Tripp Lite SU1000RTXL2UA warranty Features, Specifications, System Overview, Output

Page 2

PowerAlert Software and cabling

Mounting hardware for 4 post rack enclosures

Instruction manual with warranty information

Features

SmartOnline high performance UPS system is ideal for critical voice, data, medical and industrial network applications

True on-line, double-conversion UPS provides perfectly regulated sine wave output within 2% of 100/110/120V (user selectable) under all usage conditions

Maintains continuous operation through blackouts, voltage fluctuations and surges with zero transfer time

Highly efficient operation in optional economy mode setting, saving BTU heat output and energy costs.

Removes harmonic distortion, fast electrical impulses, frequency variations and other hard to solve power problems not addressed by other UPS types

Corrects line voltage conditions as low as 65V and as high as 138V back to selectable 100/110/120V (+/-2%) values

Standard internal battery set offers 14 minutes runtime at half load (400W) and 4.5 minutes at full load (800W)

Extended runtime available with optional BP24V15RT2U, BP24V28-2U (limit of one per UPS) or BP24V70-3U (multi-pack compatible) external battery packs

Compact rackmount form factor installs using only 2 rack spaces (2U) with a maximum installed depth of only 13.5 inches

Ships with all mounting accessories for 4 post rackmount installation

Optional 2POSTRMKITWM enables 2 post rackmount or wallmount installation

Optional 2-9USTAND accessory enables small-footprint upright tower placement

Fault tolerant auto-bypass maintains continuous utility output to connected equipment, even in cases where the UPS suffers internal failure and requires maintenance

Network interfaces support simultaneous communications via built-in USB, DB9 serial and SNMPWEBCARD slot

HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X. Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, plus any number of additional servers over IP

UPS interface supports on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge current, battery capacity, AC line frequency, timed inverter shutoff, activate self-test, load bank output power control and remote reboot, UPS nominal voltage adjustment and UPS line to battery power voltage set points

Built-in Emergency Power Off (EPO) interface with cable

NEMA 5-15P input plug/NEMA 5-15R output receptacles

Integrated 2 bank switched PDU enables remote outlet management for load shedding or remote reboot of individual devices (each load bank consists of one outlet)

Front panel LEDs offer current monitoring and battery charge level information

UPS ships fully assembled in full compliance with DOT regulations, no time consuming connection of internal batteries by user required

Supports 2 post rackmount installation with optional 2POSTRMKITWM accessory

Single line TEL/DSL or network Ethernet line surge suppression

2 year manufacturer's product warranty, $250,000 Ultimate Lifetime Insurance

Specifications

SYSTEM OVERVIEW

Voltage

120V AC (100/110/120V)

compatibility

 

 

 

Frequency

50/60 Hz compatible (auto-sensing)

compatibility

 

 

 

OUTPUT

 

Output VA

1000

 

 

Output watts

800

 

 

Output nominal

120V AC (100/110/120V)

voltage

 

 

 

Output voltage

Maintains full-time sine wave output within 2% of selected nominal, less than 3% total harmonic distortion (linear load) /

regulation

6% total harmonic distortion (computer load)

 

 

Output frequency

Regulates line frequency to 50/60Hz +/- 0.05Hz

regulation

 

 

 

Image 2
Contents Highlights DescriptionSystem Overview FeaturesSpecifications OutputInput BatteryLeds Alarms & Switches Voltage RegulationPhysical Line / Battery TransferSpecial Features EnvironmentalCertifications WarrantyRelated Items Tower Stands Surge ProtectorsDTEL2 DNET1 9USTAND