Wiring Procedure for Nominal 48 VDC Input

To connect the router to a DC power source, perform this procedure:

Step 1

Warning

Tip

Step 2

Step 3

Warning

Warning

Warning

Caution

Caution

Remove power from the DC circuit. To ensure that power is removed from the DC circuit, locate the circuit breaker for the DC circuit, switch the circuit breaker to the OFF position, and tape the circuit-breaker switch in the OFF position.

Before performing any of the following procedures, ensure that power is removed from the DC circuit. Statement 1003

Secure all power cabling when installing this unit to avoid disturbing field-wiring connections.

Strip the wires to the appropriate length for the terminal block on the power supply.

Connect the DC power input wires to the terminal block, as shown in Figure 12.

When stranded wiring is required, use approved wiring terminations, such as closed-loop or spade-type with upturned lugs. These terminations should be the appropriate size for the wires and should clamp both the insulation and conductor. Statement 1002

The illustration shows the DC power supply terminal block. Wire the DC power supply as illustrated. The proper wiring sequence is ground to ground, positive to positive, and negative to negative. The ground wire should always be connected first and disconnected last. Statement 239

An exposed wire lead from a DC-input power source can conduct harmful levels of electricity. Be sure that no exposed portion of the DC-input power source wire extends from the terminal block plug. Statement 122

The terminal arrangement on your router may not be identical to the arrangement shown in the figures. You must connect the positive, negative, and ground wires according to the labels on the terminals.

Do not overtorque the terminal block captive thumbscrew or terminal block contact screws. The recommended torque is 8.0 ± 0.5 inch-lb (0.9 ± 0.05 N-m).

Figure 12 DC Power Connections for Cisco 2600XM Series and Cisco 2612 Routers (Typical)

On/off

Negative

 

Ground

Positive

 

switch

 

 

 

 

72363

 

 

 

Terminal

 

-

+

block

 

 

16

Image 16
Contents Cisco 2600XM Series and Cisco 2612 Routers Cisco 90-Day Limited Hardware Warranty Terms Duration of Hardware WarrantyReplacement, Repair, or Refund Policy for Hardware To Receive a Return Materials Authorization RMA NumberInstall Chassis Documents, Equipment, and ToolsImportant Safety Instructions OBS! Spara Dessa Anvisningar Guarde Estas Instruções GEM Disse Anvisninger Metal object to the terminals. Statement Installing the Chassis Rack-Mounting the ChassisBracket Installation for Front Mounting in 19-Inch Rack Attaching BracketsBracket Installation for Rear Mounting in 19-Inch Rack Installing Chassis in Rack Attaching Rubber FeetGrounding the Chassis Installing on a DesktopAttaching to Wall Connect Cables System Management ConnectionsVoltages. Statement Port Color Connected To CablePower Connections Connecting Routers to AC PowerConnecting the Router to DC Power DC Wiring RequirementsWiring Procedure for Nominal 48 VDC Input Step TipWAN, LAN, and Voice Connections Connecting Routers to the Cisco Redundant Power SystemPort or Connection Port Type, Color Connected To Cable Power Up the Router Checklist for Power-UpFront Panel Indicators Power-Up ProcedurePerform Initial Configuration Initial Configuration Using the Setup Command Facility Enter a host name for the router this example uses Initial Configuration Using the CLI Manual Configuration Configuration appearsInterface Numbering WAN and LAN Interface NumberingTo access documentation on Cisco.com Where to Go NextVoice Interface Numbering To access documentation using Cisco Connection Online CCO Obtaining DocumentationDocumentation Feedback Cisco.comSubmitting a Service Request Definitions of Service Request SeverityObtaining Technical Assistance Cisco Technical Support WebsiteObtaining Additional Publications and Information USA