Emerson 1500, 3000 Important Safety Instructions, Size of Branch Circuit Overcurrent Protection

Page 5

IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS

This manual contains important instructions that should be followed during installation and mainte- nance of the UPS.

Intended for installation in a temperature-controlled, indoor area free of conductive contaminants.

Maximum ambient temperature 104°F (40°C).

Read this manual thoroughly before attempting to install or operate this UPS.

The equipment can be installed and operated by individuals without previous training.

Size of Branch Circuit Overcurrent Protection

! CAUTION

To reduce the risk of fire, connect PS3000RT3-120XR models only to a circuit provided with 30 amperes maximum branch circuit overcurrent protection in accordance with the National Electric Code, ANSI/NFPA 70. Other Liebert PSI models must be connected to a circuit with 20 amperes maximum branch circuit overcurrent protection.

! WARNING

Operate the UPS only from a properly grounded (earthed) 110-127VAC, 50Hz or 60Hz AC supply.

Some components are live, even when AC power is disconnected. For service, contact a properly trained and qualified technician. Do not remove the cover; the UPS has no user-serviceable parts inside except the internal battery pack.

! WARNING

Although the UPS has been designed and manufactured to ensure personal safety, improper use can result in electrical shock or fire. To ensure safety, observe the following rules:

Turn Off and unplug the UPS before cleaning it. Clean the UPS with a dry cloth. Do not use liquid or aerosol cleaners.

Do not install or operate the UPS in or near water.

Never block or insert any objects into the ventilation holes or other openings of the UPS. Keep all vents free of dust accumulation that could restrict air flow.

Do not place UPS power cord anywhere it might be damaged.

Battery Handling Precautions

! WARNING

Batteries should be replaced only by properly trained and qualified personnel knowledgeable of batteries and required precautions.

A battery can present a risk of electrical shock and high short-circuit current. The following precautions must be observed when working on batteries:

Remove watches, rings and other metal objects.

Use tools with insulated handles.

Do not dispose of the battery or batteries in a fire. The battery may explode.

Do not open or mutilate the battery or batteries. Released electrolyte is toxic. It may cause injury to the skin and eyes.

When replacing the battery, use the same type of battery as is listed in Table 5.

Handle, transport and recycle batteries in accordance with local regulations.

1

Image 5
Contents Liebert PSI XR Page Table of Contents Communication Battery MaintenanceSize of Branch Circuit Overcurrent Protection Important Safety InstructionsPage Status Change Button Glossary of SymbolsClosure Port 15A for 1500VA Nema 5-15R Introduction3000-rear view Rear viewWHAT’S Included Preparation InstallationRelative humidity Non-condensingStep Tower UPS InstallationConvert the Liebert PSI XR for rack installation Rack-Mount UPS Conversion and InstallationConnect Input Power and Load Orient Display for InstallationCharge Batteries and Perform Battery Startup Connect Communication Interface Connect Network Surge protectionNetwork Equipment Network surge Protection OUT jackEPO Switch Set Up Liebert MultiLink softwareBattery cabinet connector color key External Battery Cabinet InstallationConnect battery cabinets to UPS Display and status indicators function, legend Controls and IndicatorsName Status Indicators Description 3 4Control Buttons Status IndicatorsLED Status indicators-color, illumination modeStatus Buck/Boost Mode Normal ModeBattery Mode Battery Recharge OperationRemote Shutdown Via the DB-9 Connector DB-9 ConnectorNetwork Surge Protection Connectors CommunicationVoltage configurations UPS Inverter/Transfer Voltage ConfigurationsSetting Input Voltage Range Output Voltage Battery Mode UPS CommunicationsBattery Maintenance Battery Charging, StorageInternal Battery Replacement Procedure Liebert PSI XR specifications SpecificationsBatteries Battery cabinet specificationsModel Number Liebert PSI XR battery run times + 6 External + 4 External+ 5 External Troubleshooting Page Iti Ne tTi n Er t
Related manuals
Manual 88 pages 63.05 Kb Manual 60 pages 24.1 Kb Manual 88 pages 36.41 Kb Manual 22 pages 3.64 Kb Manual 76 pages 17.32 Kb Manual 184 pages 52.9 Kb

1000, 1500, 2200, 3000 specifications

The Emerson 3000 is a cutting-edge control system designed to enhance the efficiency, reliability, and precision of industrial operations. Employed across various sectors such as oil and gas, pharmaceutical, food and beverage, and power generation, the Emerson 3000 has gained recognition for its robustness and versatility.

One of the main features of the Emerson 3000 is its advanced process control capability. With integrated control algorithms, it can optimize complex processes in real-time, resulting in significant improvements in production rates and reduced operational costs. The system's predictive analytics capabilities enable operators to anticipate equipment failures and maintenance needs, allowing for proactive management and minimizing downtime.

The Emerson 3000 features a modular architecture, providing flexibility for scaling and customization. Operators can easily tailor the system to fit specific application needs, whether it requires additional control loops or integration with other systems. This adaptability is particularly beneficial for facilities planning for future expansions or modifications.

Another technology highlight of the Emerson 3000 is its seamless integration with the latest Internet of Things (IoT) advancements. The system is designed to communicate effectively with a variety of smart devices and sensors, harnessing data to create insightful analytics that drive operational excellence. This connectivity empowers businesses to leverage big data for improved decision-making and increased agility.

Additionally, the Emerson 3000 incorporates state-of-the-art cybersecurity measures to safeguard critical data and operations. With built-in security protocols and regular updates, the system protects against emerging cyber threats, ensuring the integrity of the control network.

User experience is also a focal point of the Emerson 3000. The intuitive graphical user interface presents complex data in a user-friendly format, making it easier for operators to monitor system performance and respond to alerts quickly. This ease of use contributes to enhanced safety and operational efficiency.

In summary, the Emerson 3000 represents a fusion of advanced process control, modular design, IoT connectivity, robust cybersecurity, and user-centric interface, making it an ideal choice for industries seeking to enhance their operational performance while adapting to ever-evolving technological landscapes.