Altinex manual Operation, RS-232 Control, MX2214RM PIN No, RS-232 Protocol

Page 8

SWITCHERS

OPERATION

7

7.1 RS-232 CONTROL

The MX2214RM Switcher uses a Female 9-pin HD connector on its rear panel that allows access to a variety of control capabilities.

PIN No.

PIN Designation

1No connection

2RS-232 Transmit

3RS-232 Receive

4No connection

5Ground

6Multiple Switcher Loop Control

7Analog Switch Voltage Input

8+5 V (150 mA max)

9Analog Voltage Output

Figure 1: 9-pin D connector

It is generally recommended to select a single method of control for each application, as the activation of several different controls simultaneously may cause unpredictable results.

The majority of control systems and computers used in presentation system applications use the RS-232 communications standard.

To connect the MX2214RM Switcher to a control system or computer for RS-232 Control, only three pins are required on each port: Transmit (TX), Receive (RX), and Ground (GND). The Transmit pin from the control system or computer must be connected to the Receive pin of the switcher’s Control Port; do not connect Transmit to Transmit or Receive to Receive.

The following are typical cable wiring pin outs:

IBM PIN No.

MX2214RM PIN No.

3

2

2

3

7

5

Connection of IBM-PC 25-pin D to MX2214RM 9-pin D. Note: 5, 6, 20 shorted together in IBM side only.

IBM PIN No.

MX2214RM PIN No.

2

2

3

3

5

5

Connection of IBM-PC 9-pin D to MX2214RM 9-pin D. Note: 4, 6, 8 shorted together in IBM side only.

Port setting preferences for the control system or computer being used to control the switcher should be set as follows:

BAUD RATE (Bits per second)

2400

Data bits

8

Parity

None

Stop Bits

1

There is no software or hardware flow control implemented. The RS-232 input has a 6-character buffer and will not execute additional commands until the previous command is fully processed.

7.2 RS-232 PROTOCOL

[INP0]

All channels OFF

[INP1]

Select Input 1

[INP2]

Select Input 2

[INP3]

Select Input 3

[INP4]

Select Input 4

[RSET]

Reset unit to user defaults

[VERN]

Returns firmware version

 

numbers

Commands must be issued as shown, in ALL CAPS and with the brackets [ ] included in the command string. After processing a valid command, an [OK] string will be returned.

The [VERN] command will return the corresponding software version being used by the switcher, such as an error string. [ERR] will be returned if is error string is issued.

If the control system being used is not setup to wait for the [OK] string, it is important to include a 100 millisecond delay between each command.

The MX2214RM Switcher is also designed to send feedback commands from the switcher to the control system when the buttons on the front panel of the switcher are pressed.

7

Image 8
Contents MX2214RM Table of Contents IntroductionPrecautions / Safety Warnings About Your Switcher Technical SpecificationsDescription of MX2214RM Auto Switch Mode Button Reset ButtonPower UP Default SET Power SupplyApplication Diagram Installing Your Switcher CONGRATULATIONS! YOU are DoneOperation RS-232 ControlMX2214RM PIN No RS-232 ProtocolStand by Reset MASTER-SLAVE ConfigurationContact Closure ONE Wire Analog Control MX2214RM 9-pin DLoop Control with RS-232 Command Manual Loop ControlMX2214RM Loop NoneAccessories Control CablesMX2214RM Frequently Asked QuestionsTroubleshooting Guide Limited Warranty Altinex PolicyReturn Policy Contact Information