[Function]
(1) Data communication function (TCP/IP Communication and UDP/IP Communication)
Communication Function | Description | QnA series | A series | ||
Using read/write data in the PLC CPU | Reads/writes PLC CPU data from/to an external device. | ! | ! | ||
|
|
|
|
| |
Using fixed | Procedure exist | Reads/writes any data between PLC CPU and an external device | ! | ! | |
buffers | No Procedure | using fixed buffer of the Ethernet modules. | |||
|
| ||||
Using random access buffers | Exchanges data with multiple external devices, using the Ethernet | ! | ! | ||
random access buffers. (no need to specify external device) | |||||
|
|
|
| ||
Using data link instructions | Reads/writes PLC CPU data of other stations via the Ethernet | ! | N/A | ||
using data link instructions. | |||||
|
|
|
| ||
File transfer (FTP Server Function) | Reads/writes files in the local station using the FTP server | ! | N/A | ||
function, from an external device. | |||||
|
|
|
|
(2) Other functions
Function | Description |
| QnA series | A series |
| Data communication is enabled over a network system where |
|
| N/A |
MELSECNET/10 relay communication | Ethernet and MELSECNET/10 or multiple Ethernet networks are |
| ! | |
| present. |
|
|
|
Router relay communication (Router | Communicates data via routers and gateways. (Ethernet module |
| ! | ! |
relay function) | does not function as a router.) |
| ||
|
|
| ||
External device existence confirmation | Checks whether or not the external device operates normally after |
| ! | ! |
| communication has been established (open processing). |
|
|
|
Paring open communication | Receiving connection and transmitting connection are opened as a |
| ! | ! |
single pair. (For fixed buffer communication.) |
| |||
|
|
|
| |
Communication using automatic open | Communication is enabled automatically after initial processing is |
| ! | N/A |
UDP port | completed of local station Ethernet module. (Opening and closing |
| ||
by a sequence program is unnecessary.) |
|
|
| |
|
|
|
| |
| Data is broadcasted simultaneously to all stations on the same |
|
|
|
Simultaneous broadcast | Ethernet network where the Ethernet module is located. (Using |
| ! | ! |
| UDP/IP) |
|
|
|
Access PLC CPU from GX Developer | using Ethernet connection. |
| ! | ! |
Please refer to the new module's User's Manual for the function versions and serial numbers of the products | !: Applicable | |||
(CPU module and GX Developer) related to the above functions. |
|
|
[Performance Specifications]
|
|
|
|
|
| Specification |
|
| ||
|
| Item |
| |||||||
|
|
| ||||||||
|
|
|
| |||||||
|
|
| 10BASE5 |
|
| 10BASE2 | 10BASE5 | 10BASE2 | ||
|
| Transmission speed |
|
|
| 10Mbps |
|
| ||
|
| Transmission method |
|
|
| Base band |
|
| ||
|
| Maximum | 2500m | - |
| 925m (3035ft.) | 2500m | - | 925m (3035ft.) | |
|
| distance | (8203ft.) |
| (8203ft.) | |||||
Transmission |
|
|
|
|
|
| ||||
| Maximum segment | 500m | 100m |
| 185m (607ft.) | 500m | 100m | 185m (607ft.) | ||
Specifications |
| length | (1641ft.) | (323ft.) (*1) |
| (1641ft.) | (323ft.) (*1) | |||
|
|
|
| |||||||
|
| Maximum number of | 100 units/ | Cascade |
|
| 100 units/ | Cascade | 30 units/ | |
|
| connection, |
| 30 units/ segment | connection, | |||||
|
| nodes per connection | segment |
| segment | segment | ||||
|
| maximum 4 |
|
| maximum 4 | |||||
|
|
|
|
|
|
|
| |||
|
| Minimum node interval | 2.5m (8.2ft.) | - |
| 0.5m (1.6ft.) | 2.5m (8.2ft.) | - | 0.5m (1.6ft.) | |
|
| Number of |
|
|
|
|
|
|
| |
Send/receive |
| simultaneously open |
| 8 connections (Connections usable by the sequence program) | ||||||
data storage |
| connections allowed |
|
|
|
|
|
|
| |
memory |
| Fixed buffer |
| 1k words ⋅ | 8 |
| 1k words ⋅ | 8 | ||
|
| Random access buffer |
| 6k words ⋅ | 1 |
| 3k words ⋅ | 2 | ||
Number of occupied I/O points |
|
|
| 32 points |
|
| ||||
|
|
| :0.48A | :0.48A | ||||||
5VDC current consumption | :0.56A | :0.56A | ||||||||
|
|
| ||||||||
|
|
| ||||||||
12VDC external supply power capacity | (*2) |
|
|
| (*2) |
|
| |||
(for transceiver) |
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
*1 Between hub and node.
*2 It is necessary to use a power supply that meets the specifications of the transceiver and AUI cable, considering the voltage drop (maximum 0.80V) in the module.
3