Tripp Lite APS2448UL owner manual Battery, Leds Alarms & Switches, Physical, Environmental

Page 3

Input cord length

Recommended Electrical Service

Maximum input amps / watts

BATTERY

DC INPUT: User supplies cabling. 10 gauge or larger (see manual). AC INPUT: user supplies hardwire input cabling

DC INPUT: Requires 48VDC input source capable of delivering 56A for the required duration (when used at full continuous capacity - DC requirements increase during Over-Power and Double-Boost operation). For automotive applications, professional hardwire i

DC INPUT: Full continuous load - 56A at 48VDC. AC INPUT: 33 amps at 120VAC with full inverter and charger load (13A max charger-only / combined input load to support charger and AC output is automatically controllable to 66%-33%-0% based on AC output load

Expandable battery runtime

DC system voltage

Battery recharge rate

Runtime is expandable with any number of user supplied wet or gel type batteries

48V

15A

LEDS ALARMS & SWITCHES

Front panel LEDs

Switches

PHYSICAL

Set of 6 LEDs offer continuous status information on load percentage (6 levels reported) and battery charge level (7 levels reported). See manual for sequences.

3 position on/off/remote switch enables simple on/off power control plus "auto/remote" setting that enables distant on/off control of the inverter system when used in conjunction with optional APSRM4 accessory when used in inverter mode. In AC uninterruptible power mode, "auto/remote" setting enables automatic transfer from line power to battery power - to maintain continuous AC power to connected loads.

Shipping weight (lbs)

Shipping weight (kg)

Shipping Dimensions (HWD/in)

43

19.5

13.5 x 15 x 21.5

Shipping Dimensions (HWD/cm)

34.3 x 38.1 x 54.6

Unit weight (lbs)

38.6

 

 

Unit weight (kg)

17.5

 

 

Unit Dimensions

7.25 x 8.5 x 16

(HWD/in)

 

 

 

Unit Dimensions

18.4 x 21.6 x 40.6

(HWD/cm)

 

 

 

Material of

Polycarbonate

construction

 

 

 

Form factors

Mounting slots enable permanent placement of inverter on any horizontal surface (see manual for additional mounting

supported

information)

 

 

Cooling method

Multi-speed fan

 

 

Style

Heavy-duty with built-in battery charger

 

 

ENVIRONMENTAL

 

Relative Humidity

0-95% non-condensing

 

 

Operating

32-104 Fahrenheit / 0-40 Celcius

Temperature

 

 

 

LINE / BATTERY TRANSFER

Transfer time from line power to battery mode

Low voltage transfer to battery power

8 milliseconds (typical - compatible with many computers, servers and networking equipment - verify transfer time compatibility of loads for UPS applications)

In AC "auto" mode, inverter/charger switches to battery mode as line voltage drops to 75V (user adjustable to 85, 95, 105V - see manual)

Image 3
Contents Features HighlightsDescription Output SpecificationsOverview System OverviewPhysical BatteryLeds Alarms & Switches Line / Battery TransferSpecial Features WarrantyRelated Items