Tripp Lite SU5000RT3UHV warranty Specifications, System Overview, Output, Input, Battery

Page 2

Accepts input voltages between 156 and 276, regulating output within 2% of selected 200/208/220/230/240V nominal voltage Supports connected equipment during blackouts for 20/8 minutes at half/full load levels. Runtime is further expandable with optional external battery packs

Network interfaces support simultaneous communications via 2 DB9 ports and SNMPWEBCARD slot

Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, plus any number of additional servers over IP

Communications ports support on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge current, battery capacity, AC line frequency, timed inverter shutoff, activate self-test and output power control

Built-in Emergency Power Off (EPO) interface with cable

Includes 4 built-in output receptacles (2 L6-30R, 2 L6-20R)

L6-30P input plug-in connection

Front panel LEDs and LCD readout with scroll button enables visual confirmation of all major UPS functions and current site electrical conditions

Front panel switches enable power on/off control, self-test and alarm cancel functions

Included adjustable mounting rails support installation in 4 post 19 inch rack enclosures. Optional 2POSTRMKITWM supports 2 post rackmount installation

UPS ships fully assembled in full compliance with DOT regulations, no time consuming connection of internal batteries by user is required Fault-tolerant auto-bypass maintains continuous utility output to connected equipment, even in cases where the UPS is overloaded or suffers an internal failure that requires service

2 year manufacturer's product warranty, $250,000 Ultimate Lifetime Insurance (USA & Canada only)

Specifications

SYSTEM OVERVIEW

Voltage compatibility

208V AC (200/208/220/230/240V)

 

 

Frequency

50/60Hz

compatibility

 

 

 

OUTPUT

 

Output VA

5000

 

 

Output watts

3500

 

 

Output nominal

208V AC (200/208/220/230/240V)

voltage

 

 

 

Output voltage

Maintains pure sine wave output at all times, regulated within 2% of selected nominal output voltage, less than 5% total

regulation

harmonic distortion

 

 

Output frequency

Regulates line frequency to 50/60Hz +/- 0.05Hz

regulation

 

 

 

Outlet quantity / type

2 NEMA L6-30R, 2 NEMA L6-20R

 

 

Overload protection

Resettable circuit breaker

 

 

INPUT

 

Maximum input amps

24A 208V / 21A 240V

 

 

Input connection type

NEMA L6-30P

 

 

Input cord length

10 ft / 3 m

 

 

Recommended

30A at 200, 208, 220, 230, 240V

Electrical Service

 

 

 

BATTERY

 

Full load runtime

8 minutes (5000VA / 3500 watts)

 

 

Half load runtime

20 minutes (2500VA / 1750 watts)

 

 

Expandable battery

Yes, with optional external battery packs

runtime

 

 

 

DC system voltage

240V DC

 

 

Typical battery

4-6 years

lifespan

 

 

 

Image 2