Emerson 30-130 kVA installation manual Appendix a Site Planning Data, 480 or 208 VAC Input

Page 95

Appendix A: Site Planning Data

480 or 208 VAC Input

UPS

 

 

Standard AC Input

AC Input with Filter

AC Output

Rating

AC Voltage

without Filter

 

Option

Current

 

 

 

 

 

 

Recom-

 

 

Recom-

 

 

 

 

 

 

 

 

mended

 

 

mended

 

Rec.

kVA

kW

Input

Output

Nom

Max

OPCD

Nom

Max

OCPD

Nom

OPCD

 

 

 

 

 

Concen-

 

 

Max.

Max. Heat

 

Approx.

trated

 

 

Battery

Dissipation

Dimensions

Unpacked

Floor

Cooling

Battery

Disch.

BTU/hr

WxDxH

Weight

Loading

Air

KW

(Amps)

Full Load

(Inches)

(Pounds)

(Lb/SqFt)

(CFM)

30

 

24

208

208

92

114

150

80

 

99

125

83

125

26

66

8,500

32x32.5x71

2,200

 

307

 

720

30

 

24

480

208

38

48

70

33

 

41

50

83

125

26

66

7,500

32x32.5x71

2,100

 

294

 

720

30

 

24

480

480

38

48

70

33

 

41

50

36

50

26

66

7,500

32x32.5x71

1,900

 

265

 

720

40

 

32

208

208

122

153

200

106

 

133

175

111

150

34

88

11,000

32x32.5x71

2,200

 

307

 

720

40

 

32

480

208

51

64

90

44

 

55

70

111

150

34

88

10,000

32x32.5x71

2,100

 

294

 

720

40

 

32

480

480

51

64

90

44

 

55

70

48

60

34

88

10,000

32x32.5x71

1,900

 

265

 

720

50

 

40

208

208

153

191

250

133

 

166

200

139

175

43

109

14,000

32x32.5x71

2,200

 

307

 

720

50

 

40

480

208

64

80

100

55

 

69

100

139

175

43

109

12,000

32x32.5x71

2,100

 

294

 

720

50

 

40

480

480

64

80

100

55

 

69

100

60

80

43

109

12,000

32x32.5x71

1,900

 

265

 

720

65

 

52

208

208

193

242

350

171

 

213

300

180

225

55

141

18,000

39x32.5x71

2,700

 

304

 

960

65

 

52

480

208

80

99

150

70

 

88

125

180

225

55

141

15,000

39x32.5x71

2,500

 

284

 

960

65

 

52

480

480

80

99

150

70

 

88

125

78

100

55

141

15,000

39x32.5x71

2,300

 

262

 

960

80

 

64

208

208

238

298

400

210

 

262

350

222

300

68

174

22,000

39x32.5x71

2,700

 

304

 

960

80

 

64

480

208

98

122

175

87

 

108

150

222

300

68

174

18,000

39x32.5x71

2,500

 

284

 

960

80

 

64

480

480

98

122

175

87

 

108

150

96

125

68

174

18,000

39x32.5x71

2,300

 

262

 

960

100

 

80

208

208

296

370

500

261

 

326

400

278

350

85

218

26,000

49x32.5x71

3,800

 

342

 

1440

100

 

80

480

208

122

152

225

108

 

135

175

278

350

85

218

21,000

49x32.5x71

3,600

 

324

 

1440

100

 

80

480

480

122

152

225

108

 

135

175

120

150

85

218

21,000

49x32.5x71

3,400

 

305

 

1440

130

 

104

208

208

385

481

700

339

 

420

500

361

450

111

283

33,000

49x32.5x71

3,800

 

342

 

1440

130

 

104

480

208

158

198

300

140

 

175

225

361

450

111

283

27,000

49x32.5x71

3,600

 

324

 

1440

130

 

104

480

480

158

198

300

140

 

175

225

156

200

111

283

27,000

49x32.5x71

3,400

 

305

 

1440

Notes:

 

 

 

1,3,4,5,7,8, 9,11,12, 13

 

 

2,3,5,7,8,9,11,12

6,8,9,11,12

14

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes For Table:

1.Nominal rectifier AC input current (considered continuous) is based on full rated output load. Maximum current includes nominal input current and maximum battery recharge current (considered noncontinuous). Continuous and noncontinuous current limit are defined in NEC 100. Maximum input current is controlled by current limit setting which is adjustable. Values shown are for maxi- mum setting of 125%. Standard factory setting is 115%.

2.Nominal AC output current (considered continuous) is based on full rated output load.

3.OCPD=Overcurrent Protection Device.

4.Feeder protection (by others in external equipment) for rectifier AC input and bypass AC input is recommended to be provided by separate overcurrent protection devices.

5.UPS output load cables must be run in separate conduit from input cables.

6.Power cable from module DC bus to battery should be sized for a total maximum 2.0 volt line drop (measured at the module) at maximum discharge current.

7.Grounding conductors to be sized per NEC 250-122. Neutral conductors to be sized for full capacity for systems with 4-wire loads, 310-15 (b) (4), per NEC, and half capacity for systems with 3- wire loads.

8.Rectifier AC Input: 3-phase, 3-wire, plus ground. AC Output to Load: 3-phase, 3 or 4-wire, plus ground. Bypass AC Input: 3-phase, 3 or 4-wire, plus ground. Module DC Input from Battery: 2-wire, (positive and negative).

9.All wiring is to be in accordance with National and Local Electrical Codes.

10.Minimum access clearance is 3 feet front and 1 foot above UPS.

