AC Input/Output Connection
To avoid overloading your Inverter/Charger, match the power requirements of the equipment you plan to run at any one time (add their total watts) with the output wattage capacity of your Inverter/Charger model (see Specifications). Do not confuse “continuous” wattage with “peak” wattage ratings. Most electric motors require extra power at
OverPower™ Feature
Tripp Lite Inverter/Chargers deliver up to 150% of their
*For best results, utilize OverPower for as short a duration as possible, ensure that battery bank and cabling are able to provide full nominal DC voltage under load, and allow the inverter/charger to cool completely before and after OverPower utilization.
DoubleBoost™ Feature
Tripp Lite Inverter/Chargers deliver up to twice their
* Actual duration depends on model, battery age, battery charge level and ambient temperature.
Warning! Consult a qualified electrician and follow all applicable electrical codes and requirements for hardwire connection. Disconnect both DC input and AC utility supply before attempting hardwiring. Use wire type THHN or equivalent with minimum temperature rating of 90°C.
Hardwire Connection
Remove the screws and cover plate over the hardwire terminal box. Remove the knockout covers closest to the desired electrical source and to your equipment. Attach ½" diameter conduits
Ground*
• Connect the incoming and outgoing ground wires to the ground (green) terminal 1 .
AC Input
•Connect the incoming hot wire to the input hot (brown) terminal 2 .
•Connect the incoming neutral wire to the input neutral (blue) terminal 3 .
AC Output
•Connect the outgoing hot wire to the output hot (black) terminal 4 .
•Connect the outgoing neutral wire to the output neutral (white) terminal 5 .
•Replace cover plate and tighten screws.
*If the incoming conduit only contains two wires (hot and neutral), the incoming conduit must be bonded to the main ground lug on the unit. In any case, the incoming conduit must be bonded to earth or vehicle ground, and the incoming conduit must be bonded to the outgoing conduit.
5
OUTPUT/NEUTRAL
4 OUTPUT/HOT
1 GROUND
3 INPUT/NEUTRAL
INPUT/HOT
2
“FOR USE WITH COPPER WIRE ONLY”
Service
Before returning your Inverter/Charger for service, follow these steps: 1.) Review the installation and operation instructions to ensure that the service problem does not originate from a misreading of the instructions. Also, check that the circuit breaker(s) are not tripped.* 2.) If the problem continues, do not contact or return the Inverter/Charger to the dealer. Instead, call Tripp Lite at (773)
*This is a common cause of service inquiries which can be easily remedied by following the resetting instructions in this manual. ** If you require packaging, the technician can arrange to send you proper packaging.
Maintenance
Your Inverter/Charger requires no maintenance and contains no
11