MITSUBISHI
ELECTRIC
9800A SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
UF305 | UPS CONTROL CIRCUIT | Control clock abnormality | CALL SERVICE | [2] | Major | Lit on | |
ERROR | ENGINEER | ||||||
|
|
|
|
| |||
|
|
|
|
|
|
| |
UF306 | UPS CONTROL CIRCUIT | Control power source circuit | CALL SERVICE | [2] | Major | Lit on | |
ERROR | abnormality | ENGINEER | |||||
|
|
|
| ||||
|
|
|
|
|
|
| |
UF309 | INVERTER VOLTAGE | Inverter output voltage abnormality | CALL SERVICE | [2] | Major | Lit on | |
ABNORMAL | before inverter power supply | ENGINEER | |||||
|
|
|
| ||||
|
|
|
|
|
|
| |
UF352 | CONTROL POWER | Control circuit abnormality | CALL SERVICE | [1] | Minor | Flicker | |
SUPPLY ABNORMAL | ENGINEER | ||||||
|
|
|
|
| |||
|
|
|
|
|
|
| |
UF402 | 52S ABNORMAL | 52S not turned OFF, or 52S turned | CALL SERVICE | [2] | Major | Lit on | |
OFF without any command | ENGINEER | ||||||
|
|
|
|
| |||
|
|
|
|
|
|
| |
UF403 | CB3 ABNORMAL | CB3 not turned OFF | CALL SERVICE | [2] | Major | Lit on | |
(#2) | ENGINEER | ||||||
|
|
|
|
| |||
|
|
|
|
|
|
| |
|
| 52S not turned ON, or 52S turned | CALL SERVICE |
|
|
| |
UF451 | 52S ABNORMAL | ON without any command when | [1] | Minor | Flicker | ||
ENGINEER | |||||||
|
| manual transfer |
|
|
| ||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
UF452 | CB3 ABNORMAL | CB3 open | CALL SERVICE | [1] | Minor | Flicker | |
ENGINEER | |||||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
UF453 | 52L OPERATION ERR. | 52L operated abnormality | CHECK 52L | [2] | Major | Lit on | |
|
|
|
|
|
|
| |
| AC INPUT VOLTAGE OUT | AC input voltage fell out of +/- 15% | CHECK INPUT |
|
|
| |
UA801 | POWER | [1] | Alarm | - | |||
OF RANGE | range | ||||||
| SOURCE |
|
|
| |||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
| INVERTER OVERLOAD |
| WARNING : |
|
|
| |
UA806 | Overload exceeded 105% (Note 7) | DECREASE | [1] | Alarm | - | ||
> 100% | |||||||
|
| LOAD |
|
|
| ||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
| INVERTER OVERLOAD |
| WARNING : |
|
|
| |
UA808 | Overload exceeded 125% (Note 7) | DECREASE | [1] | Alarm | - | ||
> 125% | |||||||
|
| LOAD |
|
|
| ||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
| INVERTER OVERLOAD |
| WARNING : |
|
|
| |
UA809 | Overload exceeded 150% (Note 7) | DECREASE | [1] | Alarm | - | ||
> 150% | |||||||
|
| LOAD |
|
|
| ||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
|
| Momentary | WARNING : |
|
|
| |
UA810 | INVERTER OVERLOAD | DECREASE | [1] | Alarm | - | ||
Inverter power. | |||||||
|
| LOAD |
|
|
| ||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
UA811 | OVERLOAD TRANS. | Overload transfer | - | [1] | Alarm |
| |
|
|
|
|
|
|
| |
UA812 | BYPASS VOLTAGE OUT | Bypass voltage fell out of +/- 20% | CHECK | [1] | Alarm | - | |
OF RANGE | range | BYPASS INPUT | |||||
|
|
|
| ||||
|
|
|
|
|
|
| |
UA813 | BYPASS PHASE | Phase rotation is inverted when | CHECK | [1] | Alarm | - | |
ROTATION ERROR | bypass voltage is normal | BYPASS INPUT | |||||
|
|
|
| ||||
|
|
|
|
|
|
| |
| BYPASS FREQUENCY | Bypass frequency fell out of | CHECK |
|
|
| |
UA814 | inverter synchronization | [1] | Alarm | - | |||
OUT OF RANGE | BYPASS INPUT | ||||||
| range |
|
|
| |||
|
|
|
|
|
| ||
|
|
|
|
|
|
|
MITSUBISHI ELECTRIC 9800A SERIES UPS