Tripp Lite SU5000RT4UTF manual Specifications, Output

Page 2

Tripp Lite SU5000RT4UTF 5000VA / 5kVA / 4500 watt on-line, double-conversion UPS system in a 6U rack/tower configuration (4U UPS power module with internal batteries + 2U step-down transformer)

Full-time active power conditioning maintains clean, continuous dual-conversion AC output free of voltage fluctuations, power interruptions and line noise

Fault tolerant electronic bypass maintains utility output during a variety of UPS fault conditions

L6-30P input plug, plus 2 L6-30R, 2 L6-20R and 12 5-15/20R outlets

Included rail kits support rackmount installation of both included modules in 4 post racks

Optional 2POSTRMKITHD supports installation in 2 post 19 inch racks (2 required for SU5000RT4UTF)

Optional 2-9USTAND supports upright tower placement (1 required for SU5000RT4UTF)

Maximum installed rack depth of only 20.75 in. / 52.7 cm

Maintains full-time sine wave output within 2% of 208V & 120V at 60Hz nominal in double conversion mode

Corrects brownouts to 156V at full load (100V at 50% load or less)

Corrects overvoltages to 290V at full load (300V at 90% load or less)

Double-conversion operation offers full-time AC to DC, then DC to AC conversion to maintain perfectly regulated sine wave AC output with enhanced protection from harmonic distortion, fast electrical impulses and other hard-to-solve power problems not addressed by other UPS types

High efficiency ECONOMY MODE operation significantly reduces BTU heat output and operating energy costs

Network-grade AC surge and noise suppression

Supports detailed monitoring of equipment load levels, self-test data and utility power conditions via built-in RS-232, USB and optional SNMP card slot interfaces

UPS card slot supports one card-based network interface option (part # SNMPWEBCARD) or dry-contact monitoring accessory (part #

RELAYIOCARD)

Optional SNMPWEBCARD offers communications and control via secure remote web and network interfaces

Optional RELAYIOCARD supports six configurable hard contact closure outputs for custom event notification

Optional RELAYIOMINI interface module offers three configurable hard contact closure outputs for custom event notification (requires removal of USB interface module)

HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X Includes Free PowerAlert monitoring software packages; PowerAlert LOCAL for desktops and small business networks, PowerAlert NSA (Network Shutdown Agent) for larger networks and PowerAlert NMS (Network Management System) for monitoring up to 250 SNMP-enabled UPS, PDU and other networking devices

Front panel LEDs and LCD readout with scroll controls support front-panel visual monitoring of all major UPS functions with support for a variety of control options to support advanced UPS settings and configurations

LED/LCD display panel rotates for viewing in rackmount or tower configurations

Supports Emergency Power Off (EPO) via built-in interface

Battery independent restart ensures automatic UPS power-up without user interaction after lengthy power outages, even when batteries are expired and require replacement

External battery packs are field replaceable and hot swappable

Some external battery configurations require the use of Tripp Lite's External Battery Configuration Software (see manual) $250,000 connected equipment insurance;

Specifications

OUTPUT

Output Volt Amp Capacity (VA)

Output kVA capacity (kVA)

Output Watt Capacity (watts)

Output kW capacity

Output power factor

Crest Factor

Nominal Output Voltage(s) Supported

5000

5.0

4500

4.5

0.9

3:1

120V; 208V

Image 2