Tripp Lite SU8000RT3UN50 warranty Features, Specifications, System Overview, Output, Input

Page 2

Two sets of 4 post rackmount rails (one for each of the 3U components)

One set of tower stands for upright tower configuration

PowerAlert software, complete data cabling, user manual with warranty information

Features

8,000 VA (8kVA) on-line, double-conversion UPS system (High voltage input/High voltage output)

Detachable input-output PDU module with manual bypass switch enables hot-swap UPS replacement without powering off connected equipment

Installs in only 6 rack spaces (3U power module/3U battery pack) with a maximum installed depth of 32.5 inches

Offers 6 min. runtime at full load (8000VA/6400W) and 15 min. at half load (4000VA/3200W). Runtime is expandable with any number of optional external battery packs

Full-time sine wave 200, 208, 220, 230, or 240V +/-2% output (user selectable)

Actively converts raw incoming AC power to DC, then re-converts output back to completely regulated, filtered AC output

Operates continuously without using battery power during brownouts to 156V and overvoltages to 276V

Includes Hubbell twist-lock 50A input plug for simple installation; input cordset is removeable to support professional hardwire installation

2 x NEMA L6-30R and 4 x L6-20R output receptacles

Detailed LCD panel with scroll buttons offers detailed diagnostic test information on startup and during self tests, plus real-time data on input and output voltage, frequency (Hz), load percentage, battery charge level and more

Network-grade AC surge and noise suppression

Zero transfer time between AC and battery operation

Network management interfaces support communications via RS-232, contact-closure port and optional SNMPWEBCARD slot Supports detailed monitoring of equipment load levels, self-test data and mains power conditions via network interfaces. Includes PowerAlert monitoring software and complete cabling

Emergency Power Off (EPO) interface

Front panel LEDs offer at-a-glance confirmation of line power status, battery power status, AC-to-DC & DC-to-AC conversion, bypass mode and output power status.

Fault-tolerant auto-bypass mode prevents loss of output during UPS fault conditions or excessive UPS loading

4-post rackmount and upright tower installation accessories included. 2POSTRMKITWM two post rackmount hardware accessories available

Field replaceable, hot swappable power module and external battery packs

Attractive all-black color scheme

2-year warranty; $250,000 connected equipment insurance

Extended warranty and service contracts available

Specifications

SYSTEM OVERVIEW

Voltage compatibility

208V AC (200/208/220/230/240V)

 

 

Frequency

50/60 Hz

compatibility

 

 

 

OUTPUT

 

Output VA

8000

 

 

Output watts

6400

 

 

Output nominal

208V AC (200/208/220/230/240V)

voltage

 

 

 

Output voltage

Maintains pure sine wave output at all times, regulated within 2% of selected nominal output voltage, less than 3% total

regulation

harmonic distortion when used with computer loads

 

 

Output frequency

Regulates line frequency to 50/60Hz +/- 0.05Hz

regulation

 

 

 

Outlet quantity / type

4 x NEMA L6-20R, 2 x NEMA L6-30R

 

 

INPUT

 

Maximum input amps

200V - 38A / 208V - 36A / 220V - 34A / 230V - 33A / 240V - 32A

 

 

Input connection type

Hubbell CS8265C 50A input plug (input cordset is removeable to support professional hardwire input)

Input cord length

10 ft. / 3.05 meters

Image 2
Contents Highlights DescriptionSystem Overview FeaturesSpecifications OutputSurge / Noise Suppression BatteryLeds Alarms & Switches PhysicalRelated Items Rackmount/Wallmount Kits Snmp AccessoriesStart-Up/Warranty Services Shutdown Cable Kits