Tripp Lite 1111 West 35th Street Chicago, IL 60609 USA Telephone: +(773) 869 1234 E-mail: saleshelp@tripplite.com
Model Number: PDUBHV10
Single-Phase Hot-Swap PDU, 2-2.4kW 10A 200-240V, 2U Horizontal Rackmount, 8 C13 outlets, set of 2 C14 inputs
Highlights
Single phase 10A 200-240V Hot-swap PDU
Enables live replacement of a standard UPS with zero downtime
2U horizontal rackmount installation
Compatible with any 200-240V UPS with a C14 input
Manual transfer switch controls PDU input power source
Pair of C14 compatible inputs connect to separate Utility and UPS inputs
8 Built-in C13 outlets
Description
Tripp Lite’s Hot-swap PDU systems enable live-replacement of standard UPS systems for maintenance with no interruption of connected server or networking loads. Dual input power cables support PDU connection to separate Utility and UPS power sources. Manual transfer switch with lighted status indicators controls the source of power to connected equipment between Utility and UPS. Set the switch to UPS during normal operation and connected equipment will receive full-time conditioned power from the UPS. Set the switch to Utility to momentarily power connected equipment from the Utility line cord and bypass the UPS while the UPS system is removed and replaced with a fresh one. Once the new UPS is up and running with all data and electrical connections restored, set the switch back to the UPS setting to once again provide fully-conditioned UPS power to connected equipment.
Applications
Hot-swap PDUs are ideal to install along with standard UPS systems to ensure that connected networking equipment will see no power interruption
as the UPS is serviced, replaced or upgraded
Package Includes
Hot-swap PDU System
2U mounting brackets
Set of 2 C13-C14 interconnect cables
User manual with warranty information
Features
Tripp Lite Hot-swap PDU systems support live-replacement of standard UPS systems for maintenance with no interruption of connected server or networking loads
PDUBHV10 is universally compatible with any Tripp Lite or other brand of 200-240V UPS rated up to 1500VA with a C14 input cable option
2U horizontal rackmount form factor compatible with 2 or 4 post racks
Supports space saving rear-post mounting in the same rack space as many Tripp Lite Rackmount UPS systems (select installations, see manual)
Pair of detachable PDU input cables connect to separate Utility and UPS power sources (2 C13-C14 interconnect cables included - user supplied alternate cabling supported)
8 C13 outlets support critical networking loads in both Utility and UPS operating modes
One additional C13 pass-through outlet supports UPS input power cord
Dual input power cables support PDU connection to separate Utility and UPS power sources
Manual transfer switch with lighted status indicators controls the source of power to connected equipment between Utility and UPS