b.Wait 10 seconds for the Oil Pressure Delay interval to expire, then momentarily jumper
c.Turn the CONTROLLLER ON / OFF - RESET SWITCH to the OFF - RESET position then back to the CONTROLLER ON position to reset the LOW OIL PRESSURE Alarm.
High Water Temperature Test
a.WITH the AUTOMATIC / MANUAL SWITCH in the AUTOMATIC position, start the engine by depressing the TEST PUSHBUTTON on the Weekly Timer.
b.Momentarily jumper the
c.Turn the CONTROLLLER ON / OFF - RESET SWITCH to the OFF - RESET position then back to the CONTROLLER ON position to reset the HIGH WATER TEMPERATURE Alarm.
Optional Remote Start
a.With the AUTOMATIC / MANUAL SWITCH in the AUTO position, open the remote start contacts,
b.Turn the CONTROLLER ON / OFF SWITCH to the OFF position to stop engine.
c.Close the remote start contacts.
Optional AC Power Failure Start (if enabled)
a.With the AUTOMATIC / MANUAL SWITCH to the AUTO position, disconnect the AC power supply to the Controller.
b.After the
c.Reconnect the AC power to reset the alarms.
d.Turn the CONTROLLER ON / OFF - RESET SWITCH to the OFF - RESET position to stop the engine.
End of Startup Testing
Switches
1.Automatic/Manual – Selects automatic or manual mode.
2.Crank Battery 1 – Cranks the engine using battery 1.
3.Crank Battery 2 – Cranks the engine using battery 2.
4.Stop – Stops the engine in automatic if there are no start conditions and control switch is in “Auto”.
5.Normal/ Silence – Silences optional pump house alarm only. Standard alarms required NFPA 20 cannot be silenced.