Tripp Lite 2POSTRMKITWM owner manual Basic Operation, Buttons Front Panel

Page 7

Basic Operation

Buttons (Front Panel)

“ON/OFF/STANDBY” Button

To turn the UPS ON: with the UPS plugged into a live AC wall outlet*, press and hold the “ON/OFF/STANDBY” button for one second.** Release the but- ton. If utility power is absent, you can “cold-start” the UPS (i.e.: turn it ON and supply power for a limited time from its batteries***) by pressing and holding the “ON/OFF/STANDBY” button for one second.**

To turn the UPS OFF: with the UPS ON and receiving utility power, press and hold the “ON/OFF/STANDBY” button for one second.** Then unplug the UPS from the wall outlet. The UPS will be completely OFF.

*After you plug the UPS into a live AC outlet, the UPS (in ”Standby” mode) will automatically charge its batteries, but will not supply power to its outlets until it is turned ON. ** The alarm will beep once briefly after the indicated interval has passed. *** If fully charged.

“MUTE/TEST” Button

To Silence (or “Mute”) UPS Alarms: briefly press and release the MUTE/TEST button.*

To Run a Self-Test: with your UPS plugged in and turned ON, press and hold the MUTE/TEST button for two seconds.* Continue holding the button until the alarm beeps several times and the UPS performs a self test. See “Results of a Self-Test” below. Note: you can leave connected equipment on during a self-test. Your UPS, however, will not perform a self-test if the UPS is not turned on (see “ON/OFF/STANDBY” Button description).

CAUTION! Do not unplug your UPS to test its batteries. This will remove safe electrical grounding and may introduce a damaging surge into your system connections.

Results of a Self-Test: The test will last approximately 10 seconds as the UPS switches to battery to test its load capacity and battery charge.

If the “OUTPUT LOAD LEVEL” LED remains lit red and the alarm contin- ues to sound after the test, the UPS’s outlets are overloaded. To clear the over- load, unplug some of your equipment and run the self-test repeatedly until the “OUTPUT LOAD LEVEL” LED is no longer lit red and the alarm is no longer sounding.

CAUTION! Any overload that is not corrected by the user immediately following a self-test may cause the UPS to shut down and cease supplying output power in the event of a blackout or brownout.

If the “BATTERY WARNING” LED remains lit and the alarm continues to sound after the test, the UPS batteries need to be recharged or replaced. Allow the UPS to recharge continuously for 12 hours, and repeat the self-test. If the LED remains lit, contact Tripp Lite for service. If your UPS requires battery replacement, visit www.tripplite.com to locate the specific Tripp Lite replacement battery for your UPS.

* The alarm will beep once briefly after the indicated interval has passed.

7

Image 7
Contents Audio/Video Automatic Voltage Regulation AVR UPS Systems UPS Connection Warnings Important Safety InstructionsBattery Warnings UPS Location WarningsPost Mounting Rack Mounting2U UPS Models Only Tower MountingPost Mounting All UPS ModelsPlug your equipment into the UPS Plug the UPS into an outlet on a dedicated circuitTurn the UPS on USB and RS-232 Serial Communications all models External Battery Connection Select models onlyEPO Port Connection all models Buttons Front Panel Indicator Lights Front Panel Other UPS Features Rear Panel Basic Operation Storage ServiceRegulatory Compliance Identification Numbers Procedure