Emerson 30-130 kVA installation manual Battery Power Pack, 25-Inch Cabinet

Page 43

BATTERY SERVICE ACCESS

CASTER CENTERS

12mm DIA. THREADED MOUNTING HOLE (4) TYP.

(SEE NOTES 12 & 13)

(SEE DETAIL A)

NOTES:

1.

ALL DIMENSIONS ARE IN INCHES.

2.

MIN CLEARANCE 36 INCHES IN FRONT, 12 INCHES

AT TOP FOR AIR EXHAUST.

3.

KEEP CABINET WITHIN 15° OF VERTICAL WHILE

HANDLING.

Figure 14

BIB

CONDUIT ENTRY 6.5 x 6.0

TOP ONLY

2 PLACES

MAX DOOR SWING 120°

2.72

12MM

 

CASTER

CENTERS

 

 

CENTERS

 

FRONT

 

 

12MM THREADED

 

MOUNTING HOLE

LEVELER

12MM CENTERS

DETAIL A

4.

EXTERIOR CABLE ENTRY AVAILABLE THROUGH

REMOVABLE TOP ACCESS PLATES. REMOVE, PUNCH

TO SUIT CONDUIT SIZE, AND REPLACE.

5.

CONTROL WIRING AND POWER WIRING MUST BE RUN

IN SEPARATE CONDUIT.

6.

ALUMINUM AND COPPER CLAD ALUMINUM CABLES ARE

NOT RECOMMENDED.

7.

ALL WIRING IS TO BE IN ACCORDANCE WITH

NATIONAL AND LOCAL ELECTRICAL CODES.

8.

RECOMMENDED OPERATING TEMPERATURE RANGE:

Outline Drawing,

BOARD

ACCESS

TOP VIEW

CENTER

GRAVITY

BOTTOM VIEW

CIRCUIT

BREAKER

CIRCUITMOTOR

BREAKER OPERATOR

OPTIONAL

DC BUS BARS

BATTERIES

NOTE:

(10)TRAY SHOWN.

(8)TRAY FOR FR200 BATTERY ASSY AND SMALLER

SUPPORT TRAY & SUPPORT BRACKET (SEE NOTE 15)

REAR OF UNIT SHOWN

WITHOUT SIDE PANEL

DC BUS BARS

CONTROL AND POWER WIRE SIDE ACCESS APPROX AREA 4.6 x 2.2

(BOTH SIDES)

CENTER

GRAVITY

68°F-77°F (20°C-25°C).

9. COLOR - IBM OFF WHITE.

10. UNIT BOTTOM IS STRUCTURALLY ADEQUATE FOR

FORKLIFT HANDLING.

11. APPROX WEIGHT OF CABINET IS 1500 TO 3000 LBS.

12. THREADED MOUNTING HOLES USED FOR SEISMIC

ANCHORING OR FLOORSTAND. NOTE, IF FLOORSTAND

IS USED THE WEIGHT OF THE UNIT MUST BE

SUPPORTED UNDER ALL CASTERS.

13. EACH MOUNTING LOCATION IS SUPPORTED

BY (2) 10 GA. (.135") GALVANIZED STEEL. THE THREADED 12MM INSERT IS APPROX. 3/4" DEEP.

MOUNTING BOLTS MUST BE THREADED INTO UNIT MOUNTING HOLES FROM UNDERNEATH UNIT BASE.

14.REFER TO DETAIL A FOR DIMENSION TO FRAME WITH SIDE PANEL REMOVED. SIDE PANELS ARE REMOVED BETWEEN ADJACENT UNITS WHICH ARE BOLTED TOGETHER.

15."BEFORE SLIDING OUT BATTERIES ON BATTERY TRAY" POSITION SUPPORT TRAY AND ATTACH TO CABINET. THEN SECURE (2) SUPPORT BRACKETS TO THE SUPPORT TRAY AND TO THE CABINET. REFER TO THE APPROPRIATE USERS MANUAL FOR FURTHER DESCRIPTION & DETAILS.

Battery Power Pack, 25-Inch Cabinet

Installation Drawings 33

FRONT VIEW

FRONT VIEW

 

 

 

WITH DOOR AND

 

SIDE VIEW

 

 

 

 

WITH DOOR

WITH COVER REMOVED

 

BARRIER REMOVED

DETAIL FOR DC BUS BARS

 

 

 

 

DRAWN BY

 

 

 

 

V CARMONA

OUTLINE DRAWING

 

 

 

CHK BY

DWG. NO.

 

 

25" BATTERY CABINET

 

 

 

 

UBC11001

 

 

NPOWER

 

 

REF. DWG.

REV. NO.

