Specifications
PROFIBUS DP Connector
| Interface | DB9 connector |
| Transmission | High-speed RS-485 |
| method |
| Transmission cable | Shielded twisted pair cable |
| Electrical isolation | 500V DC |
Communication
Message type | Loop-type data exchange |
Equipment ID | 0AFE (hex) |
| Serial transmission | 9.6kbps; 19.2kbps; 93.75kbps; 187.5kbps; 500kbps; 1.5Mbps; 3Mbps; 6Mbps; |
| speed supported |
| 12Mbps (bits per second) |
| (auto-detection) |
| |
| Environment | |
| Standards | IEC 61131-2,UL508 |
| Storage/operation | Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity) |
| Operation: 0°C ~ 55°C (temperature), 50 ~ 95% (humidity), pollution degree 2 |
| |
| Shock/vibration | International standards: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC |
| immunity | 68-2-27 (TEST Ea) |
| Interference | RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 1000MHz, 1.4GHz ~ 2GHz, 10V/m |
| EFT (IEC 61131-2, IEC 61000-4-4): Analog & Communication I/O: 1KV |
| immunity |
| ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge |
| |
| Certificates | CE, UL |
Connecting to PROFIBUS DP Connector
Insert the PROFIBUS DP bus connector into
the PROFIBUS DP connector on
DVPPF02-H2. Screw it tight to ensure
DVPPF02-H2 and the PROFIBUS DP bus
are properly connected.
Installation & Wiring
1. | Install DVPPF02-H2 in an enclosure with sufficient | D | D |
| space around it to allow heat dissipation (see the | | |
| figure). | EH2 PLC | PF0 2- H2 |
2. | D | | D |
DO NOT place the I/O signal wires and power | | |
| supply wire in the same wiring circuit. | D | D |
D>5 0mm
Control Register
The control registers (CR) are the registers inside DVPPF02-H2. See the table below for the definitions of all the CRs. DVP-EH2 series PLC MPU can read or write the CR allowed through DFROM/DTO instructions.
| | | 注意事項 | | | | | | |
| | | | | | | | | | | | |
| | | | | | | | | | | | |
| 配線時 | | 關閉電源。 | | | | | | |
| 本使用說明書僅提供電氣規格、功能規格、安裝配線、故障排除及周邊裝置部分說明,本使用說明書僅DVPPF02-H2PROFIBUS DP |
| | | | PROFIBUS DP | | | | | 協定的詳細內容這裏不作介紹。如果讀者想瞭 |
| | | | | | | | | | | | |
| 殼機配為線開箱放內型。機另殼必,須因具此備保護者措使施用(本如機:時特,殊必的須工將具其或安鑰裝匙於才具可防打塵開、),防防潮止及非免維於護電人擊員∕操衝作擊或意意外外的衝外 |
| | | | | | | | | | | | |
| | 產品用來控制運轉中的機械及設備。為避免損壞本產品,只有合格且熟悉本產品結構及操作的專業人 |
| | | | | | | | | | | | |
| 交流輸入電源不可連接於輸入∕輸出信號端 | 否則可能造成嚴重損壞。請在上電前再次確認電源配線, |
| | | | | | | | | 務必正確的接地,以提高產品抗雜訊能力。 |
| | 產品簡DVPPF02介 -H2 | | DVPPF02-H2 | PROFIBUS DP | |
PROFIBUS DP | | DVP-EH2 | PLC | | | DVPPF02-H2 | 通訊模組,可用於DVP-EH2 |
| | | DVP-EH2 | | | | | | | 主機連 |
| 使用前 | | 仔細閱讀本 | 手冊 並依照本手冊指示進行操作,以免造成產品受損或人員受傷。 |
1. | |
| | DP | | | | | | | | |
2. | | | | 請務必 | | | GSD | | | | |
| PROFIBUS DP | | | | | |
| 作為 | | | | 操作指南和入門參考, | | | | | |
| 解更多 | | | 協定使用的內容,請參閱相關專業文章或書籍資料。 | |
| 擊本體,造成危險及損壞。 | | | | | | |
| 員才可進行本產品的安裝、操作、配線及維護。 | | | |
| 且請勿在上電時觸摸任何端子。本體上的接地端子 | | | |
Components
PROFIBUS DP Connector
To connect to PROFIBUS DP network, use standard DP connector for the wiring.
Content
Model name
Firmware version
Length of I/O data
DVPPF02-H2 model code = H’0250
Displaying the current firmware version in hex, e.g. V1.00 is indicated as H’0100.
