zDifferences from QJ71LP21-25
The
However, the
[Performance Specifications]
| Item | ||||
Maximum number |
| LX/LY | 8192 points | ||
of link points per |
| LB | 16384 points (In MELSECNET/10 mode: 8192 points) | ||
network |
|
| LW | 16384 points (In MELSECNET/10 mode: 8192 points) | |
Maximum number of | link points per | ((LY + LB) /8 + (2 × LW) ≤ 2000 bytes | |||
station |
|
|
| ||
|
|
|
| ||
Communication speed | 25 Mbps/10 Mbps (Selectable by mode switch) | ||||
Number of connectable stations per | 64 stations (control station: 1, normal station: 63) | ||||
network |
|
|
| ||
|
|
|
| ||
Connection cable |
| Optical fiber cable *1 | |||
Overall distance |
| 30 km (98430 ft.) | |||
|
|
|
| Sl optical cable:200 m (656.2 ft.) | |
|
|
| 25Mbps | ||
|
|
| |||
Distance between |
|
| |||
|
| QSl optical cable:1 km (3281 ft.) | |||
stations |
|
|
| Sl optical cable: 500 m (1640.5 ft.) | |
|
|
| 10Mbps | SI type | |
|
|
| |||
|
|
|
| ||
|
|
|
| QSl optical cable:1 km (3281 ft.) | |
Maximum number of | networks | 239 (Total including number of remote I/O networks) | |||
Maximum number of groups | 32 (In MELSECNET/10 mode: 9) | ||||
Transmission path format | Duplex loop | ||||
Communication method | Token ring | ||||
Synchronous method | Frame synchronous method | ||||
Encoding method |
| NRZI (Non Return to Zero Inverted) code | |||
Transmission format |
| Conforms to HDLC (Frame type) | |||
Error control system |
| Retries based on CRC (X16+X12+X5+1) and timeover | |||
|
|
|
| y Loopback function due to error detection and cable breakage | |
RAS function |
|
|
| y Link line | |
|
|
| y Prevention of system failure by switching to alternative control station | ||
|
|
|
| ||
|
|
|
| y Error detection using special relays and registers | |
|
|
|
| y | |
Transient transmission | y Various send/receive instructions from sequence programs | ||||
(ZNRD/ZNWR,SEND/RECV,RECVS,READ/WRITE,SREAD/SWRITE, | |||||
|
|
|
| REQ,RRUN/RSTOP,RTMRD/RTMWR) | |
|
|
|
| y Send function by addressing to channel number of 1 to 8 | |
Special cyclic transmission function | y | ||||
No. of occupied I/O points | 48 points (I/O assignment: first 16 points as empty, last 32 points as intelligent) *2 | ||||
| Voltage | 20.4 to 31.2 V DC | |||
External | Current | 0.20 A | |||
Terminal screw size | M3 screw | ||||
supply | Applicable solderless | R1. | |||
power | terminal | ||||
| |||||
| Applicable wire size | 0.3 to 1.25 mm2 | |||
| Tightening torque | 42 to 58Nycm | |||
Internal current consumption (5 VDC) | 0.55 A | ||||
Weight |
|
|
| 0.20kg |
*1: For conventional optical fiber cable
*2: Two I/O slots are occupied.
The head I/O address should be the number added on 10H to the head address of installed slot, because the first slot occupies 16 points as a vacant and the second slot occupies 32 points for the automatic I/O assignment. It is available to assign zero for the first slot.
(Example)
When installing the module to slot 0, set 10H to “Start I/O No.”
(When 0 point is set for slot 0 in the I/O assignment, set 0H to “Start I/O No.”)