You can use Table D as a guide to determine the necessary wire gauge (AWG) for various cable distances that provide 24 VAC power. Or use it in a reverse fashion to determine the maximum allowable cable distance for a particular wire gauge. Table D applies when using
The minimum acceptable voltage is calculated as follows:
24.0VAC
21.6(Minimum Acceptable Voltage)
The minimum acceptable voltage used to create Table D was 21.6 V. Therefore, the
|
|
|
|
|
|
| Table D. Required Wire Gauge |
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
| Required Wire Gauge Table (AWG) |
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
| Equipment Loads (VA) |
|
|
|
|
|
|
|
|
|
|
| ||||