Length of output I/O data Length of input I/O data
3. | PROFIBUS DP | | 4 (slot) | | | | |
4. | | | | | | 12Mbps | | | | |
5. | I/O | | | | PROFIBUS DP | | , | | 100 | word |
| 4 | slot | | | | | 100 | word 4 slot | | , |
6. | | | | | 網路通訊模組。 | 定義為 | 配置長度之和)。 |
謝謝您使用台達 | | 無需外接電源,與 | | |
接好後由 | | 網路與 | 系列 | 主機的連接, | | | |
| | 主機提供電源。 | | | | | |
PIN name
-
-
Rxd/Txd-P
-
DGND
VP
-
Rxd/Txd-N
-
Definition
Not defined
Not defined
Sending/receiving data P(B)
Not defined
Data reference potential
Power voltage - positive
Not defined
Sending/receiving data N(A)
Not defined
#3 ~ #102
#103 ~ #202
#203 ~ #206
#207 ~ #250
#251
#252 ~ #383
#384 ~ #511
Input data mapping
Output data mapping
Error
Area for storing data from DVPPF02-H2 to PROFIBUS DP master
Area for storing data from PROFIBUS DP master to DVPPF02-H2.
Set up by the system. DO NOT use it.
Reserved
Register for storing errors. See for error codes.
Reserved
Set up by the system. DO NOT use it.
| | | | | | | | | | | | | | | | |
| | | | | | 3 | | | | | | | 1 | | | |
| | | | 1 6 | | | | | | | | | | | |
| 2 | | | 1 6 | | 4 | | | | | | | 2 | | | |
| | | | 色40 [1.575] | | | | | | | | 3 | POWER LED | |
| 6 | | | 1 | | | | | | | 4 | NET LED | | |
| | ] | | | | | | | | | |
| | [3 5.43 | | | | | | 8 | | |
| | | | | | | | | | 5 | PROFIBUS DP | |
| | 90 | | | | | | | | | 6 | | | |
| 5 | | | | | | | | | | | | |
| | | | | | | | | | | 7 | DIN | | |
| | 6] | | | | 82 [3.228] | | 7 | | 8 | DIN | | |
| | | | | | | | | |
| | 27 | | | | | | | | | | | | |
| 功能特. | | | | | | | | | | | |
| | 0 | 主站與多個從站之間的迴圈資料傳輸。 | | | | | | | |
| | [ | | | | | | | |
| | 7 | | | | | | | |
| 支持 | | | | | | | |
| 在 | | | | 網路配置工具中 | mm | 槽 | 文檔。 | | | | | | |
| | | | | | | | | | |
| | | | | 。 | 配置。 | | | | | | |
| 自動偵測通訊速率,最高通訊速率支援 | | | 輸入資料長度總和最大可配置 | 個 |
| | 資料長度可通過 | | 網路配置工具自由 |
| ( 個 | | 配置長度之和),輸出資料長度總和最大可配置 | | 個 | | ( 個 | | |
| 錯誤碼診斷功能。 | | | | | | | | | | | |
| 產品外觀及各部介紹 | | | | | | | | 位址設定開關埠 | |
| | | | | | | | | | | | | | | 指示燈 | |
| | | | | | | | | | | | | | | 指示燈 | |
| | | | | | | | | | | | | | 擴充模組連接 | |
Warning
Please read this instruction sheet carefully before use and follow this instruction to operate the device in order |
to prevent damages on the device or injuries to staff. |
Switch off the power before wiring. |
This instruction sheet only provides introductory information on electrical specification, functions, wiring, |
trouble-shooing the peripherals for DVPPF02-H2. Details of PROFIBUS DP protocol are not included in this |
sheet. For more information on PROFIBUS DP protocol, please refer to relevant reference or literatures. |
DVPPF02-H2 is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust, |
humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the |
device (e.g. key or specific tools are required to open the enclosure) in case danger and damage on the device |
may occur. |
DVPPF02-H2 is to be used for controlling the operating machine and equipment. In order not to damage it, |
only qualified professional staff familiar with the structure and operation of if can install, operate, wire and |
maintain it. |
Address Setup Rotary Switch
The two rotary address setup switches set up the node addresses on | | |
PROFIBUS DP network in hexadecimal form. Setup range: 0x01 ~ 0x7D (0 or | 1 | RESS |
0x7E ~ 0xFF are forbidden). | | | | x1 6 |
| | | | DE ADD |
| | | | | | 0 |
Rotary switch | | | x 161 | | x 160 | x1 6 | NO |
Multiple | | | × 16 | | × 1 | | |
Example: If you need to set the node address of DVPPF02-H2 as 26 (1A Hex), simply switch the corresponding rotary switch of x161 to “1" and the corresponding rotary switch of x160 to”A”.
| | Switch setting | | | | | | Description | Note: The changed values on switches are |
| | 0x01 ~ 0x7D | | Valid PROFIBUS DP address | only valid when DVPPF02-H2 is re-powered. |
| | | When DVPPF02-H2 is operating, changing |
| 0 or 0x7E ~ 0xFF | | Invalid PROFIBUS DP address | the set value of the address will be regarded |
| | invalid. |
| | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
LED Indicators & Trouble-Shooting
There are 2 LED indicators on DVPPF02-H2. POWER indicator displays the status of the working power. NET indicator displays the connection status of the communication.
