Operating temperature (AC and DC systems)
| 4.5º to 40º C (40º to 104º F) | |
|
|
|
6000 to 8000 ft
8000 to 10,000 ft
4.5º to 35º C (40º to 95º F)
4.5º to 30º C (40º to 86º F)
Short term (<72 hrs) operating temp. (DC systems only)
6000 to 8000 ft
8000 to 10,000 ft
Heat dissipation (maximum)
CEC cab. (AC systems)
Expansion cab. (AC systems) 15,131 Btu/hr
CEC cab. (DC systems)
Expansion cab. (DC systems) 12,283 Btu/hr
Relative humidity
Max. rate of temp. change
Acoustical noise (per cabinet)
Fans at normal speed
Fans at full speed
5.3 Electrical (AC Cabinets)
AC service requirements |
| Two 30A, |
|
|
|
AC input voltage range |
| |
|
| |
Nominal |
| 200 to 240 V AC |
|
|
|
Absolute |
| 180 to 264 V AC |
|
|
|
AC input frequency range |
| 47 to 63 Hz |
|
|
|
Efficiency (min.) |
| 82% |
|
|
|
Power factor |
| >.99 (>10% load) |
|
|
|
AC input power (max.) |
| 4.44 KVA |
|
|
|
Input current (@ 3600 W of power delivered to load)