8. “BATTERY HI/MED/LO” (All models)

These three lights will turn ON in several sequences to show the approximate charge level and voltage of your connected battery bank and alert you to several fault conditions:

BATTERY CHARGE INDICATION (Approximate)

Indicator

Capacity

Green

91%

- Full

Green & yellow

81%

- 90%

Yellow

61%

- 80%

Yellow & red

41%

- 60%

Red

21%

- 40%

All three lights off

1% - 20%

Flashing red

0% (Inverter shutdown)

All three lights flash slowly*

Excessive discharge

All three lights flash quickly**

Overcharge

*Approximately 1/2 second on, 1/2 second off. See Troubleshooting section.

**Approximately 1/4 second on, 1/4 second off. May also indicate a battery charger fault exists. See Troubleshooting section.

Other Features

9. DC Input Terminals (All models)

The terminals’ lug screws secure the wires leading from your external battery or battery system. Your battery or battery system must provide your APS with proper DC voltage and your equipment with an adequate amp hour capacity. See Battery Selection section, pg. 7 for more information.

10. AC Receptacles: NEMA 5-15R (Corded models only)

These receptacles allow you to connect equipment that would normally be plugged into a utility outlet. They feature ground fault indicator switches that trip when the receptacles are in danger of short circuiting. If the switches trip, press to reset them when the short circuit situation is remedied.

11. AC Input Line Cord: NEMA 5-15P fixed (Corded models only)

This cord should be plugged into a 120V, 60 Hz, dedicated 15 Amp AC utility outlet. DO NOT plug the cord into the APS’s AC receptacles.

12. Hardwire AC Input/Output Terminal Strip (Hardwire models only)

Use the lug screws on these terminals to secure hardwire connections for AC input and output. See pages 9 & 32 for wiring instructions.

13. Resettable Circuit Breakers (All models)

These circuit breakers protect your APS against damage due to input or output overload. If a breaker trips, remove some of the load on the APS to prevent overload, then wait 1 minute to allow components to cool before resetting the circuit breaker.

14. Remote Module Connector (All models)

The front panel of all models has an RJ 45 receptacle for use with the optional remote module. (Module is included with all VR models.) See the installation instructions packed with the remote module.

15. Load Sense Potentiometer (All models)

In order to save battery power, the APS’s inverter automatically shuts off when no load is connected. When the unit detects a load, it automatically turns the inverter on. Users may choose the minimum load the APS will detect by adjusting the Load Sense Potentiometer. Using a small tool, turn the potentiometer clockwise to lower the minimum load that will be detected, causing the inverter to turn on for smaller loads. When the potentiometer is turned fully clockwise, the inverter will operate even when there is no load. Turn the potentiometer counterclockwise to increase the minimum load that will be detected, causing the inverter to stay off until the new minimum load is reached. The factory setting for the potentiometer is fully clockwise, but in areas with frequent power interruptions, the potentiometer should be adjusted counterclockwise until the inverter is only in operation when the APS’s load is in use.

11

Image 11
Contents Configuration & Connection p APS PowerVerterIntroduction Frequency-Controlled Inverter Output Advanced, 3-Stage Battery ChargerVoltage Regulation Select models only Load Sharing Select models onlyEquipment Connection Warnings SafetyBattery Connection Warnings APS Location WarningsConfiguration Load Sharing Equalize Battery ChargeDisable Battery Charger APS 2448 only Selecting Battery Amp Hour Capacity Battery SelectionLimit Battery Charger APS 1012 and APS 2012 only Selecting Battery TypeMounting Optional Battery Connection StandardBattery Connection DC Vehicular See Diagram 2, pAC Input Electrical Connection Hardwired Electrical ConnectionsSet Operating Mode Switch AC ConnectionIndicator Lights Switches, Indicator Lights Other FeaturesSwitches Other Features Service Maintenance & ServiceLimited Warranty MaintenanceSymptom Problems Corrections TroubleshootingInverter Specifications Corded ModelsSpecifications Hardwired Models Diagrams/Esquemas APS 12V Battery HI/MED/LO Th Street Chicago, IL 60609 USA Customer Support 773