Hubbell LX3000 instruction manual End of Startup Testing Switches, High Water Temperature Test

Page 5

b.Wait 10 seconds for the Oil Pressure Delay interval to expire, then momentarily jumper TB1-4 to TB1-11. The alarm will sound and the Common Trouble relay will energize. The LOW OIL PRESSURE LED will come on and remain on after the engine stops.

c.Turn the CONTROLLLER ON / OFF - RESET SWITCH to the OFF - RESET position then back to the CONTROLLER ON position to reset the LOW OIL PRESSURE Alarm.

High Water Temperature Test

a.WITH the AUTOMATIC / MANUAL SWITCH in the AUTOMATIC position, start the engine by depressing the TEST PUSHBUTTON on the Weekly Timer.

b.Momentarily jumper the TB1-5 to TB1-11. The alarm will sound and the Common Trouble relay will energized. The HIGH WATER TEMPERATURE LED will come on and remain on after the engine stops.

c.Turn the CONTROLLLER ON / OFF - RESET SWITCH to the OFF - RESET position then back to the CONTROLLER ON position to reset the HIGH WATER TEMPERATURE Alarm.

Optional Remote Start

a.With the AUTOMATIC / MANUAL SWITCH in the AUTO position, open the remote start contacts, TB1-12 & 13, starting the engine.

b.Turn the CONTROLLER ON / OFF SWITCH to the OFF position to stop engine.

c.Close the remote start contacts.

Optional AC Power Failure Start (if enabled)

a.With the AUTOMATIC / MANUAL SWITCH to the AUTO position, disconnect the AC power supply to the Controller.

b.After the pre-set time delay (0 to 90 seconds) the engine will start. The audible alarm should sound, AC POWER LOSS LED will come on, and both the Common TROUBLE and AC POWER LOSS relays will energize.

c.Reconnect the AC power to reset the alarms.

d.Turn the CONTROLLER ON / OFF - RESET SWITCH to the OFF - RESET position to stop the engine.

End of Startup Testing

Switches

1.Automatic/Manual – Selects automatic or manual mode.

2.Crank Battery 1 – Cranks the engine using battery 1.

3.Crank Battery 2 – Cranks the engine using battery 2.

4.Stop – Stops the engine in automatic if there are no start conditions and control switch is in “Auto”.

5.Normal/ Silence – Silences optional pump house alarm only. Standard alarms required NFPA 20 cannot be silenced.

Image 5
Contents Hubbell Industrial Controls, Inc Model LX3000 Diesel Engine Fire Pump ControllerIntroduction InstallationStart Up Instructions Set the timeProgramming Controller TestingAutomatic Engine Cranking in Test Battery Failure TestAutomatic Pressure Start Charger Failure TestHigh Water Temperature Test End of Startup Testing SwitchesOptional AC Power Failure Start if enabled Optional Remote StartHazardous voltage will shock, burn TroubleshootingStart Troubleshooting Condition Possible cause Checks ActionManual Crank #1 Manual Crank #2Troubleshooting Manual SwitchAutomatic Manual StartAuto Condition Possible cause Checks ActionManual Start Stop Page Pen replacement Pressure Switch / Recorder Changing the Chart PaperStatus LED’S Pressure SettingsStop Pressure Start PressureSpecifications Battery Charger IntroductionSymptom Possible cause Solution Troubleshooting ChartLocation and Description of Control Settings