POWER LED
LED status | | Indication | | | How to deal with it? |
Green light on | | The power is normal. | | -- | |
| | | | | |
| | | | 1. | Check if the power of DVP-EH2 is normal. |
Off | | No power | | 2. | Check if the connection between DVPPF02-H2 |
| | | | | and DVP-EH2 is normal. |
NET LED
| | | | | | | 通訊連接器 |
PROFIBUS DP | | | | | | |
| | DB9 | | | | |
| | | RS-485 | | | |
| | 500V DC | | | |
| | | | . | | |
| | | | | | |
ID | | 0AFE (hex) | | | 頭 |
| | | | | |
| | | 9.6kbps; 19.2kbps; 93.75kbps; 187.5kbps; 500kbps; 1.5Mbps; 3Mbps; 6Mbps; |
| | 支持 | | | 固定扣 | |
功能規格 | 12Mbps | | 軌槽 | | |
尺寸單位: | | | |
| 連接器 | | | | | |
DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. |
Check all the wiring again before switching on the power, and DO NOT touch any terminal when the power is |
switched on. Make sure the ground terminal | is correctly grounded in order to prevent electromagnetic |
interference. | |
Introduction | |
Thank you for choosing Delta DVPPF02-H2 PROFIBUS DP communication module. DVPPF02-H2 can be applied to the connection with DVP-EH2 series PLC MPU in a PROFIBUS DP network. DVPPF02-H2 does not need to be connected to an external power supply. The power will be supplied from DVP-EH2 once it is connected to DVP-EH2.
Extension Port
The extension port on DVPPF02-H2 is used for the connection to the next DVPPF02-H2 or extension modules of DVP-EH2 series PLC MPU.
Basic Operation
Connecting DVPPF02-H2 to DVP-EH2 Series PLC MPU
LED status
Off
Red light on
Red light flashes
Indication
No power
DVPPF02 is operating but is not connected to PROFIBUS DP bus.
Depending on the value in CR#251
How to deal with it?
1.Check if the power of DVP-EH2 is normal
2.Check if the connection between DVPPF02-H2 and DVP-EH2 is normal
Check if DVPPF02-H2 is normally connected to PROFIBUS DP bus.
See the error code table for how to deal with it.
接頭 | | IEC 61131-2,UL508 | | |
| | -25°C ~ 70°C | 5 ~ 95% | |
| | 0°C ~ 55°C | 50 ~ 95% | 2 |
| | | IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27 |
| (TEST Ea) | | | |
| RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 1000MHz, 1.4GHz ~ 2GHz, 10V/m |
| EFT (IEC 61131-2, IEC 61000-4-4): Analog & Communication I/O: 1KV |
| ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge | |
方式 | 高速 | 接頭 | | | |
| 雙絞線 | | | |
傳輸電纜 | 遮罩 | | | |
電氣隔離 | 迴圈式資料交換 | | |
通訊 | | | |
資訊類型 | | |
設備 | | | | | |
支援串列傳輸速度 | | | | | |
Features |
1. Supports loop-type data exchange between DP master and many slaves. |
Switch off DVP-EH2. Open the connection
port on the right hand side of DVP-EH2 and
connect DVPPF02-H2 to DVP-EH2. Switch
DVPPF02-H2 is in data exchange status.
2. | Supports GSD files in PROFIBUS DP network configuration tools. |
3. | Supports 4 slots in PROFIBUS DP network configuration tools. |
4. | Auto-detects baud rates; supports Max. 12Mbps. |
5. | The length of I/O data can be freely configured through PROFIBUS DP network configuration tools. |
| Max. input data length = 100 words (the sum of 4 slots); Max. output data length = 100 words (the |
| sum of 4 slots). |
on DVP-EH2, and DVP-EH2 will supply
power to DVPPF02-H2. There is no need to
connect DVPPF02-H2 to an external power
supply.
Error Codes
CodeDescription
00 | DVPPF02-H2 operates normally. |
| |
| |
| |
| |
| |
| |
| | | |
PROFIBUS DP | | | |
PROFIBUS DP | | PROFIBUS DP | |
標準 | 儲存 | 標準 | (濕度) |
操作∕儲存環境 | (溫度), |
耐震動∕衝擊 | 操作: | (溫度), | (濕度),污染等級 |
國際標準規範 | | |
6. Error code diagnosis. |
Product Profile & Outline |
Installing DVP-EH2 and DVPPF02-H2 on DIN Rail
02 | PROFIBUS DP watch dog error |
Send your DVPPF02-H2 back to the factory for repair.
Check if DVPPF02-H2 is normally connected to PROFIBUS DP bus.
Set the address within the range 0x01 ~ 0x7D and re-power DVP-EH2.
Check if the power voltage of DVP-EH2 is normal; check if DVPPF02-H2 is normally connected to DVP-EH2.
Send your DVPPF02-H2 back to the factory for repair.