Hubbell Type D6, Type D7 warranty 541,717 6,818,846 6,946,607, Type AR Switch Ratings, Description

Page 2

®

®

U.S. Patents 6,207,919; 6,215,082;

 

14A-2

 

6,281,460; 6,409,135; 6,459,053;

 

POWER SYSTEMS, INC.

 

6,541,717; 6,818,846; 6,946,607.

 

 

Type AR (Automation-Ready) Switch

14.4kV, 25kV or 34.5kV  900 Amperes Continuous/Interrupt

Description

The Hubbell unitized Type AR switch is a distribution-level, loadbreak, gang-operated side-break switch designed to meet not only today’s needs but well into utilities’ future of distribution automation. Designed for nominal system voltages of 14.4kV and 25kV three- and four-wire systems and 34.5kV grounded-wye systems. The Type AR switch is available with a variety of options, and in ratings for present and planned requirements.

To minimize field installation time, the Type AR switch is pre-assembled, adjusted and mounted on a crossarm. Instal- lation time is even faster for a Type AR switch with the hook stick-operation option.

Horizontal Mounting

(Torsional

down-the-pole control shown)

Inverted Mounting

Variations and Configurations

The Type AR switch is available in five basic configura- tions:

•Horizontal •Vertical •Phase-over-Phase •Delta •Inverted

All feature clockwise opening and are operable by torsional or reciprocating controls as well a hookstick operation option (full-length down-the-pole control or crossarm-mounted hook stick-operation control).

1.Full-length down-the-pole controls consist of Torsional swing-handle operation for Horizontal, Delta and Inverted switches and Reciprocating pump-handle operation for Verti- cal and Phase-over-Phase switches. (Standard Duty or Heavy Duty conrols are available for Vertical and Phase-over-Phase switches.) Switch open or close positions locking provisions are provided.

2.Crossarm-mounted hook stick-operation controls provide pull-to-open / pull-to-close switch with maximum target hook stick accessibility.

Features:

All three phase switches feature a four-link overtoggle mecha- nism to assure locked closed blades, mechanical advantage for easier open and close operation, and "snap" feedback to the operator.

(Hook stick control shown)

Vertical Mounting

(Reciprocating down-the-pole control shown)

Phase- over- Phase Mounting

(Reciprocating down-the-pole control shown)

Delta Mounting

(Hook

stick control shown)

Type AR Switch Ratings

Nominal Voltage/Lightning Impulse Withstand

.... 14.4 kV/110 kV, 25 kV/150 kV or 34.5 kV grounded-wye/150 kV

Continuous Current

 900 amperes

Interrupting Current

900 amperes

Peak Withstand Current

65,000 amperes peak

Short Time Withstand Current

3 sec

25,000 amperes, symmetrical

Fault Making: 1 time

25,000 amperes, asymmetrical

3 time

20,000 amperes, asymmetrical

Dead-ending:

8,000-lb. working load

Ice Breaking:

3/4-in. thick, opening and closing

SEPTEMBER 2007

HUBBELL / CHANCE COMPANY – CENTRALIA, MISSOURI

Image 2
Contents Overhead Switches 541,717 6,818,846 6,946,607 Type AR Switch RatingsVariations and Configurations 14.4kV, 25kV or 34.5kV 900 Amperes Continuous/InterruptAvailable Options Single Phase of Type AR Switch 14A-3Horizontal Mounting Vertical Mounting Phase-over-Phase Mounting a Side ViewDelta Mounting Inverted Mounting Patents 6,207,919 Option Tables by ConfigurationReplacement Parts 215,082 6,281,460Convenient Installation Type D7 Switches - UnitizedHorizontal Mounting Phase-over-Phase Riser Pole Mounting 15 to 38 kV AmperesInterrupters Design FeaturesThru 34.5 kV Switch Base and Bearings Terminal Pads, Arcing Horns15 to 38 kV Amperes Riser Pole Mounting 15 to 38 kV 600 Amperes Horizontal Mounting 15 to 38 kV Amperes Phase-over-Phase Mounting 27kV 150kV LIW* Switch Phase Outline 34.5 kV 150kV LIW* Switch Phase OutlineSupport 38 kV 600 Amperes 38 kV 200 LIW* Switch Phase OutlineOptions RatingsBlade Opening Type D6 Switches - Non-UnitizedBases and Bearings Terminal Pads, Arcing HornControls For alternate mounting configurations, see precedingHorizontal Mounting 38 kV - 200 kV LIW 14A-19 Mail hpsliterature@hps.hubbell.com