Tripp Lite 1111 West 35th Street Chicago, IL 60609 USA Telephone: +(773) 869 1234 E-mail: saleshelp@tripplite.com
Model #: SU10000RT3U
SmartOnline Expandable Rack/Tower UPS System - Online, double-conversion protection for mission critical applications
Highlights
10,000VA/10kVA on-line 6U rack/tower UPS with expandable runtime (3U
Power Module + 3U Battery Pack)
Zero transfer time, on-line, double-conversion and economy-mode operation supported
Manual bypass switch and detachable PDU enable hot-swap UPS replacement without powering off connected loads
200, 208, 230 or 240V selectable input/output voltage
2% output voltage regulation over an input voltage range of 156-276V
Enhanced serial communications ports, SNMP/Web Card Slot and EPO interfaces
$250,000 Ultimate Lifetime Insurance (USA, Puerto Rico & Canada only)
Description
10,000VA (10kVA) on-line, double-conversion UPS system for critical server, network and telecommunications equipment. Installs in only 6 rack spaces (3U power module and 3U battery pack); maximum installed rack depth of 32.5 in. Expandable battery runtime with optional external battery packs. Full-time sine wave 200, 208, 220, 230, or 240V +/-2% output. Actively converts raw incoming AC power to DC, then re-converts output back to completely regulated, filtered AC output. Operates continuously without consuming battery power during brownouts to 156V and overvoltages to 276V. Highly efficient operation in optional economy mode setting, saving BTU heat output and energy costs. Standard 3-wire 208V hardwire input connection; NEMA L6-30R and L6-20R output receptacles. Detachable input-output PDU module with manual bypass switch enables hot-swap UPS replacement without disrupting power to connected equipment. Network-grade AC surge and noise suppression. Zero transfer time between AC and battery operation. Network management interfaces support communications via RS-232, contact-closure port and optional SNMPWEBCARD slot. Supports detailed monitoring of equipment load levels, self-test data and utility power conditions via network interfaces. Includes PowerAlert monitoring software and complete cabling. Emergency Power Off (EPO) interface. Front panel LEDs provide at-a-glance confirmation of line power status, battery power status, AC-to-DC conversion, DC-to-AC conversion, bypass mode and output power status. LED/LCD display panel rotates for better viewing in rackmount or tower configurations. Detailed LCD panel with scroll buttons provides detailed diagnostic test information at startup and during self tests, plus real-time data on input and output voltage, frequency (Hz), load percentage and battery charge level. Audible alarm. Self-test. Fault-tolerant auto-bypass mode. 4-post rackmount accessories and 2-9USTAND tower kit included; 2POSTRMKITWM 2-post rackmount hardware accessories available. Field-replaceable, hot-swappable power module and external battery packs. Attractive all-black color scheme.
2-year warranty; extended warranty and service contracts available. $250,000connected equipment insurance
Applications
Ideal for protection of sensitive electronics in any application calling for upright tower or 19-in. rackmount UPS protection. Common applications include any mix of servers, workstations, hubs, routers, concentrators, IP telephony and traditional PBX switching systems
Package Includes
3U power module with detachable hot-swap PDU input/output panel and bypass switch 3U external battery pack