Appendix A: Site Planning Data | 480 or 208 VAC Input |
UPS |
|
| Standard AC Input | AC Input with Filter | AC Output | ||||||
Rating | AC Voltage | without Filter |
| Option | Current | ||||||
|
|
|
|
|
| Recom- |
|
| Recom- |
|
|
|
|
|
|
|
| mended |
|
| mended |
| Rec. |
kVA | kW | Input | Output | Nom | Max | OPCD | Nom | Max | OCPD | Nom | OPCD |
|
|
|
|
| Concen- |
| |
| Max. | Max. Heat |
| Approx. | trated |
| |
| Battery | Dissipation | Dimensions | Unpacked | Floor | Cooling | |
Battery | Disch. | BTU/hr | WxDxH | Weight | Loading | ||
Air | |||||||
KW | (Amps) | Full Load | (Inches) | (Pounds) | (Lb/SqFt) | (CFM) |
30 |
| 24 | 208 | 208 | 92 | 114 | 150 | 80 |
| 99 | 125 | 83 | 125 | 26 | 66 | 8,500 | 32x32.5x71 | 2,200 |
| 307 |
| 720 |
30 |
| 24 | 480 | 208 | 38 | 48 | 70 | 33 |
| 41 | 50 | 83 | 125 | 26 | 66 | 7,500 | 32x32.5x71 | 2,100 |
| 294 |
| 720 |
30 |
| 24 | 480 | 480 | 38 | 48 | 70 | 33 |
| 41 | 50 | 36 | 50 | 26 | 66 | 7,500 | 32x32.5x71 | 1,900 |
| 265 |
| 720 |
40 |
| 32 | 208 | 208 | 122 | 153 | 200 | 106 |
| 133 | 175 | 111 | 150 | 34 | 88 | 11,000 | 32x32.5x71 | 2,200 |
| 307 |
| 720 |
40 |
| 32 | 480 | 208 | 51 | 64 | 90 | 44 |
| 55 | 70 | 111 | 150 | 34 | 88 | 10,000 | 32x32.5x71 | 2,100 |
| 294 |
| 720 |
40 |
| 32 | 480 | 480 | 51 | 64 | 90 | 44 |
| 55 | 70 | 48 | 60 | 34 | 88 | 10,000 | 32x32.5x71 | 1,900 |
| 265 |
| 720 |
50 |
| 40 | 208 | 208 | 153 | 191 | 250 | 133 |
| 166 | 200 | 139 | 175 | 43 | 109 | 14,000 | 32x32.5x71 | 2,200 |
| 307 |
| 720 |
50 |
| 40 | 480 | 208 | 64 | 80 | 100 | 55 |
| 69 | 100 | 139 | 175 | 43 | 109 | 12,000 | 32x32.5x71 | 2,100 |
| 294 |
| 720 |
50 |
| 40 | 480 | 480 | 64 | 80 | 100 | 55 |
| 69 | 100 | 60 | 80 | 43 | 109 | 12,000 | 32x32.5x71 | 1,900 |
| 265 |
| 720 |
65 |
| 52 | 208 | 208 | 193 | 242 | 350 | 171 |
| 213 | 300 | 180 | 225 | 55 | 141 | 18,000 | 39x32.5x71 | 2,700 |
| 304 |
| 960 |
65 |
| 52 | 480 | 208 | 80 | 99 | 150 | 70 |
| 88 | 125 | 180 | 225 | 55 | 141 | 15,000 | 39x32.5x71 | 2,500 |
| 284 |
| 960 |
65 |
| 52 | 480 | 480 | 80 | 99 | 150 | 70 |
| 88 | 125 | 78 | 100 | 55 | 141 | 15,000 | 39x32.5x71 | 2,300 |
| 262 |
| 960 |
80 |
| 64 | 208 | 208 | 238 | 298 | 400 | 210 |
| 262 | 350 | 222 | 300 | 68 | 174 | 22,000 | 39x32.5x71 | 2,700 |
| 304 |
| 960 |
80 |
| 64 | 480 | 208 | 98 | 122 | 175 | 87 |
| 108 | 150 | 222 | 300 | 68 | 174 | 18,000 | 39x32.5x71 | 2,500 |
| 284 |
| 960 |
80 |
| 64 | 480 | 480 | 98 | 122 | 175 | 87 |
| 108 | 150 | 96 | 125 | 68 | 174 | 18,000 | 39x32.5x71 | 2,300 |
| 262 |
| 960 |
100 |
| 80 | 208 | 208 | 296 | 370 | 500 | 261 |
| 326 | 400 | 278 | 350 | 85 | 218 | 26,000 | 49x32.5x71 | 3,800 |
| 342 |
| 1440 |
100 |
| 80 | 480 | 208 | 122 | 152 | 225 | 108 |
| 135 | 175 | 278 | 350 | 85 | 218 | 21,000 | 49x32.5x71 | 3,600 |
| 324 |
| 1440 |
100 |
| 80 | 480 | 480 | 122 | 152 | 225 | 108 |
| 135 | 175 | 120 | 150 | 85 | 218 | 21,000 | 49x32.5x71 | 3,400 |
| 305 |
| 1440 |
130 |
| 104 | 208 | 208 | 385 | 481 | 700 | 339 |
| 420 | 500 | 361 | 450 | 111 | 283 | 33,000 | 49x32.5x71 | 3,800 |
| 342 |
| 1440 |
130 |
| 104 | 480 | 208 | 158 | 198 | 300 | 140 |
| 175 | 225 | 361 | 450 | 111 | 283 | 27,000 | 49x32.5x71 | 3,600 |
| 324 |
| 1440 |
130 |
| 104 | 480 | 480 | 158 | 198 | 300 | 140 |
| 175 | 225 | 156 | 200 | 111 | 283 | 27,000 | 49x32.5x71 | 3,400 |
| 305 |
| 1440 |
Notes: |
|
| — |
| 1,3,4,5,7,8, 9,11,12, 13 |
|
| 2,3,5,7,8,9,11,12 | 6,8,9,11,12 | 14 | 14 | — |
| — |
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Notes For Table:
1.Nominal rectifier AC input current (considered continuous) is based on full rated output load. Maximum current includes nominal input current and maximum battery recharge current (considered noncontinuous). Continuous and noncontinuous current limit are defined in NEC 100. Maximum input current is controlled by current limit setting which is adjustable. Values shown are for maxi- mum setting of 125%. Standard factory setting is 115%.
2.Nominal AC output current (considered continuous) is based on full rated output load.
3.OCPD=Overcurrent Protection Device.
4.Feeder protection (by others in external equipment) for rectifier AC input and bypass AC input is recommended to be provided by separate overcurrent protection devices.
5.UPS output load cables must be run in separate conduit from input cables.
6.Power cable from module DC bus to battery should be sized for a total maximum 2.0 volt line drop (measured at the module) at maximum discharge current.
7.Grounding conductors to be sized per NEC
8.Rectifier AC Input:
9.All wiring is to be in accordance with National and Local Electrical Codes.
10.Minimum access clearance is 3 feet front and 1 foot above UPS.
11.Top or bottom cable entry through removable access plates. Cut plate to suit conduit size. Conduit or wireway must not obstruct removal of top panels.
12.Control wiring and power cables must be run in separate conduits. Control wiring must be stranded tinned conductors.
13.10% maximum input harmonic current and
14.Dimensions and weights shown do not include Battery Cabinet,