoxManual ConnectionsWHAT’S Included Configuration Disk DB-9 port coverInstallation and Configuration Install the Main CabinetTower UPS Installation Attach Bezels to TopInstalling the Adjustable Rack-Mount Kit-Sold Separately Rack-Mount UPS InstallationQuantity Return flanges Retaining Latches Front Innermembers membersScrews UPS or Install the Internal BatteriesCabinet Apply grease inside Push it into the rackConnect Input/Output Power Connect the Internal Batteries Using the External ConnectorBattery Door Captive Screws Remove these screws to release connectorFront of PD-L630 power distribution box Attach Power Distribution BoxLoosen these three Distribution Box Electrical Connections External Battery Cabinet Installation Initial START-UP and Electrical Checks Configuration Program GXT2-6000RTL630 Configuration Program FeaturesWhat You Will Need Controls and Indicators ON/Alarm Silence/Manual Battery Test ButtonAll indicators illuminated for illustration only Standby/Manual Bypass ButtonBattery Level Indicators 5 Green Load Level Indicators 4 Green, 1 AmberFault Indicator LED Red Bypass Indicator LED AmberBattery Mode Operation Normal Mode OperationBypass Mode Operation Battery Recharge ModeCommunications Interface Port Pin 4 Remote Shutdown on BatteryCommunications DB-9 pin assignmentLiebert’s Ocwebcard DB9 RS232 port covered UPS Intelligent CommunicationsRepo switch connection diagram Remote Emergency Power OffMaintenance Internal BatteryBattery Door Captive Screws 3U Battery Access Door Internal Battery ReplacementBattery Connectors Retaining bracketDisconnect AC Power ConnectionsCaptive Rear ViewReconnect Indicator meanings TroubleshootingLED status Diagnosis/Audible alarm UPS Troubleshooting guideAlarm conditions Troubleshooting guide cont’dBattery run times Auto-Learning Battery Run Times UPS specifications SpecificationsOutput distribution specifications Internal battery specificationsBattery Parameters External battery cabinet specificationsModel Number DIS Product Environmental Systems Web SiteNit

GXT2-6000RTL630 specifications

The Emerson GXT2-6000RTL630 is a high-performance uninterruptible power supply (UPS) designed to safeguard critical equipment in various applications, including data centers, telecom systems, and industrial processes. This model is part of the GXT2 series, which is renowned for its reliability and advanced features.

One of the standout characteristics of the GXT2-6000RTL630 is its robust power capacity of 6000 VA/6000 W. This makes it ideal for protecting sensitive electronic devices against power disturbances such as surges, spikes, and complete power outages. The UPS is designed to deliver clean, continuous power with a sine wave output, ensuring that all connected equipment operates optimally.

A key feature of the GXT2-6000RTL630 is its double-conversion online technology. This ensures that the UPS provides uninterrupted power supply through its inverter, converting incoming AC power to DC and then back to AC. This process isolates connected devices from power fluctuations and increases the overall reliability of the power supply. With a wide input voltage range, the UPS can adjust to varying power conditions while maintaining a stable output.

The GXT2-6000RTL630 is equipped with an intuitive LCD display. This user-friendly interface provides real-time information about the UPS status, including input/output voltage, load level, battery capacity, and alarms. This allows users to monitor the system easily and take proactive measures if necessary.

In terms of battery management, the GXT2-6000RTL630 features advanced battery charging technology. It includes a hot-swappable battery design, allowing users to replace batteries without shutting down the system. This capability reduces downtime and increases operational efficiency. Additionally, the UPS employs intelligent battery management to maximize battery life and ensure reliable operation.

Another notable feature is its network management capability. The GXT2-6000RTL630 can be connected to a network through an optional SNMP/HTTP card, enabling remote monitoring and management. This is particularly beneficial for larger installations and organizations that require centralized control over multiple units.

Furthermore, the UPS supports multiple configurations, allowing for flexibility in installation according to space and power requirements. It can be rack-mounted or placed in tower mode, making it suitable for various environments.

In summary, the Emerson GXT2-6000RTL630 is a sophisticated UPS that combines high capacity, advanced technology, and user-friendly features. Its double-conversion architecture, real-time monitoring, and intelligent battery management make it an excellent choice for anyone needing reliable power protection for critical applications. Whether for data centers, telecommunications, or industrial operations, this UPS ensures that equipment remains protected and operational, even in the face of power issues.