Set the switch to UPS during normal operation and connected equipment will receive full-time conditioned power from the UPS

Set the switch to Utility to bypass the UPS and provide connected equipment with unfiltered power directly from the Utility line cord while the UPS system is removed and replaced with a fresh one

Once the new UPS is up and running with all connections restored, set the switch back to the UPS setting to once again provide fully-conditioned UPS power to connected equipment

Specifications

OVERVIEW

PDU Type

Hot-Swap

OUTPUT

Output Watt Capacity (watts)

Output Capacity Details

Frequency compatibility

Output nominal voltage

Outlet quantity / type

Outlet Type

INPUT

2300

2.1kW (208V input), 2.2kW (220V input), 2.3kW (230V input), 2.4kW (240V input), 2.0kW (200V input); 10A maximum

50 / 60 Hz

200-240V nominal, single phase

8 C13 outlets support critical connected loads; 1 designated pass-through C13 outlet supports C14 input plug from UPS

IEC-C13

PDU Input Voltage

Maximum Input Amps

(A)

Input connection type

PDU Plug Type

Input cord length (ft.)

Input cord length (m)

Phase

200; 208; 220; 230; 240

10

UTILITY & UPS inputs are available from separately labelled C14 inlets, compatible with included C13-C14 interconnect cables or with compatible user-supplied cabling

IEC-320 C14

6

1.83

Single-Phase

LEDS ALARMS & SWITCHES

Switches

Front panel LEDs

PHYSICAL

Manual 2 position transfer switch offers fast switching between UPS and Utility operating modes in less than 6 milliseconds

Lighted indicators confirm UPS and Utility switch position and operating mode

Shipping Dimensions (HWD/in)

Shipping Dimensions (HWD/cm)

Shipping weight (lbs)

Shipping weight (kg)

Unit Dimensions (HWD/in)

9.84x 22.75 x 9.44

25 x 57.8 x 24

11

5

3.42 x 17.32 x 3.03