Mitsubishi Electronics MELSECNET/H Performance Specifications, ZDifferences from QJ71LP21-25

Page 3

zDifferences from QJ71LP21-25

The QJ71LP21S-25 has the same function and performance as the QJ71LP21-25. Therefore, the program for the QJ71LP21-25 is available for the QJ71LP21S-25.

However, the QJ71LP21S-25 requires two I/O slots while the Q71LP21-25 requires only one I/O slot.

[Performance Specifications]

 

Item

QJ71LP21S-25

Maximum number

 

LX/LY

8192 points

of link points per

 

LB

16384 points (In MELSECNET/10 mode: 8192 points)

network

 

 

LW

16384 points (In MELSECNET/10 mode: 8192 points)

Maximum number of

link points per

((LY + LB) /8 + (2 × LW) 2000 bytes

station

 

 

 

 

 

 

 

Communication speed

25 Mbps/10 Mbps (Selectable by mode switch)

Number of connectable stations per

64 stations (control station: 1, normal station: 63)

network

 

 

 

 

 

 

 

Connection cable

 

Optical fiber cable *1

Overall distance

 

30 km (98430 ft.)

 

 

 

 

Sl optical cable:200 m (656.2 ft.)

 

 

 

25Mbps

H-PCF optical cable :400m (1312.4 ft.)

 

 

 

Broad-band H-PCF optical cable :1 km (3281 ft.)

Distance between

 

 

 

 

QSl optical cable:1 km (3281 ft.)

stations

 

 

 

Sl optical cable: 500 m (1640.5 ft.)

 

 

 

10Mbps

SI type H-PCF optical cable :1 km (3281 ft.)

 

 

 

Broad-band H-PCF optical cable :1 km (3281 ft.)

 

 

 

 

 

 

 

 

QSl optical cable:1 km (3281 ft.)

Maximum number of

networks

239 (Total including number of remote I/O networks)

Maximum number of groups

32 (In MELSECNET/10 mode: 9)

Transmission path format

Duplex loop

Communication method

Token ring

Synchronous method

Frame synchronous method

Encoding method

 

NRZI (Non Return to Zero Inverted) code

Transmission format

 

Conforms to HDLC (Frame type)

Error control system

 

Retries based on CRC (X16+X12+X5+1) and timeover

 

 

 

 

y Loopback function due to error detection and cable breakage

RAS function

 

 

 

y Link line self-diagnostic function

 

 

 

y Prevention of system failure by switching to alternative control station

 

 

 

 

 

 

 

 

y Error detection using special relays and registers

 

 

 

 

y N-to-N communication (monitoring, program up/downloading, etc.)

Transient transmission

y Various send/receive instructions from sequence programs

(ZNRD/ZNWR,SEND/RECV,RECVS,READ/WRITE,SREAD/SWRITE,

 

 

 

 

REQ,RRUN/RSTOP,RTMRD/RTMWR)

 

 

 

 

y Send function by addressing to channel number of 1 to 8

Special cyclic transmission function

y Low-speed cyclic transmission function

No. of occupied I/O points

48 points (I/O assignment: first 16 points as empty, last 32 points as intelligent) *2

 

Voltage

20.4 to 31.2 V DC

External

Current

0.20 A

Terminal screw size

M3 screw

supply

Applicable solderless

R1. 25-3

power

terminal

 

 

Applicable wire size

0.3 to 1.25 mm2

 

Tightening torque

42 to 58Nycm

Internal current consumption (5 VDC)

0.55 A

Weight

 

 

 

0.20kg

*1: For conventional optical fiber cable (A-2P-), the distance between stations varies with the type L and H.

*2: Two I/O slots are occupied.

The head I/O address should be the number added on 10H to the head address of installed slot, because the first slot occupies 16 points as a vacant and the second slot occupies 32 points for the automatic I/O assignment. It is available to assign zero for the first slot.

(Example)

When installing the module to slot 0, set 10H to “Start I/O No.”

(When 0 point is set for slot 0 in the I/O assignment, set 0H to “Start I/O No.”)

3

Image 3
Contents New Network system using only QJ71LP21-25 FeaturesZDifferences from QJ71LP21-25 Performance SpecificationsManual Packing list