11.Top or bottom cable entry through removable access plates. Cut plate to suit conduit size. Conduit or wireway must not obstruct removal of top panels.

12.Control wiring and power cables must be run in separate conduits. Control wiring must be stranded tinned conductors.

13.10% maximum input harmonic current and 0.92-0.95 lagging input power factor at full load with optional input filter. 30% maximum input harmonic current and 0.85 lagging input power factor at full load without optional input filter.

14.Dimensions and weights shown do not include Battery Cabinet, Slim-Line Distribution Cabinet or other options.

85

Image 95
Contents 1SRZHU Before YOU Call $51,1 Important Safety InstructionsPage Table of Contents Page List of Figures 6FKHPDWLFLDJUDP0DLQWHQDQFH%\SDVV,QWHUORFN6\VWHPZLWK32 List of Tables Page 127 Safety PrecautionsWHPSHUDWXUHVFDQFDXVHVLJQLILFDQWO\UHGXFHGEDWWHU\OLIH Installation Considerations$7&1752*5$9,760%2/6$1750,1 Unloading and Handling Unloading and HandlingFork Locations Inspections External InspectionsInternal Inspections Equipment Location General InstructionsSpecial Considerations for 1+1 Redundant Systems Battery Installation Battery Safety Precautions3RUWHUGHVJDQWVHWGHVERWWHVGHFDRXWFKRXF Dffxpxodwhxuv Glvwdqfhv Matching Battery CabinetsEhuwvdohvuhsuhvhqwdwlyhuhjduglqjwklvrswlrq Non-Standard Batteries1276 Configuring Your Neutral and Ground ConnectionsOdwhuvhfwlrqv 1276 Wudqvihudqguhwudqvihurshudwlrqv 7KH56DQGPRGHOVFDQRQO\VXSSRUWZLUHORDGV RWK836PRGXOHVPXVWVKDUHDFRPPRQE\SDVVVRXUFH Grounding for A/B or G/H UPS Models, 1+1 ConfigurationEHIRUHFRQQHFWLQJWKHPRGXOHVWRWKH3DUDOOHOLQJ&DELQHW Grounding for D/E or K/L UPS Models, 1+1 ConfigurationGrounding Diagram, R/S or X/Y UPS Models, 1+1 Configuration Grounding for R/S or X/Y UPS Models, 1+1 ConfigurationWklvpdqxdo Grounding Configurations, Battery SystemsWiring Considerations 3RZHUDQGFRQWUROZLULQJPXVWEHVHSDUDWHG Power WiringUxqlqdvhsdudwhfrqgxlwwrplqlplhfrqwurovljqdolqwhuihuhqfh Control Wiring5HIHUWRLJXUH Ljxuh Ljxuh Dqgljxuh $1*5 Battery WiringDSSURSULDWHIDFWRU\IXUQLVKHGFDEOHV Wiring Connections127 Power Wiring Terminals Factory Supplied Wiring InspectionCopper Aluminum or Copper-Clad Aluminum Outline Drawing, 30-50 kVA UPS Installation DrawingsOutline Drawing, 65-80 kVA UPS Outline Drawing, 100-130 kVA UPS Battery Power Pack, 25-Inch Cabinet Outline Drawing Outline Drawing, Maintenance Bypass Cabinet, L Configuration Outline Drawing, Maintenance Bypass Cabinet, N Configuration Outline Drawing, Maintenance Bypass Cabinet, P Configuration Outline Drawing, Maintenance Bypass Cabinet, Q Configuration Installation Drawings Installation Drawings Installation Drawings Installation Drawings Installation Drawings Outline Drawing Outline Drawing, 1+1 Paralleling Panelboard, Configuration N Size B Configuration N, Size C Outline Drawing, Seismic Anchoring, 30-50 kVA UPS Outline Drawing, Seismic Anchoring, 65-80 kVA UPS Outline Drawing, Seismic Anchoring, 100-130 kVA UPS Outline Drawing, Remote Battery Breaker 30 130 kVA Installation Drawings Outline Drawing, Remote Battery Breaker with BIB Installed Outline Drawing, Remote Alarm Status Panel Outline Drawing, LBS Control Panel Outline Drawing, LBS Alarm Status Contacts Outline Drawing, LBS Transformer Panel Installation Drawings Installation Drawings Control Wiring, 30 130 kVA UPS Control Wiring, 1+1 Category 5 Patch Cable Connection Control Wiring, 1+1 Twisted-Pair Cable Connection Control Wiring, Remote Alarm Status Panel Option Control Wiring, 2 or 3 Remote Alarm Status Panels Installation Drawings Control Wiring, Site Scan Interface Control Wiring, Programmable Relay Board Option Control Wiring, Input Contact Isolator Board Control Wiring, NIC Option Control Wiring, Power Supply Option Control Wiring, Internal Modem Option Control Wiring, AS 400 Signal Cable Option Control Wiring, Open Wire Cable Adaptor Option Control Connection Diagram 50 --130 kVA Control Connection Location Diagram, 30-130 kVA UPS Terminal Details, 30 50 kVA UPS Terminal Details, 65 80 kVA UPS Terminal Details, 100 130 kVA UPS Schematic Diagram Maintenance Bypass Interlock System Installation Drawings Line-Up Detail Maintenance Bypass and Distribution Cabinets Wiring Diagram, UPS with Single Battery Cabinet Installation Drawings Installation Drawings 480 or 208 VAC Input Appendix a Site Planning Data600VAC Input Site Planning DataSite Planning Data 220 or 240 VAC Input Page Page Locations Technical Support/ServicePower Protection Company Behind the Products