Tripp Lite SU3000RTXL2U Input, Battery, Voltage Regulation, Leds Alarms & Switches, Physical

Page 3

Output frequency regulation

Outlet quantity / type

Customized load management receptacles

Frequency is regulated to 50/60Hz +/-0.05 Hz. Frequency conversion from 50 to 60Hz and 60 to 50Hz is supported (output watt capacity is reduced by 25% in when frequency conversion is in use).

7 outlets total (6 5-15/20R / 1 L5-30R)

Two individually controllable load banks (each bank consists of 3 5-15/20R outlets)

Overload

L5-30R outlet is non breakered, load banks 1 & 2 (three 5-15/20R outlets each) are protected by separate 20A circuit

protection

breakers

 

 

INPUT

 

Maximum input

24A (120v)

amps

 

 

 

Input connection

L5-30P (120V 30A)

type

 

 

 

Input cord length

10 ft / 3m

 

 

Recommended

100/110/115/120/127V 30A

Electrical Service

 

 

 

BATTERY

 

Full load runtime

6 minutes (2500w)

 

 

Half load runtime

15 minutes (1250w)

 

 

Expandable

Runtime is expandable with optional BP72V15-2U (limit 1) and BP72V28RT3U (multi-pack compatible) external battery

battery runtime

packs

 

 

DC system voltage

72VDC

 

 

Battery recharge

6.8 hours to 90%

rate

 

 

 

Replacement

RBC96-2U

Battery Cartridge

 

 

 

VOLTAGE REGULATION

Voltage regulation description

Overvoltage correction

Brownout correction

In double conversion mode, output is regulated within 2% of selected nominal voltage. In economy mode, output is regulated within -12% / +10% of selected nominal voltage.

Corrects overvoltages to 144V

Corrects undervoltages to 80V (70V at less than 70% load)

LEDS ALARMS & SWITCHES

Front panel LEDs

LED STATUS DISPLAY: line power (green), online (green), bypass (yellow), on battery (green), overload (red), battery low (yellow) - 4 LED LOAD / BATTERY LEVEL DISPLAY (100%, 75%, 50%, 25%). LCD display panel easily rotates for viewing in rackmount or tower configurations.

Alarms

Multi-function audible alarm with distinctive ring patterns offer notification of backup operation (2 seconds on / 0.5 seconds off), low battery warning (1.25 seconds on / 0.5 seconds off), overload (sounds continuously), UPS fault (4.2 seconds on / 1 second off), input voltage out of frequency (2.1 seconds on / 0.14 seconds off) and high input voltage (2.1 seconds on 0.07 seconds off)

Switches

Includes power off/on switch to enable system turn on (press ON switch), UPS battery test (press ON switch during normal AC operation), buzzer silence (press ON switch during battery operation) and OFF (press OFF switch) - all switch functions require that the switch be pressed and held for longer than 2 seconds, but less than 4 seconds

SURGE / NOISE SUPPRESSION

AC surge suppression

AC suppression response time

EMI / RFI AC noise suppression

PHYSICAL

504joules

Instantaneous

Yes

Image 3
Contents Description HighlightsOutput FeaturesSpecifications System OverviewVoltage Regulation BatteryLeds Alarms & Switches InputCommunications Line / Battery TransferSpecial Features EnvironmentalRelated Items WarrantyTripp Lite. All Rights Reserved