Elmo PSS 6U, PSS 3U manual Capacitor Reforming, LED Diagnostics

Page 17

Elmo PSS User Guide

Installation

MAN-PSSUG (Ver. 3.01)

 

 

 

3-4

3.3.2Capacitor Reforming

All PSS power supplies undergo capacitor reforming prior to shipment to the customer. However, if the power supply has been idle (at the customer site) for a period of nine months or more, the capacitors must be reformed before startup.

To perform capacitor reforming:

1.Connect a 25-VAC supply at the AC input terminals and a 100-W/220-V (or 50W/110-VAC) light bulb at the power output terminals.

2.Run the power supply for an hour and then increase the voltage to 50 VAC for an additional hour.

3.For higher-voltage types, run the supply for another hour at 100 VAC.

Noncompliance with these instructions may result in capacitor failure.

3.3.3LED Diagnostics

The following LEDs are mounted on the PSS:

LED

Indication

L1

(Vs)

Existence of internal supply.

L2

(SO)

Shunt is on.

L3

(In)

Shunt is inhibited.

Image 17
Contents PSS Important Notice Contents Safety Information Warranty Information Product Description Standard FeaturesFault Protection Technical Specifications Block DiagramPSS Power Supplies with Shunt Regulators Shunt Regulator SpecificationsDimensional Drawings 2PS1 Top View 1 PS1 for PSSF-20/100 and PSSF-20/2005PS2 Top View 2 PS2 for PSS-15/100 and PSS-12/2008PS3 Top View 3 PS3 for PSS-30/200 and PSSF-60/20011PSS Rack Mount 3U/12T Side View, Length Rack MountWiring Guidelines Mounting and Wiring the PSSAC Power Supplies Unpacking the System ComponentsVAC min VAC 0.9 x VAC max Wiring DiagramsSwitching from Single-phase to Three-phase 3U only Startup ProceduresCapacitor Reforming LED Diagnostics