Mitsubishi Electronics 9800A SERIES technical manual Inverter Voltage

Page 65

MITSUBISHI

ELECTRIC

9800A SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

6-4

UF305

UPS CONTROL CIRCUIT

Control clock abnormality

CALL SERVICE

[2]

Major

Lit on

ERROR

ENGINEER

 

 

 

 

 

 

 

 

 

 

 

 

UF306

UPS CONTROL CIRCUIT

Control power source circuit

CALL SERVICE

[2]

Major

Lit on

ERROR

abnormality

ENGINEER

 

 

 

 

 

 

 

 

 

 

 

UF309

INVERTER VOLTAGE

Inverter output voltage abnormality

CALL SERVICE

[2]

Major

Lit on

ABNORMAL

before inverter power supply

ENGINEER

 

 

 

 

 

 

 

 

 

 

 

UF352

CONTROL POWER

Control circuit abnormality

CALL SERVICE

[1]

Minor

Flicker

SUPPLY ABNORMAL

ENGINEER

 

 

 

 

 

 

 

 

 

 

 

 

UF402

52S ABNORMAL

52S not turned OFF, or 52S turned

CALL SERVICE

[2]

Major

Lit on

OFF without any command

ENGINEER

 

 

 

 

 

 

 

 

 

 

 

 

UF403

CB3 ABNORMAL

CB3 not turned OFF

CALL SERVICE

[2]

Major

Lit on

(#2)

ENGINEER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

52S not turned ON, or 52S turned

CALL SERVICE

 

 

 

UF451

52S ABNORMAL

ON without any command when

[1]

Minor

Flicker

ENGINEER

 

 

manual transfer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF452

CB3 ABNORMAL

CB3 open

CALL SERVICE

[1]

Minor

Flicker

ENGINEER

 

 

 

 

 

 

 

 

 

 

 

 

 

UF453

52L OPERATION ERR.

52L operated abnormality

CHECK 52L

[2]

Major

Lit on

 

 

 

 

 

 

 

 

AC INPUT VOLTAGE OUT

AC input voltage fell out of +/- 15%

CHECK INPUT

 

 

 

UA801

POWER

[1]

Alarm

-

OF RANGE

range

 

SOURCE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INVERTER OVERLOAD

 

WARNING :

 

 

 

UA806

Overload exceeded 105% (Note 7)

DECREASE

[1]

Alarm

-

> 100%

 

 

LOAD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INVERTER OVERLOAD

 

WARNING :

 

 

 

UA808

Overload exceeded 125% (Note 7)

DECREASE

[1]

Alarm

-

> 125%

 

 

LOAD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INVERTER OVERLOAD

 

WARNING :

 

 

 

UA809

Overload exceeded 150% (Note 7)

DECREASE

[1]

Alarm

-

> 150%

 

 

LOAD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Momentary over-current during

WARNING :

 

 

 

UA810

INVERTER OVERLOAD

DECREASE

[1]

Alarm

-

Inverter power.

 

 

LOAD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UA811

OVERLOAD TRANS.

Overload transfer

-

[1]

Alarm

 

 

 

 

 

 

 

 

UA812

BYPASS VOLTAGE OUT

Bypass voltage fell out of +/- 20%

CHECK

[1]

Alarm

-

OF RANGE

range

BYPASS INPUT

 

 

 

 

 

 

 

 

 

 

 

UA813

BYPASS PHASE

Phase rotation is inverted when

CHECK

[1]

Alarm

-

ROTATION ERROR

bypass voltage is normal

BYPASS INPUT

 

 

 

 

 

 

 

 

 

 

 

 

BYPASS FREQUENCY

Bypass frequency fell out of

CHECK

 

 

 

UA814

inverter synchronization follow-up

[1]

Alarm

-

OUT OF RANGE

BYPASS INPUT

 

range

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MITSUBISHI ELECTRIC 9800A SERIES UPS

Image 65
Contents ALN-H0776 For parallel operation possible model onlyPreface Parts Replacement Table of ContentsList of Tables List of Figures How to use this Manual Introduction Important Safety Instructions Retain These InstructionsMitsubishi 9800A Series UPS General Mitsubishi 9800A Series UPS Overview Static Transfer Single Line Diagram Battery Operation 52S CUPS Parts Location 500kVA DUPS Parts Location 750kVA SYNC.LED Mitsubishi 9800A Series UPS Specifications Environmental InputRating of Contactors and Fuses 540V Operator Controls and IndicatorsLoad on bypass Load on Bypass green Battery operation Battery OP. yellowLED Display Load on inverter Load on Inverter green Start/Stop screen Figure Liquid Crystal DisplayMenu Measurement Menu Figure Start/Stop screenSetup Menu Figure 11 Main screen Input Power Failure13 Main screen Fault indication Fault Indication FigureTN1 External Signal Terminal Block52L AX 52C AX TN216 Control Wiring for External Contacts Output Contacts for external alarm annunciationTerminals 3 to 4 Remote Inverter Stop input terminal IN2 Input Contacts for remote access of UPSTerminals 5 to 6 Battery Temp. High contact input IN3 External communication connector Terminals 7 to 8 Power Demand Command contact input IN4Mitsubishi Electric 9800A Series UPS Mitsubishi 9800A Series UPSElectric Owners / Technical Manual External Battery SupplyProcedure for Cable Connections Mitsubishi 9800A Series UPS Mitsubishi 9800A Series UPS Recommended Cable Sizes Crimp Type Compression Lug UPS module Auxiliary Negative +Positive Input UPS module Cabinet Input Cabinet Bypass Output Input A50,B50,C50 A40,B40,C40 Mitsubishi 9800A Series UPS Input Input Cabinet UPS module Wall mounted DC breaker UPS Floor mounted DC breaker Input cabinet UPS module Auxiliary N50 Rectifier Cabinet Critical Load Cabinet IOAU-04 Critical Load CabinetUPS-1 AC Output UPS-2 AC OutputUPS-2 IOAU-04 TN2 UPS-1 IOAU-04 TN2A Start-up Procedure Operating Procedures Start-up ProcedureB Shut-down Procedure Shut-down ProcedureUPS-1 Bypass Operation ProcedureElectric Owners / Technical Manual Response to UPS Failure UPS FaultUPS Component Parts Battery Contact Mitsubishi Electric Automation, Inc. at Fault CodesNumber Mitsubishi ElectricIgbt Fault a Inverter Voltage Emergency Stop Mitsubishi Electric 9800A Series UPS Mitsubishi Electric Automation Inc 847