Tripp Lite SU6000RT3UHV Voltage Regulation, Leds Alarms & Switches, Surge / Noise Suppression

Page 3

Battery recharge rate

Less than 8 hours to 90% (included battery set only)

VOLTAGE REGULATION

Voltage regulation description

Overvoltage correction

Brownout correction

On-line, double-conversion process give this UPS the ability to maintain output voltage within +/-2% of selected nominal voltage at all times

Maintains continuous operation without using battery power during overvoltages to 276VAC, regulating output within 2% of selected nominal

Maintains continuous operation without using battery power during brownout / undervoltage conditions to 156VAC, regulating output within 2% of selected nominal

LEDS ALARMS & SWITCHES

Front panel LEDs

6 LED DISPLAY: line power, bypass, inverter, charger, output AC and battery operation. SELECTABLE LCD DISPLAY: input/output voltage, Hz, battery voltage and charge level and detailed warnings regarding all major UPS functions. LED/LCD display panel easily rotates for viewing in rackmount or tower configurations.

Alarms

Switches

Multi-function audible alarm offers notification of UPS start, backup operation, low battery, overload, UPS fault, inverter fault, DC bus fault, overtemperature, remote shutdown, shutdown imminent and shutdown complete

Includes main power off/on switch, plus 2 switches to set and execute scrollable LCD functions

SURGE / NOISE SUPPRESSION

AC suppression

Instantaneous

response time

 

 

 

EMI / RFI AC noise

Yes

suppression

 

 

 

PHYSICAL

 

Shipping weight

323

(lbs)

 

 

 

Shipping weight

145.4

(kg)

 

 

 

Unit weight (lbs)

Power Module 43.8 lbs., Battery Pack: 139 lbs.

 

 

Unit weight (kg)

Power Module: 19.7 kg, Battery Pack: 61kg

 

 

Unit Dimensions

Power Module 5.25 x 17.5 x 26, Battery Pack 5.25 x 17.5 x 25

(HWD/in)

 

 

 

Unit Dimensions

Power Module 13.3 x 44.5 x 66, Battery Pack 13.3 x 44.5 x 63.5

(HWD/cm)

 

 

 

Material of

Steel

construction

 

 

 

Form factors

Rack (6U)

supported

 

 

 

Cooling method

Built-in cooling fan

 

 

Battery Access

User replaceable, hot swappable external battery pack

 

 

ENVIRONMENTAL

 

Relative Humidity

0 to 95%, non-condensing

 

 

Storage

+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius

Temperature

 

 

 

Operating

+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius

Temperature

 

 

 

Line mode BTU/hr.

1418

(Max.)

 

 

 

COMMUNICATIONS

 

Network

Includes 2 built-in DB9 monitoring ports (1-RS232 / 1-contact closure)

monitoring port

 

 

 

Software and

Includes PowerAlert UPS monitoring software for all common network and standalone operating systems. Cabling

cabling included

included.

 

 

SNMP compatibility

Built-in accessory slot accommodates internal SNMP / Web card and other network accessories

Image 3
Contents Features HighlightsDescription Output SpecificationsBattery System OverviewPhysical Leds Alarms & SwitchesVoltage Regulation Surge / Noise SuppressionRelated Items Line / Battery TransferSpecial Features WarrantyEnvirosense Snmpwebcard Snmp AccessoriesStart-Up/Warranty Services AS400CABLE KIT