Unit Dimensions | 10.25 x 9 x 20.5 |
(HWD/in) |
|
|
|
Unit Dimensions | 26 x 22.9 x 52.1 |
(HWD/cm) |
|
|
|
Material of | Steel |
construction |
|
|
|
Form factors | Tower |
supported |
|
|
|
Cooling method | |
|
|
Battery Access | User replaceable, |
|
|
ENVIRONMENTAL |
|
Relative Humidity | 0 to 95%, |
|
|
Storage | +5 to +122 degrees Fahrenheit / |
Temperature |
|
|
|
Operating | +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius |
Temperature |
|
|
|
Line mode BTU/hr. | 1113 BTU/hr. |
(Max.) |
|
|
|
Battery mode | 1219 BTU/hr. |
BTU/hr. (Max.) |
|
|
|
Audible Noise |
|
|
|
COMMUNICATIONS |
|
Network | Includes USB and DB9 serial ports. |
monitoring port | closure monitoring ability. |
| shutdown features of Windows and Mac OS X. |
|
|
Software and | Yes, includes PowerAlert software |
cabling included |
|
|
|
SNMP compatibility | Yes, includes slot for optional SNMPWEBCARD accessory (#SNMPWEBCARD) |
|
|
WatchDog | Yes, compatible with Tripp Lite's Watchdog system service to restore operation to locked equipment through soft reboot |
compatibility | of application / OS or hard power off/on reboot of connected equipmentideal for unattended kiosk applications |
|
|
LINE / BATTERY TRANSFER
Transfer time from line power to battery mode
Low voltage transfer to battery power
Zero, online UPS continuously converts incoming AC to DC, then back to AC. When commercial power is interrupted, UPS maintains continuous output from battery reserves with absolutely no disruption in output AC power.
Maintains continuous operation during undervoltages as low as 65V (80V at load levels over 70%). Below this switchover point, output is supported from battery derived AC power.
High voltage | Maintains continuous operation without using battery power during overvoltages to 138V. Above this point, output is |
transfer to battery | supported from battery derived AC power. |
power |
|
|
|
SPECIAL FEATURES |
|
EPO port | Supports "Emergency Power Off" via set of dedicated |
|
|
Cold Start
Yes, inverter can be "cold started" to enable temporary AC output during a power failure
Appearance
Attractive black steel rackmount housing
BATTERY PACK ACCESSORY (optional)
Battery Pack | |
Accessory |
|
(optional) |
|
|
|
CERTIFICATIONS |
|
Certifications | Tested to UL1778 (USA), CSA (Canada), NOM (Mexico), Class A (emissions), FCC Part 68 / Industry Canada |
| (telecommunications), RoHS compliant |
|
|
WARRANTY |
|