Table 6-1 Troubleshooting (Continued)

Condition

Possible cause

Checks

Action

 

 

 

 

Engine does not crank

Remote switch faulty

Check switch and

Repair circuits

with Remote Start

Main Logic Board

switch circuits

Replace switch

 

 

 

Cranks when water

faulty

Check Main Logic

Replace Main logic

pressure decreases

 

Board

Board

 

 

 

 

Engine does not start

Power Sense Board or

Check Power Sense

Replace Power Sense

after AC power loss

Main Logic Board

Board

Board

 

faulty

 

 

 

 

Check Main Logic

Replace Main Logic

 

 

Board

 

 

Board

 

 

 

 

 

 

 

Engine does not stop

Another start condition

Check controller start

 

with optional AUTO

present

conditions

 

STOP

Main Logic Board

Check Main Logic

Replace Main Logic

 

 

faulty

Board

Board

 

 

 

 

Note

The above troubleshooting guide does not represent all possible conditions or problems. If the above information can not resolve a problem, consult the factory or a local representative for further assistance.

Image 11
Contents Hubbell Industrial Controls, Inc Model LX3000 Diesel Engine Fire Pump ControllerSet the time InstallationIntroduction Start Up InstructionsProgramming Controller TestingCharger Failure Test Battery Failure TestAutomatic Engine Cranking in Test Automatic Pressure StartOptional Remote Start End of Startup Testing SwitchesHigh Water Temperature Test Optional AC Power Failure Start if enabledHazardous voltage will shock, burn TroubleshootingManual Crank #2 Troubleshooting Condition Possible cause Checks ActionStart Manual Crank #1Manual Start Manual SwitchTroubleshooting AutomaticAuto Condition Possible cause Checks ActionManual Start Stop Page Pen replacement Pressure Switch / Recorder Changing the Chart PaperStart Pressure Pressure SettingsStatus LED’S Stop PressureSpecifications Battery Charger IntroductionSymptom Possible cause Solution Troubleshooting ChartLocation and Description of Control Settings