DATE

1050 DEARBORN DRIVE,

 

 

 

3

1/22/03

COLUMBUS, OHIO 43229

 

 

FILE NAME: Batts\UBC11001-03

 

Image 43
Contents 1SRZHU Before YOU Call $51,1 Important Safety InstructionsPage Table of Contents Page List of Figures 6FKHPDWLFLDJUDP0DLQWHQDQFH%\SDVV,QWHUORFN6\VWHPZLWK32 List of Tables Page 127 Safety PrecautionsWHPSHUDWXUHVFDQFDXVHVLJQLILFDQWO\UHGXFHGEDWWHU\OLIH Installation Considerations$7&1752*5$9,760%2/6$1750,1 Unloading and Handling Unloading and HandlingFork Locations Internal Inspections External InspectionsInspections Special Considerations for 1+1 Redundant Systems General InstructionsEquipment Location Battery Installation Battery Safety Precautions3RUWHUGHVJDQWVHWGHVERWWHVGHFDRXWFKRXF Dffxpxodwhxuv Glvwdqfhv Matching Battery CabinetsEhuwvdohvuhsuhvhqwdwlyhuhjduglqjwklvrswlrq Non-Standard Batteries1276 Configuring Your Neutral and Ground ConnectionsOdwhuvhfwlrqv 1276 Wudqvihudqguhwudqvihurshudwlrqv 7KH56DQGPRGHOVFDQRQO\VXSSRUWZLUHORDGV RWK836PRGXOHVPXVWVKDUHDFRPPRQE\SDVVVRXUFH Grounding for A/B or G/H UPS Models, 1+1 ConfigurationEHIRUHFRQQHFWLQJWKHPRGXOHVWRWKH3DUDOOHOLQJ&DELQHW Grounding for D/E or K/L UPS Models, 1+1 ConfigurationGrounding Diagram, R/S or X/Y UPS Models, 1+1 Configuration Grounding for R/S or X/Y UPS Models, 1+1 ConfigurationWklvpdqxdo Grounding Configurations, Battery SystemsWiring Considerations 3RZHUDQGFRQWUROZLULQJPXVWEHVHSDUDWHG Power WiringUxqlqdvhsdudwhfrqgxlwwrplqlplhfrqwurovljqdolqwhuihuhqfh Control Wiring5HIHUWRLJXUH Ljxuh Ljxuh Dqgljxuh $1*5 Battery WiringDSSURSULDWHIDFWRU\IXUQLVKHGFDEOHV Wiring Connections127 Power Wiring Terminals Factory Supplied Wiring InspectionCopper Aluminum or Copper-Clad Aluminum Outline Drawing, 30-50 kVA UPS Installation DrawingsOutline Drawing, 65-80 kVA UPS Outline Drawing, 100-130 kVA UPS Battery Power Pack, 25-Inch Cabinet Outline Drawing Outline Drawing, Maintenance Bypass Cabinet, L Configuration Outline Drawing, Maintenance Bypass Cabinet, N Configuration Outline Drawing, Maintenance Bypass Cabinet, P Configuration Outline Drawing, Maintenance Bypass Cabinet, Q Configuration Installation Drawings Installation Drawings Installation Drawings Installation Drawings Installation Drawings Outline Drawing Outline Drawing, 1+1 Paralleling Panelboard, Configuration N Size B Configuration N, Size C Outline Drawing, Seismic Anchoring, 30-50 kVA UPS Outline Drawing, Seismic Anchoring, 65-80 kVA UPS Outline Drawing, Seismic Anchoring, 100-130 kVA UPS Outline Drawing, Remote Battery Breaker 30 130 kVA Installation Drawings Outline Drawing, Remote Battery Breaker with BIB Installed Outline Drawing, Remote Alarm Status Panel Outline Drawing, LBS Control Panel Outline Drawing, LBS Alarm Status Contacts Outline Drawing, LBS Transformer Panel Installation Drawings Installation Drawings Control Wiring, 30 130 kVA UPS Control Wiring, 1+1 Category 5 Patch Cable Connection Control Wiring, 1+1 Twisted-Pair Cable Connection Control Wiring, Remote Alarm Status Panel Option Control Wiring, 2 or 3 Remote Alarm Status Panels Installation Drawings Control Wiring, Site Scan Interface Control Wiring, Programmable Relay Board Option Control Wiring, Input Contact Isolator Board Control Wiring, NIC Option Control Wiring, Power Supply Option Control Wiring, Internal Modem Option Control Wiring, AS 400 Signal Cable Option Control Wiring, Open Wire Cable Adaptor Option Control Connection Diagram 50 --130 kVA Control Connection Location Diagram, 30-130 kVA UPS Terminal Details, 30 50 kVA UPS Terminal Details, 65 80 kVA UPS Terminal Details, 100 130 kVA UPS Schematic Diagram Maintenance Bypass Interlock System Installation Drawings Line-Up Detail Maintenance Bypass and Distribution Cabinets Wiring Diagram, UPS with Single Battery Cabinet Installation Drawings Installation Drawings 480 or 208 VAC Input Appendix a Site Planning Data600VAC Input Site Planning DataSite Planning Data 220 or 240 VAC Input Page Page Locations Technical Support/ServicePower Protection Company Behind the Products