Installation Sheet
RDM-SWM Switch Module 2400 W
The
Specifications
• Dimensions (HW): 10.00" x 2.75" (25.40 cm x 6.99 cm) |
• |
• Use wires rated at 75°C (167°F) |
• Torque terminals to 7 |
• Max. wire size: 10 AWG (4 mm²) |
• Wire stripping length: 0.28" (7 mm) |
Mounting points
Line in (hot)
Load out
• Weight: 0.5 lbs. (0.227 kg) | |
• | BTU/hr: 5 |
• | Control current: 85 mA @ 12 VDC |
Caution:
• All Class 1 wiring must be connected to proper terminals. |
• All control wiring must be connected to proper terminals. |
• Disconnect power while installing or connecting the unit. |
• Keep top and bottom air vents clear at all times. |
• Test loads for shorts before connecting. |
• Use |
• Use field installed copper conductors. |
Relay A
• All electrical ratings are for continuous duty. | |
• | For indoor use only. |
• | This module may require extra power from the AXlink connection or an |
| external power supply connected to the control card. |
Connecting the RDM-SWM to the AMX Lighting Master
Pin 4 (GND)
Pin 3 (RLY)
Pin 2 (DIM)
Pin 1 (+12 V)
3
1 (+)
NOTE: The
the
FIG. 1 RDM-SWM Switch Module
FIG. 2 RDM-SWM connections
•General purpose: 2400 W
•Resistive: 2400 W
•Ballast: 2400 W
•Motor: 277 VAC, 1 hp
Suggested Switched Loads
•Incandescent
•
•Motors
•Switched outlets
•Fluorescent