Cooper Bussmann EDSC2199 dimensions With General Electric Switches

Page 2

EDS Series Factory Sealed

Cl. I, Div. 1 & 2, Groups B*, C, D

Explosionproof

2C

Manual Motor Starting Switches

Cl. II, Div. 1, Groups E, F, G

Dust-Ignitionproof

 

Cl. II, Div. 2, Groups F, G

Raintight

 

and Enclosures

Cl. III

Wet Locations

 

NEMA 3, 7B*CD, 9EFG

Ordering Information

With Allen-Bradley Bulletin 600 Switches

Maximum HP Ratings

 

 

115–230

115–230

 

Poles

Volts AC

Votts DC

Cat. #

 

 

 

 

1

1 hp

 

A B BUL 600 TOX4

2

1 hp

3/4 hp

A B BUL 600 TOX5

 

Hub

 

 

Poles

Size in.

Dead end Cat. #

Through feed Cat. #

 

 

 

Single Gang

EDS2199

EDSC2199

1

3/4

1

EDS3199

EDSC3199

 

2

3/4

EDS21100

EDSC21100

1

EDS31100

EDSC31100

 

 

 

 

Two Gang

EDS2299

EDSC2299

1

3/4

1

EDS3299

EDSC3299

 

2

3/4

EDS22100

EDSC22100

1

EDS32100

EDSC32100

 

With General Electric Switches

Maximum HP Ratings

 

 

 

 

 

115–230

115

230

 

 

Poles

Volts AC

Votts DC

Votts DC

Cat. #

 

 

 

 

 

1

1 hp

1 hp

1/4 hp

GE CR101 Y

 

2

1 hp

1 hp

1 hp

GE CR101 H

 

Hub Size

 

 

 

 

Poles

in.

Dead end Cat. # Through feed Cat. #

 

 

 

 

 

Single Gang

EDS21093

EDSC21093

1

3/4

1

EDS31093

EDSC31093

 

2

3/4

EDS21094

EDSC21094

1

EDS31094

EDSC31094

 

 

 

 

 

 

Two Gang

EDS22093

EDSC22093

1

3/4

1

EDS32093

EDSC32093

 

2

3/4

EDS22094

EDSC22094

1

EDS32094

EDSC32094

 

2C

Heater Table (Allen-Bradley)

 

 

Heater Table (General Electric)

 

Max. Motor

 

Max. Motor

 

 

Max. Motor

 

Max. Motor

 

Full-Load

Crouse-Hinds

Full-Load

Crouse-Hinds

 

Full-Load

Crouse-Hinds

Full-Load

Crouse-Hinds

Amps

Symbol Number

Amps

Symbol Number

 

Amps

Symbol Number

Amps

Symbol Number

 

 

 

 

 

 

 

 

 

0.17

P1

2.92

P22

.48

G2

3.01

G22

0.21

P2

3.09

P23

.53

G3

3.27

G23

0.25

P3

3.32

P24

.58

G4

3.56

G24

0.32

P4

3.77

P25

.65

G5

3.88

G25

0.39

P5

4.16

P26

.71

G6

4.22

G26

0.46

P6

4.51

P27

.78

G7

4.60

G27

0.57

P7

4.93

P28

.86

G8

5.00

G28

0.71

P8

5.43

P29

.95

G9

5.43

G29

0.79

P9

6.03

P30

1.04

G10

5.90

G30

0.87

P10

6.83

P31

1.14

G11

6.41

G31

0.98

P11

7.72

P32

1.25

G12

6.98

G32

1.08

P12

8.24

P33

1.37

G13

7.60

G33

1.19

P13

8.9

P34

1.49

G14

8.25

G34

1.30

P14

9.6

P35

1.63

G15

8.95

G35

1.43

P15

10.8

P36

1.78

G16

9.75

G36

1.58

P16

12.0

P37

1.95

G17

10.6

G37

1.75

P17

13.5

P38

2.13

G18

11.4

G38

1.88

P18

15.2

P39

2.32

G19

12.5

G39

2.13

P19

 

 

2.53

G20

13.6

G40

2.40

P20

 

 

2.76

G21

14.8

G41

2.58

P21

 

 

 

 

 

16.0

G42

Includes one interchangeable heater. Select heater from the table below individual listings and use symbol number as second section of the Cat. No. Example: EDS2199-P5. Insert symbol 0 (zero) to omit heater.

These heaters are for motors rated 40°C continuously. For motors rated 50°C or 55°C, multiply full load motor current by 0.9 and use this value to select heaters. Symbol 0 (zero) must be used to indicate heater omitted.

*Add GB suffix. Seals must be installed within 11/2" of each conduit opening for Group B usage.

www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2010 Cooper Crouse-Hinds

463

Image 2
Contents Applications FeaturesDimensions Certifications CompliancesHeater Table Allen-Bradley Heater Table General Electric With General Electric SwitchesMax. Motor Full-Load Crouse-Hinds Amps Symbol Number Maximum HP Ratings 120-240 Poles Volts AC Volts DC Cat. # With Cutler-Hammer SwitchesHeater Table Cutler-Hammer