Emerson 2200 Remote Shutdown Via the DB-9 Connector, Network Surge Protection Connectors

Page 23

Communication

6.0COMMUNICATION

6.1DB-9 Connector

The UPS has a DB-9 (9 pin female) connector on the rear to allow UPS status communications with a computer running Liebert MultiLink software in contact closure mode. The connection provides On Battery and Low Battery notification.

When power is interrupted and battery power is low, Liebert MultiLink software can signal the host computer to gracefully shut down the operating system.

Table 4

DB-9 pin assignment

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DB-9 Pin

 

 

 

 

 

 

Assignment Description

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

Low Battery (open collector)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

UPS TxD (not used)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

UPS RxD (not used)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

Remote Shutdown (5-12V); on-battery operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

Common

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

Output Off, (short to Pin 5, non-latching); any mode operation

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

 

Low Battery (open emitter)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

 

 

Utility Fail (open emitter)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

 

 

 

Utility Fail (open collector)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pin Assignment

 

 

Collector to Emitter*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

7

 

8

9

 

 

 

 

 

(+)

Open

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Collector

 

 

 

 

 

 

 

 

 

330 Ohms

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

4

5

 

 

 

(-)

Open

 

 

 

 

 

 

 

Emitter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6.2Remote Shutdown Via the DB-9 Connector

The Liebert PSI XR can be shut down remotely by shorting Pins 5 and 6 or via Pins 4 and 5 of the DB-

9 connector.

6.2.1Any Mode Shutdown Via Pins 5 & 6

When Pin 6 is shorted to Pin 5, the UPS output is shut Off no matter what mode the UPS is operating in. The UPS cannot be started as long as the pins are shorted. When the short is removed, the UPS output can be enabled by pressing the ON/Alarm Silence/Manual Self-Diagnostic Test button.

6.2.2Battery Mode Shutdown Via Pins 4 & 5

While the UPS is operating on battery, a 5-12VDC signal for 2 seconds or longer is required to signal a shutdown. Signals for less than 2 seconds are ignored.

After Pin 4 receives the shutdown signal, a 2-minute shutdown timer begins a countdown. The shut- down timer cannot be stopped: If utility power returns during the 2-minute countdown, the shutdown timer continues until the end of 2 minutes and the UPS turns Off. The UPS will restart 10 seconds after utility power returns.

6.3Network Surge Protection Connectors

Network (in and out) connectors on the rear of the UPS provide transient voltage surge suppression (TVSS) for network devices.

19

Image 23
Contents Liebert PSI XR Page Table of Contents Communication Battery MaintenanceSize of Branch Circuit Overcurrent Protection Important Safety InstructionsPage Status Change Button Glossary of SymbolsClosure Port 15A for 1500VA Nema 5-15R Introduction3000-rear view Rear viewWHAT’S Included Non-condensing InstallationPreparation Relative humidityStep Tower UPS InstallationConvert the Liebert PSI XR for rack installation Rack-Mount UPS Conversion and InstallationConnect Input Power and Load Orient Display for InstallationCharge Batteries and Perform Battery Startup Network surge Protection OUT jack Connect Network Surge protectionConnect Communication Interface Network EquipmentEPO Switch Set Up Liebert MultiLink softwareBattery cabinet connector color key External Battery Cabinet InstallationConnect battery cabinets to UPS 3 4 Controls and IndicatorsDisplay and status indicators function, legend Name Status Indicators DescriptionControl Buttons Status IndicatorsLED Status indicators-color, illumination modeStatus Battery Recharge Operation Normal ModeBuck/Boost Mode Battery ModeCommunication DB-9 ConnectorRemote Shutdown Via the DB-9 Connector Network Surge Protection ConnectorsUPS Communications UPS Inverter/Transfer Voltage ConfigurationsVoltage configurations Setting Input Voltage Range Output Voltage Battery ModeBattery Maintenance Battery Charging, StorageInternal Battery Replacement Procedure Liebert PSI XR specifications SpecificationsBatteries Battery cabinet specificationsModel Number Liebert PSI XR battery run times + 6 External + 4 External+ 5 External Troubleshooting Page Er t Ne tIti Ti n
Related manuals
Manual 88 pages 63.05 Kb Manual 60 pages 24.1 Kb Manual 88 pages 36.41 Kb Manual 22 pages 3.64 Kb Manual 76 pages 17.32 Kb Manual 184 pages 52.9 Kb

1000, 1500, 2200, 3000 specifications

The Emerson 3000 is a cutting-edge control system designed to enhance the efficiency, reliability, and precision of industrial operations. Employed across various sectors such as oil and gas, pharmaceutical, food and beverage, and power generation, the Emerson 3000 has gained recognition for its robustness and versatility.

One of the main features of the Emerson 3000 is its advanced process control capability. With integrated control algorithms, it can optimize complex processes in real-time, resulting in significant improvements in production rates and reduced operational costs. The system's predictive analytics capabilities enable operators to anticipate equipment failures and maintenance needs, allowing for proactive management and minimizing downtime.

The Emerson 3000 features a modular architecture, providing flexibility for scaling and customization. Operators can easily tailor the system to fit specific application needs, whether it requires additional control loops or integration with other systems. This adaptability is particularly beneficial for facilities planning for future expansions or modifications.

Another technology highlight of the Emerson 3000 is its seamless integration with the latest Internet of Things (IoT) advancements. The system is designed to communicate effectively with a variety of smart devices and sensors, harnessing data to create insightful analytics that drive operational excellence. This connectivity empowers businesses to leverage big data for improved decision-making and increased agility.

Additionally, the Emerson 3000 incorporates state-of-the-art cybersecurity measures to safeguard critical data and operations. With built-in security protocols and regular updates, the system protects against emerging cyber threats, ensuring the integrity of the control network.

User experience is also a focal point of the Emerson 3000. The intuitive graphical user interface presents complex data in a user-friendly format, making it easier for operators to monitor system performance and respond to alerts quickly. This ease of use contributes to enhanced safety and operational efficiency.

In summary, the Emerson 3000 represents a fusion of advanced process control, modular design, IoT connectivity, robust cybersecurity, and user-centric interface, making it an ideal choice for industries seeking to enhance their operational performance while adapting to ever-evolving technological landscapes.