MITSUBISHI
ELECTRIC
9800A SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
UA817 | EMERGENCY STOP | Emergency stop applied | - | - | Alarm | - | |
ACTIVATED | |||||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
UA819 | REMOTE START | There is an error with the remote | CALL SERVICE | [1] | Alarm | - | |
BUTTON ABNORMAL | start switch. | ENGINEER | |||||
|
|
|
| ||||
|
|
|
|
|
|
| |
UA820 | REMOTE STOP BUTTON | There is an error with the remote | CALL SERVICE | [1] | Alarm | - | |
ABNORMAL | stop switch. | ENGINEER | |||||
|
|
|
| ||||
|
|
|
|
|
|
| |
UA824 | CB2 OPEN | Battery disconnect circuit breaker | TURN ON CB2 | [1] | Alarm | - | |
CB2 turned OFF | |||||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
UA831 | EMERGENCY BYPASS | Emergency bypass switch turned | - | [1] | Alarm | - | |
SWITCH ON | to <Emergency> | ||||||
|
|
|
|
| |||
|
|
|
|
|
|
| |
| BATTERY DEPLETED | DC voltage dropped below |
|
|
|
| |
UA834 | discharge end during inverter | - | - | Alarm | - | ||
INV. STOPPED | |||||||
| operation |
|
|
|
| ||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
UA841 | CONVERTER OPE. | Converter operation interlock | - | - | Alarm | - | |
PROHIBITION | applied | ||||||
|
|
|
|
| |||
|
|
|
|
|
|
| |
UA842 | OUTPUT CIRCUIT | Load bus voltage sensor | - | - | Alarm | - | |
ABNORMAL | abnormality | ||||||
|
|
|
|
| |||
|
|
|
|
|
|
|
#1: It has the possibility that output
MITSUBISHI ELECTRIC 9800A SERIES UPS