CONFIGURATION PROGRAM
This is a new feature included with the new Liebert GXT2U line. Several UPS settings that were previously not available or required custom manufacturing may now be modified using this program. For most users, the factory default settings will be adequate. This manual illustrates the features available for modification, as well as the factory default setting.
NOTE
The UPS must be turned
While the UPS is in Normal Mode operation, press the OFF button once to put the UPS into Bypass Mode.
Once the UPS is in Bypass Mode operation, press and release the OFF button two distinct times (for about a second each time) to turn off the UPS.
Liebert GXT2U Configuration Program Abilities
•Select one of five output voltages to match voltages found around the world.
•Enable/Disable
•Select frequency converter operation with a fixed output frequency of 50 or 60 Hz.
•Set the Low Battery Warning alarm time from 2 to 30 minutes.
•Enable/Disable the
•Set the
•Select the number of external battery cabinets connected to the UPS to adjust the remaining run time calculations reported by Liebert software products.
•Modify the shutdown setting of
NOTE
This program is compatible with UPS models beginning with
What You Will Need
In addition to the Liebert GXT2U UPS, you will need the configuration program diskette and serial cable (beige or tan,
22